2021-01-15 12:10:07 | 1/20/21 SPOKE WITH KEVIN THE CONTRACTOR, ENTIRE JOB | | REVISED, PLANS REFLECT ENTIRE REVISION. | | | | PASSED. | | | | PML | | | | | | | | | | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) THERE IS AN INDICATION ON THE APPLICATION OF A | | REVISION. THERE ARE NO INDICATION ON THE PALN SHEETS OF | | WHAT HAS BEEN REVISED. | | | | THE TITLE BLOCK IN THE REVISION TABLE THERE ARE NO | | INDICATIONS OF #, EVISIO COMMENT NOT DATE. | | | | PER NFPA 1 | | | | 1.14 PLAN REVIEW. | | 1.14.5 WHEN REQUIRED BY THE AHJ, REVISED CONSTRUCTION | | DOCUMENTS OR SHOP DRAWINGS SHALL BE PREPARED AND | | SUBMITTED FOR REVIEW AND APPROVAL TO ILLUSTRATE | | CORRECTIONS OR MODIFICATIONS NECESSITATED BY FIELD | | CONDITIONS OR OTHER REVISIONS TO APPROVED PLANS. | | | | | | | | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | ABOVE. | | | | | | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | RE-SUBMITTAL OF THE ABOVE. | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | |
|