Plan Review Notes
Plan Review Notes For Permit 20120618
Permit Number 20120618
Review Stop Z
Sequence Number 2
Notes
Date Text
2021-02-22 15:52:26** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) SHOW PROPOSED LOCATION OF THE A/C COMPRESSOR UNIT
 IN THE SITE PLAN/SURVEY AND PROVIDE SETBACK DISTANCE
 FROM THE UNIT TO THE PROPERTY LINE. PLEASE NOTE THAT
 ANY MECHANICAL EQUIPMENT MAY NOT PROJECT MORE THAN 4
 FT. INTO A REQUIRED SETBACK. [ZLDR S.94-305(A)(4)]
  
 [12/29/2020 REPEAT COMMENT: ALTHOUGH THE LOCATION OF
 THE A/C PAD HAS BEEN ILLUSTRATED IN THE BOUNDARY AND
 TOPOGRAPHIC SURVEY (CONSTRUCTION LAYOUT), THE SETBACK
 DISTANCE TO THE REAR PROPERTY LINE HAS NOT BEEN
 PROVIDED. ADDITIONALLY, THE LOCATION OF THE A/C PAD IN
 THE CONSTRUCTION LAYOUT DOES NOT MATCH THE LOCATION
 PROVIDED IN THE FLOOR PLAN (SHEET A-1) AND THE
 ELECTRICAL PLANS AND MUST MATCH FOR CONSISTENCY. PLEASE
 ADDRESS.]
  
  
 NOTES:
  
 * ADDITIONAL SEPARATE PERMITS REQUIRED FOR:
 LANDSCAPING, DRIVEWAY, SWIMMING POOL.
  
 * ANY REVISIONS MAY RESULT IN ADDITIONAL COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * Z = MF20
  
 * LOT DIMENSION: 50 FT. X 105 FT. = 5,250 SQ. FT.
  
 * PROPOSED USE: SFR
  
 * ATTEMPTED TO CONTACT CONTRACTOR, DON ANDERSON, TO
 CLARIFY PLACEMENT OF THE A/C PAD ON 2/22/2021; HOWEVER,
 NO PHONE NUMBER/EMAIL PROVIDED IN THE APPLICATION.
  