Plan Review Notes For Permit 20120638 |
Permit Number |
20120638 |
|
Review Stop |
B |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2021-01-11 13:43:14 | ROOFING | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected]. | | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 | | AMENDMENTS | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | *****COMMENTS BELOW ARE FOR THE "SILCOR 900HA LIQUID | | WATERPROOFING"******** | | 1) PLEASE PROVIDE INSTALLATION DETAILS ALONG WITH | | STRUCTURAL CALCULATIONS TO SHOW THAT THE LIQUID | | WATERPROOFING WILL MEET OR EXCEED THE REQUIRED WIND | | DESIGN PRESSURES OR PROVIDE A COMPLETE MIAMI DADE OR | | FLORIDA STATE PRODUCT APPROVAL THAT SHOWS THE DESIGN | | WIND PRESSURES WILL MEET OR EXCEED THE PRESSURES SHOWN | | ON DRAWING (S1) - FBC R905.15.3 APPLICATION. | | LIQUID-APPLIED ROOFING SHALL BE INSTALLED IN ACCORDANCE | | WITH THIS CHAPTER AND THE MANUFACTURER'S INSTRUCTIONS. | | THE APPROVED ALLOWABLE UPLIFT RESISTANCE FOR THE | | LIQUID-APPLIED COATINGS SHALL BE EQUAL TO OR GREATER | | THAN THE UPLIFT RESISTANCE FOR THE ROOF BASED ON TABLE | | R301.2(2). | | 2) R905.15.1 SLOPE. | | LIQUID-APPLIED ROOFING SHALL HAVE A DESIGN SLOPE OF NOT | | LESS THAN ONE-FOURTH UNIT VERTICAL IN 12 UNITS | | HORIZONTAL (2-PERCENT SLOPE). |
|