2021-01-04 13:32:36 | PLAN REVIEW / ELECTRICAL |
| |
| CHRISTOPHER S. THROOP, C.B.O. |
| PLANS EXAMINER BUILDING - PX3169 |
| PLANS EXAMINER 1&2 FAMILY - SFP306 |
| CONSTRUCTION SERVICES DIVISION |
| TEL: 561-805-6726 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| CODES IN EFFECT: |
| 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1 ADMINISTRATION |
| 2014 NEC |
| |
| 1ST REVIEW |
| |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| |
| 1. PROVIDE ACTUAL TRANSFORMER SECONDARY FAULT CURRENT |
| FROM UTILITY. |
| |
| E3404.2INTERRUPTING RATING. |
| |
| EQUIPMENT INTENDED TO INTERRUPT CURRENT AT FAULT LEVELS |
| SHALL HAVE A MINIMUM INTERRUPTING RATING OF 10,000 |
| AMPERES. EQUIPMENT INTENDED TO INTERRUPT CURRENT AT |
| LEVELS OTHER THAN FAULT LEVELS SHALL HAVE AN |
| INTERRUPTING RATING AT NOMINAL CIRCUIT VOLTAGE OF NOT |
| LESS THAN THE CURRENT THAT MUST BE INTERRUPTED. (110.9) |
| |
| PROVIDE NOTE THAT THE SERVICE EQUIPMENT SHALL BE MARKED |
| WITH THE MAXIMUM AVAILABLE SHORT CIRCUIT CURRENT |
| AVAILABLE PER NEC 110.24 & FBC RE E3606.4 |
| |
| 2. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT |
| SERVICE. SHOW ON PLAN. NEC 250.94; FBC RE E3609.3 |
| |
| 3. R404.1LIGHTING EQUIPMENT (MANDATORY). |
| NOT LESS THAN 75 PERCENT OF THE LAMPS IN PERMANENTLY |
| INSTALLED LIGHTING FIXTURES SHALL BE HIGH-EFFICACY |
| LAMPS OR NOT LESS THAN 75 PERCENT OF THE PERMANENTLY |
| INSTALLED LIGHTING FIXTURES SHALL CONTAIN ONLY |
| HIGH-EFFICACY LAMPS. |
| EXCEPTION: LOW-VOLTAGE LIGHTING. |
| A NOTE ON THE PLAN WILL SUFFICE. FBC EC R404.1 |
| |
| 4. PROVIDE GFCI PROTECTION FOR DISHWASHERS. NEC |
| 210.8(D); FBC RE E3902.10 |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |