2020-12-18 09:42:19 | PLAN REVIEW / ELECTRICAL |
| |
| CHRISTOPHER S. THROOP, C.B.O. |
| PLANS EXAMINER BUILDING - PX3169 |
| PLANS EXAMINER 1&2 FAMILY - SFP306 |
| CONSTRUCTION SERVICES DIVISION |
| TEL: 561-805-6726 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| CODES IN EFFECT: |
| 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1 ADMINISTRATION |
| 2014 NEC |
| |
| 1ST REVIEW |
| |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| |
| 1. NEW EMERGENCY PANEL AND SUB PANEL SHOWN IN PANEL |
| SCHEDULE. PROVIDE A NEW ELECTRICAL RISER DIAGRAHM. |
| INCLUDE GROUNDING ELECTRODE SYSTEM. |
| PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF SERVICE |
| EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE, WIRE AND |
| BREAKER SIZES FOR SERVICE AND FEED TO ANY SUB-PANEL(S). |
| SHOW GEC SIZE AND SYSTEM, SHOW INTERSYSTEM BONDING |
| TERMINATION POINT. NEC 215.5, 230, 250.50, 250.94, |
| 408.30; FBC RE E3706.1, E3608.1, E3609.3; WPB FBC |
| 107.2.1 |
| |
| 2. PANEL SCHEDULE SUBMITTED FOR REVIEW DOES NOT INCLUDE |
| NEW RANGE AND HOOD CIRCUTS AND GAS W/H IGNITER CIRCUT. |
| ALSO PROVIDE THE CONDUCTOR TYPE, WIRE SIZE AND V.A. OF |
| EACH CIRCUT. |
| PANEL SCHEDULE: |
| PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED |
| CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS, |
| AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY |
| WITH CODE. NEC 210.8, 210.12, 210.19, 210.20, 215.5, |
| 408.4; WPB FBC 107.3.5; FBC RE E3706.2, E3902. |
| |
| 3. LOAD CALC'S SUBMITTED FOR REVIEW DO NOT INCLUDE THE |
| POOL EQUIPMENT, NEW SUB PANEL AND NEW EMERGENCY PANEL. |
| PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE EXISTING |
| AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE IS |
| ADEQUATE. NEC 215.2, 220, 408.30; FBC RE E3602.2 |
| |
| 4. R404.1LIGHTING EQUIPMENT (MANDATORY). |
| NOT LESS THAN 75 PERCENT OF THE LAMPS IN PERMANENTLY |
| INSTALLED LIGHTING FIXTURES SHALL BE HIGH-EFFICACY |
| LAMPS OR NOT LESS THAN 75 PERCENT OF THE PERMANENTLY |
| INSTALLED LIGHTING FIXTURES SHALL CONTAIN ONLY |
| HIGH-EFFICACY LAMPS. |
| EXCEPTION: LOW-VOLTAGE LIGHTING. |
| A NOTE ON THE PLAN WILL SUFFICE. FBC EC R404.1 |
| |
| 5. PROVIDE OUTLET AT FRONT OF STRUCTURE. |
| E3901.7 OUTDOOR OUTLETS. |
| NOT LESS THAN ONE RECEPTACLE OUTLET THAT IS READILY |
| ACCESSIBLE FROM GRADE LEVEL AND LOCATED NOT MORE THAN 6 |
| FEET, 6 INCHES (1981 MM) ABOVE GRADE, SHALL BE |
| INSTALLED OUTDOORS AT THE FRONT AND BACK OF EACH |
| DWELLING UNIT HAVING DIRECT ACCESS TO GRADE LEVEL. |
| |
| 6. AN OUTLET IS REQUIRED ON THE SIDE OF THE NEW CLOSET |
| IN THE FAMILY ROOM. |
| E3901.2.2 WALL SPACE. |
| AS USED IN THIS SECTION, A WALL SPACE SHALL INCLUDE THE |
| FOLLOWING: [210.52(A)(2)] |
| 1.ANY SPACE THAT IS 2 FEET (610 MM) OR MORE IN WIDTH, |
| INCLUDING SPACE MEASURED AROUND CORNERS, AND THAT IS |
| UNBROKEN ALONG THE FLOOR LINE BY DOORWAYS AND SIMILAR |
| OPENINGS, FIREPLACES, AND FIXED CABINETS. |
| |
| WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |
| |
| |