Plan Review Notes For Permit 20120595 |
Permit Number |
20120595 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2021-03-01 09:51:53 | PLAN | | REVIEW COMMENTS | | | | 2ND REVIEW: FBC SIXTH EDITION (2017) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) [THE LOCATION OF THE GENERATOR IS NOT SHOWN ON THE | | SURVEY AND THE REQUIRED 10 FT DISTANCE FROM OPENINGS IS | | NOT SPECIFIED.]THE GENERATOR EXHAUST IS REQUIRED TO BE | | 10 FEET FROM ANY OPENINGS INTO THE BUILDING. R303.5.1 | | INTAKE OPENINGS. | | MECHANICAL AND GRAVITY OUTDOOR AIR INTAKE OPENINGS | | SHALL BE LOCATED NOT LESS THAN 10 FEET (3048 MM) FROM | | ANY HAZARDOUS OR NOXIOUS CONTAMINANT, SUCH AS VENTS, | | CHIMNEYS, PLUMBING VENTS, STREETS, ALLEYS, PARKING LOTS | | AND LOADING DOCKS. | | | | 2) THE PRE-FAB GENERATOR PAD ENGINEERING IS COMPATIABLE | | WITH THE 24KW GENERATOR SPECIFICATIONS THAT WERE | | SUBMITTED. HOWEVER, THE DRAWINGS DO NOT HAVE THE | | ENGINEER'S DIGITAL SIGNATURE. SEE THE SIGNATURE REVIEW | | STOP. | | | | 3) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A | | RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE | | CITY RE-SUBMITTAL FORM. | | |
|