2021-03-19 13:19:45 | IT APPEARS THAT NONE OF THE EXISTING COMMENTS HAVE BEEN |
| ADDRESSED ON THIS RESUBMITTAL. |
| |
| 1) INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM |
| ON THE PLAN PER 2017 FBC-FUEL GAS SEC.402.1, 402.4.3 |
| THRU 402.6 OR 2017 FBC RES. SEC. G2413.2, G2413.4.3. |
| 2) SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED. WPB |
| AMEND. TO FBC SEC. 107.2.1. |
| 3) LIST THE BTU LOAD OF THE GENERATOR AND THE TOTAL BTU |
| LOAD ON THE SYSTEM. REFER TO THE 2017 FBC-FUEL GAS |
| SECS.401.8, 402.2, AND TABLES 402.4 (1) THRU 402.4 (37) |
| OR 2017 FBC-RES. SEC. G2413.3, G2413.4 AND TABLES |
| G2413.4 (1 ) THROUGH G2413.4 (21). |
| 4) SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS |
| METER) TO THE MOST REMOTE OUTLET/ REGULATOR IN THE |
| BUILDING AND / OR SYSTEM PER THE 2017 FBC-FUEL GAS |
| SEC.402.4.1, 402.4.2, OR 2017 FBC-RES. SEC. G 2413.4.1, |
| G2413.4.2. NOTE: EXISTING PLANS ON FILE WITH THE CITY |
| SHOW THE DISTANCE AS 39 FEET. |
| 5) SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES |
| USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE |
| PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM |
| THE GAS CODE OR OTHER STANDARD THAT WERE USED IN THE |
| DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017 FBC-FUEL |
| GAS SECS. 401.4, 401.8, 402.3, AND TABLES 402.4 (1) |
| THRU 402.4 (37) OR 2017 FBC-RES. SEC. G2413.3, G2412.8, |
| G2413.1, G2413.2, & G2413.3. NOTE: CITY RECORDS SHOW |
| THIS SYSTEM AS A 2 PSI SYSTEM. |
| 6) SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS. |
| A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY |
| AHEAD OF EACH MP REGULATOR. 2017 FBC-FUEL GAS |
| SEC.409.4, FBC-RESIDENTIAL SEC. G 2420.4. |
| 7) THE PLANS INDICATE AN EXISTING GAS METER AND CITY |
| RECORDS SHOW AN EXISTING GAS SYSTEM FOR THIS ADDRESS. |
| THE BTU LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED |
| INTO THE TOTAL BTU LOAD ON THE SYSTEM TO ENSURE THE |
| EXISTING SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, THE |
| EXISTING SYSTEM MUST BE REDONE TO ENSURE A SAFE |
| OPERATING SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM |
| THAT SHOWS THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD |
| OF EACH APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO |
| EACH APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH |
| OF PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE |
| OUTLET AND THE LOAD OF THE SECTION. |
| 8) ) SHOW THE TYPE OF PIPE AND PIPE SIZE AT THE OUTLET |
| OF THE 2-PSI METER. WPB AMEND. TO FBC SEC. 107.2.1. |
| 9) SHOW THE PIPE SIZE TO THE THE EXISTING GAS LOAD. WPB |
| AMEND. TO FBC SEC. 107.2.1. |
| 10) EXISTING PLANS ON FILE SHOW THE GAS SYSTEM AS A 2 |
| PSI SYSTEM. SHOW THE LOCATION OF ALL EXISTING |
| REGULATORS ON THE GAS PLAN.WPB AMEND. TO FBC SEC. |
| 107.2.1. |
| 11) THE GAS DRAWING SHOWS TWO SHUTOFF VALVES IN THE GAS |
| LINE TO THE GENERATOR. CLARIFY. |
| 12) SINCE THIS IS AN EXISTING 2 PSI SYSTEM, A REGULATOR |
| IS REQUIRED AT THE GENERATOR. SUBMIT MANUFACTURER'S |
| SPECIFICATIONS AND INSTALATION INTRUCTIONS FOR THE |
| REGULATOR. REGULATORS INSTALLED ON THE EXTERIOR OF THE |
| BUILDING SHALL BE APPROVED OR OUTDOOR INSTALLATION PER |
| FFBC-FUEL GAS SEC.410.1. |
| |