Plan Review Notes
Plan Review Notes For Permit 20120638
Permit Number 20120638
Review Stop B
Sequence Number 1
Notes
Date Text
2020-12-18 08:11:36ROOFING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE PROVIDE A COMPLETE PRODUCT APPROVAL THAT
 SHOWS THE DESIGN WIND PRESSURES NEEDED SHOWN ON DRAWING
 (S1) - FBC R905.15.3 APPLICATION.
 LIQUID-APPLIED ROOFING SHALL BE INSTALLED IN ACCORDANCE
 WITH THIS CHAPTER AND THE MANUFACTURER?S INSTRUCTIONS.
 THE APPROVED ALLOWABLE UPLIFT RESISTANCE FOR THE
 LIQUID-APPLIED COATINGS SHALL BE EQUAL TO OR GREATER
 THAN THE UPLIFT RESISTANCE FOR THE ROOF BASED ON TABLE
 R301.2(2).


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved