Plan Review Notes
Plan Review Notes For Permit 20120513
Permit Number 20120513
Review Stop B
Sequence Number 3
Notes
Date Text
2022-09-19 14:48:36WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20120513
 ADD: 1900 CONSULATE PL. SUITE: 705
 CONT: MOSS DELCO INC.
 TEL: 561-644-0302
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: MON. SEPT. 19TH/ 2022
 ACTION: DENIED
  
  
 ***** NOTICE ONLY ***** 4X FEE / NOTICE!!!!! FLORIDA
 STATUTE 553.80(2)(B)
  
 WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS???
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW.
  
  
  
  
 1) 3RD REQUEST. SAME NOTES FROM DESIGN PROFESSIONAL
 FROM 4/12/2021. THE PLAN REVIEW RESPONSE COMMENTS STATE
 THAT THE VALUE OF THE WORK HAS BEEN REVISED TO MORE
 ACCURATELY REFLECT THE WORK ACCOMPLISHED. THE VALUE OF
 WORK HAS NOT CHANGED NOR DECLARED. IT APPEARS WHEN
 READING THE PLAN REVIEW RESPONSES THAT THIS WORK HAS
 ALREADY BEEN COMPLETED. PLEASE RESPOND HAS THIS WORK
 BEEN COMPLETED WITHOUT A PERMIT.
  
 1ST ROUND OF COMMENTS. THE DESCRIPTION OF WORK IS TO DO
 A REMODEL OF THE INTERIOR OF THE TENANT SPACE, KITCHEN
 CABINETS AND COUNTERTOP NEW SINK AND SUPPLY, 2 NEW
 VANITIES, TUB & SHOWER AND REPLACEMENT OF FLOORING WITH
 TILE WITH THE EXCEPTION OF THE FOYER, REMOVAL OF ALL
 DEBRIS AND COST OF DESIGN PROFESSIONAL AND THE
 CONTRACTOR OVERHEAD AND PROFIT. THE PERMIT VALUE
 DECLARED IS EXTREMELY LOW!!!
 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION SECTION 109.3 BUILDING
 PERMIT VALUATION. IF, IN THE OPINION OF THE BUILDING
 OFFICIAL, THE CLAIMED VALUATION OF BUILDING,
 ALTERATION, STRUCTURE, ELECTRICAL, GAS, MECHANICAL, OR
 PLUMBING SYSTEMS APPEARS TO BE UNDERESTIMATED ON THE
 APPLICATION, THE PERMIT SHALL BE DENIED. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 2-4B) COMPLIED.
  
 4C) BUILDING PROVISO: TO BE DETERMINED IN THE FIELD.
 2017 FBC-B SHOWERS & TUBS 1210.3. SHOWER COMPARTMENTS
 AND BATHTUBS WITH INSTALLED SHOWER HEADS SHALL BE
 FINISHED WITH A NONABSORBENT SURFACE TO A HEIGHT NOT
 LESS THAN 72 INCHES ABOVE THE DRAIN INLET.
  
  
 5) 3RD REQUEST. NO FLOORING INSULATION WAS SUBMITTED
 FOR THE 2ND OR 3RD REVIEW. THE RESPONSE STATES THE
 FLOOR SOUND INSULATION MATERIALS WERE INSTALLED AS PER
 THE BUILDING REQUIREMENTS FOR STANDARDS OF TILE FLOOR
 INSTALLATIONS. IF FIELD TESTING BY A CERTIFIED
 LABORATORY, PLEASE SUBMIT BOTH REQUIRED REPORTS FOR THE
 IIC AND STC REQUIREMENTS. COMMENT 5C THE FLAME SPREAD
 REPORT WILL ALSO NEED TO BE SATISFIED.
  
 1ST ROUND COMMENT. THE PLANS STATED REPLACE ALL
 FLOORING, EXCEPT ENTRY, WITH NEW FLOOR TILE. FLOOR
 INSULATION (FBC-B 2017) OR TILE, STONE, MARBLE, VINYL
 AND WOOD FLOORING ALL NEED TO HAVE HAD THE SOUND
 UNDERLAYMENT TESTED FLOOR ASSEMBLIES TO THE FOLLOWING
 STANDARDS AND MEET THE QUALIFICATIONS LISTED UNDER EACH
 OF THE STANDARDS FOR A 6 INCH CONCRETE FLOOR ASSEMBLY/
 NO DROPPED CEILING:
 PLEASE PROVIDE ALL THREE TEST REPORTS FOR TYPE I AND OR
 TYPE II BUILDINGS SHOWING COMPLIANCE WITH:
  
 5A)3RD REQUEST. FBC-B 2020 1207.3 STRUCTURE-BORNE
 SOUND. FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS
 OR BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492.
  
 5B) 3RD REQUEST. FBC-B 2020 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 5)3RD REQUEST. FLAME SPREAD- FBC-B 2020 603.1.
 EXCEPTION 2. INSULATION INSTALLED BETWEEN A FINISHED
 FLOOR AND SOLID DECKING WITHOUT INTERVENING AIRSPACE
 SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT
 MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 6) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/
 RETIRED.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
  