Date |
Text |
2023-02-07 13:39:09 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| SERVICES/ BUILDING DIVISION |
| 2017 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 20120513 |
| ADD: 1900 CONSULATE PL. SUITE: 705 |
| CONT: MOSS DELCO INC. |
| TEL: 561-644-0302 |
| E-MAIL: [email protected] |
| |
| 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| BUILDING CODE, BUILDING. |
| |
| 4TH REVIEW |
| DATE: TUES. FEB. 07TH/ 2023 |
| ACTION: DENIED |
| |
| |
| ***** NOTICE ONLY ***** 4X FEE / NOTICE!!!!! FLORIDA |
| STATUTE 553.80(2)(B) |
| |
| WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS??? |
| DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN |
| ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING |
| CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS |
| REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO |
| CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY |
| NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, |
| EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY, |
| ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL, |
| MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER |
| REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING |
| COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL |
| GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH |
| REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION, |
| A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE |
| PERMIT FEE ATTRIBUTED TO PLANS REVIEW. |
| |
| |
| |
| |
| 1) COMPLIED, NEW VALUE OF $50,000.00 |
| |
| 2-4B) COMPLIED. |
| |
| 4C) BUILDING PROVISO: TO BE DETERMINED IN THE FIELD. |
| 2017 FBC-B SHOWERS & TUBS 1210.3. SHOWER COMPARTMENTS |
| AND BATHTUBS WITH INSTALLED SHOWER HEADS SHALL BE |
| FINISHED WITH A NONABSORBENT SURFACE TO A HEIGHT NOT |
| LESS THAN 72 INCHES ABOVE THE DRAIN INLET. |
| |
| |
| 5) 4TH REVIEW, SEMI- COMPLIED. SUBMITTED THIS REVIEW |
| CYCLE HEATHER CHOICE FLOORING STC OF 67, 6 INCH |
| CONCRETE SLAB WITH DROPPED CEILING, SUSPENDED GYPSUM |
| BOARD CEILING W/ 3-1/2 INCHES OF BATT INSULATION, HCAU |
| UNDERLAYMENT & LVT (LUXURY VINYL TILE). THE SPEC SHEET |
| SUBMITTED PROVIDES SOUND RATINGS BUT NOT THE FLOOR |
| ASSEMBLY. |
| |
| 5A) 4TH REQUEST. NO REPORT THIS REVIEW. FBC-B 2020 |
| 1207.3 STRUCTURE-BORNE SOUND. FLOOR/CEILING ASSEMBLIES |
| BETWEEN DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A |
| PUBLIC OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE |
| AN IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS |
| THAN 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE |
| WITH ASTM E-492. |
| |
| 5B) 4TH REQUEST. NO TEST REPORTS TO DATE. FBC-B 2020 |
| 1207.2 AIR-BORNE SOUND. WALLS, PARTITIONS AND |
| FLOOR/CEILING ASSEMBLIES SEPARATING DWELLING UNITS FROM |
| EACH OTHER OR FROM PUBLIC OR SERVICE AREAS SHALL HAVE A |
| SOUND TRANSMISSION CLASS (STC) OF NOT LESS THAN 50 (45 |
| IF FIELD TESTED) FOR AIR-BORNE NOISE WHEN TESTED IN |
| ACCORDANCE WITH ASTM E 90. |
| |
| 5) 4TH REQUEST. SUBMITTED ONE PAGE OF A REPORT, PLEASE |
| SUBMIT THE FULL REPORT. THE FINISH FLOOR MATERIAL IS |
| VINYL SO TEST REPORTS SHOULD BE IN COMPLIANCE WITH |
| FBC-B 804.4.4.1 SOFT FLOOR FINISHES (LVT/ LPT OR |
| LAMINATED OR ENGINEERED WOOD FLOORING) WITHIN TENANT |
| SPACE. INTERIOR FLOOR COVERING MATERIALS SHALL COMPLY |
| WITH THE REQUIREMENTS OF THE COC FF-1 ???PILL TEST??? |
| (CPSC 16 CFR PART 1630) OR WITH ASTM D2859. |
| LVT & LPT LUXURY VINYL TILE. FLOOR FINISH |
| CLASSIFICATION AS REQUIRED IN SECTION 804.2 |
| CLASSIFICATION AND 804.3 TESTING AND IDENTIFICATION OF |
| THE 2020 FBC-B. 804.2 & 804.3/ ASTM E648 OR NFPA 253 |
| |
| 6) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| REVIEW CYCLE. |
| |
| PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID |
| 19 |
| IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS |
| 561-718-9724. |
| WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/ |
| RETIRED. |
| |
| JAMES A. WITMER BN, PX, SFP, CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| TEL: 561-805-6717 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| DEVELOPMENT SERVICES HOME PAGE |
| HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| |
| |
| |
| |
| |
| |