2021-04-26 14:57:10 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| SERVICES/ BUILDING DIVISION |
| 2017 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 20120513 |
| ADD: 1900 CONSULATE PL. SUITE: 705 |
| CONT: MOSS DELCO INC. |
| TEL: 561-644-0302 |
| E-MAIL: [email protected] |
| |
| 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| BUILDING CODE, BUILDING. |
| |
| 2ND REVIEW |
| DATE: MON. APRIL 26TH/ 2021 |
| ACTION: DENIED |
| |
| 1) 2ND REQUEST. THE PLAN REVIEW RESPONSE COMMENTS STATE |
| THAT THE VALUE OF THE WORK HAS BEEN REVISED TO MORE |
| ACCURATELY REFLECT THE WORK ACCOMPLISHED. THE VALUE OF |
| WORK HAS NOT CHANGED NOR DECLARED. IT APPEARS WHEN |
| READING THE PLAN REVIEW RESPONSES THAT THIS WORK HAS |
| ALREADY BEEN COMPLETED. PLEASE RESPOND HAS THIS WORK |
| BEEN COMPLETED WITHOUT A PERMIT. |
| |
| 1ST ROUND OF COMMENTS. THE DESCRIPTION OF WORK IS TO DO |
| A REMODEL OF THE INTERIOR OF THE TENANT SPACE, KITCHEN |
| CABINETS AND COUNTERTOP NEW SINK AND SUPPLY, 2 NEW |
| VANITIES, TUB & SHOWER AND REPLACEMENT OF FLOORING WITH |
| TILE WITH THE EXCEPTION OF THE FOYER, REMOVAL OF ALL |
| DEBRIS AND COST OF DESIGN PROFESSIONAL AND THE |
| CONTRACTOR OVERHEAD AND PROFIT. THE PERMIT VALUE |
| DECLARED IS EXTREMELY LOW!!! |
| 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| CODE, CHAPTER 1, ADMINISTRATION SECTION 109.3 BUILDING |
| PERMIT VALUATION. IF, IN THE OPINION OF THE BUILDING |
| OFFICIAL, THE CLAIMED VALUATION OF BUILDING, |
| ALTERATION, STRUCTURE, ELECTRICAL, GAS, MECHANICAL, OR |
| PLUMBING SYSTEMS APPEARS TO BE UNDERESTIMATED ON THE |
| APPLICATION, THE PERMIT SHALL BE DENIED. FOR PERMITTING |
| PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE |
| TOTAL REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND |
| SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE |
| STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR |
| FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR |
| BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING |
| COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED |
| DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS |
| FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE |
| CONGRESS. |
| |
| 2-4B) COMPLIED. |
| |
| 4C) BUILDING PROVISO: TO BE DETERMINED IN THE FIELD. |
| 2017 FBC-B SHOWERS & TUBS 1210.3. SHOWER COMPARTMENTS |
| AND BATHTUBS WITH INSTALLED SHOWER HEADS SHALL BE |
| FINISHED WITH A NONABSORBENT SURFACE TO A HEIGHT NOT |
| LESS THAN 72 INCHES ABOVE THE DRAIN INLET. |
| |
| |
| 5) 2ND REQUEST. NO FLOORING INSULATION WAS SUBMITTED |
| FOR THE 2ND REVIEW. THE RESPONSE STATES THE FLOOR SOUND |
| INSULATION MATERIALS WERE INSTALLED AS PER THE BUILDING |
| REQUIREMENTS FOR STANDARDS OF TILE FLOOR INSTALLATIONS. |
| IF FIELD TESTING BY A CERTIFIED LABORATORY, PLEASE |
| SUBMIT BOTH REQUIRED REPORTS FOR THE IIC AND STC |
| REQUIREMENTS. COMMENT 5C THE FLAME SPREAD REPORT WILL |
| ALSO NEED TO BE SATISFIED. |
| |
| 1ST ROUND COMMENT. THE PLANS STATED REPLACE ALL |
| FLOORING, EXCEPT ENTRY, WITH NEW FLOOR TILE. FLOOR |
| INSULATION (FBC-B 2017) OR TILE, STONE, MARBLE, VINYL |
| AND WOOD FLOORING ALL NEED TO HAVE HAD THE SOUND |
| UNDERLAYMENT TESTED FLOOR ASSEMBLIES TO THE FOLLOWING |
| STANDARDS AND MEET THE QUALIFICATIONS LISTED UNDER EACH |
| OF THE STANDARDS FOR A 6 INCH CONCRETE FLOOR ASSEMBLY/ |
| NO DROPPED CEILING: |
| PLEASE PROVIDE ALL THREE TEST REPORTS FOR TYPE I AND OR |
| TYPE II BUILDINGS SHOWING COMPLIANCE WITH: |
| |
| 5A) FBC-B 2020 1207.3 STRUCTURE-BORNE SOUND. |
| FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492. |
| |
| 5B) FBC-B 2020 1207.2 AIR-BORNE SOUND. WALLS, |
| PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING |
| DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS |
| (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR |
| AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E |
| 90. |
| |
| 5) FLAME SPREAD- FBC-B 2020 603.1. EXCEPTION 2. |
| INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. |
| |
| FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| |
| 6) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| REVIEW CYCLE. |
| |
| PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID |
| 19 |
| IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS |
| 561-718-9724. |
| WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/ |
| RETIRED. |
| |
| JAMES A. WITMER BN, PX, SFP, CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| TEL: 561-805-6717 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| DEVELOPMENT SERVICES HOME PAGE |
| HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| |
| PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| |
| MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| |