Plan Review Notes
Plan Review Notes For Permit 20120595
Permit Number 20120595
Review Stop SIGNATURE
Sequence Number 2
Notes
Date Text
2021-03-01 09:59:33THE PREFAB GENERATOR PAD DRAWINGS DO NOT HAVE THE
 ENGINEER'S DIGITAL SIGNATURES. ELECTRONICALLY SUBMITTED
 DRAWINGS ARE REQUIRED TO HAVE THE ENGINEER'S DIGITAL
 SIGNATURE ON THEM. YOU ALSO HAVE THE OPTION TO SUBMIT
 THE SIGNED AND SEALED PAPER VERSION OF DRAWINGS. AFTER
 THE ELECTRONIC PLANS HAVE BEEN APPROVED, YOU CAN SUBMIT
 THE CORRESPONDING PAPER DRAWINGS AT THE BUILDING
 DEPARTMENT TO BE VERIFIED. THE ENGINEER'S ORIGINAL
 HANDWRITTEN SIGNATURE AND SEAL IS REQUIRED TO BE ON THE
 DRAWINGS. NO PHOTOCOPY OR OTHER FACSIMILES OF THE
 SIGNATURE ARE ACCEPTABLE. FS 471 & 61G15
  
 NO SIGNATURE OF CONTRACTOR ON ELECTRIC RISER DIAGRAHM.
 CT