Plan Review Notes For Permit 20120595 |
Permit Number |
20120595 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2020-12-17 14:48:57 | PLAN REVIEW / ELECTRICAL | | | | CHRISTOPHER S. THROOP, C.B.O. | | PLANS EXAMINER BUILDING - PX3169 | | PLANS EXAMINER 1&2 FAMILY - SFP306 | | CONSTRUCTION SERVICES DIVISION | | TEL: 561-805-6726 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | | | CODES IN EFFECT: | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | CHAPTER 1 ADMINISTRATION | | 2014 NEC | | | | 1ST REVIEW | | | | RESULTS: DENIED | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | 1. PROVIDE UPDATED LOAD CALC'S. SHOW LOAD SHARING. | | PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE EXISTING | | AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE IS | | ADEQUATE. NEC 215.2, 220, 408.30; FBC RE E3602.2 | | | | 2. USE PROPER FILE NAMING GUIDELINES. | | SEE PROJECT DOX QUICK START GUIDE. | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | |
|