2020-12-23 08:23:05ROOFING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE PROVIDE A COMPLETE PRODUCT APPROVAL THAT
 SHOWS THE DESIGN WIND PRESSURES NEEDED SHOWN ON DRAWING
 (S1) - FBC R905.15.3 APPLICATION.
 LIQUID-APPLIED ROOFING SHALL BE INSTALLED IN ACCORDANCE
 WITH THIS CHAPTER AND THE MANUFACTURER'S INSTRUCTIONS.
 THE APPROVED ALLOWABLE UPLIFT RESISTANCE FOR THE
 LIQUID-APPLIED COATINGS SHALL BE EQUAL TO OR GREATER
 THAN THE UPLIFT RESISTANCE FOR THE ROOF BASED ON TABLE
 R301.2(2).
 2) R905.15.1 SLOPE.
 LIQUID-APPLIED ROOFING SHALL HAVE A DESIGN SLOPE OF NOT
 LESS THAN ONE-FOURTH UNIT VERTICAL IN 12 UNITS
 HORIZONTAL (2-PERCENT SLOPE).