Plan Review Notes
Plan Review Notes For Permit 20120638
Permit Number 20120638
Review Stop B
Sequence Number 3
Notes
Date Text
2021-01-11 13:43:14ROOFING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 *****COMMENTS BELOW ARE FOR THE "SILCOR 900HA LIQUID
 WATERPROOFING"********
 1) PLEASE PROVIDE INSTALLATION DETAILS ALONG WITH
 STRUCTURAL CALCULATIONS TO SHOW THAT THE LIQUID
 WATERPROOFING WILL MEET OR EXCEED THE REQUIRED WIND
 DESIGN PRESSURES OR PROVIDE A COMPLETE MIAMI DADE OR
 FLORIDA STATE PRODUCT APPROVAL THAT SHOWS THE DESIGN
 WIND PRESSURES WILL MEET OR EXCEED THE PRESSURES SHOWN
 ON DRAWING (S1) - FBC R905.15.3 APPLICATION.
 LIQUID-APPLIED ROOFING SHALL BE INSTALLED IN ACCORDANCE
 WITH THIS CHAPTER AND THE MANUFACTURER'S INSTRUCTIONS.
 THE APPROVED ALLOWABLE UPLIFT RESISTANCE FOR THE
 LIQUID-APPLIED COATINGS SHALL BE EQUAL TO OR GREATER
 THAN THE UPLIFT RESISTANCE FOR THE ROOF BASED ON TABLE
 R301.2(2).
 2) R905.15.1 SLOPE.
 LIQUID-APPLIED ROOFING SHALL HAVE A DESIGN SLOPE OF NOT
 LESS THAN ONE-FOURTH UNIT VERTICAL IN 12 UNITS
 HORIZONTAL (2-PERCENT SLOPE).


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved