2021-02-23 14:33:07 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| 1) THERE ARE INDICATIONS OF WORK THAT MAY INVOLVE NEW |
| FLOOR/TILE BUT NO SPECIFICATIONS SHEETS THAT INDICATE |
| MEETING THE REQUIREMENTS PER NFPA FOR FALME SPREAD AND |
| SMOKE GENERATION. |
| |
| PER NFPA 101, CH 32 |
| |
| 30.3.3.2 INTERIOR WALL AND CEILING FINISH. INTERIOR |
| WALL AND |
| CEILING FINISH MATERIALS COMPLYING WITH SECTION 10.2 |
| SHALL BE |
| PERMITTED AS FOLLOWS: |
| (1) EXIT ENCLOSURES ? CLASS A |
| (2) LOBBIES AND CORRIDORS ? CLASS A OR CLASS B |
| (3) OTHER SPACES ? CLASS A, CLASS B, OR CLASS C |
| |
| 30.3.3.3 INTERIOR FLOOR FINISH. |
| 30.3.3.3.1 INTERIOR FLOOR FINISH SHALL COMPLY WITH |
| SECTION 10.2. |
| 30.3.3.3.2 INTERIOR FLOOR FINISH IN EXIT ENCLOSURES AND |
| EXIT ACCESS |
| CORRIDORS AND SPACES NOT SEPARATED FROM THEM BY WALLS |
| COMPLYING |
| WITH 30.3.6 SHALL BE NOT LESS THAN CLASS II. |
| 30.3.3.3.3 INTERIOR FLOOR FINISH SHALL COMPLY WITH |
| 10.2.7.1 OR |
| 10.2.7.2, AS APPLICABLE |
| |
| |
| 10.2.1.1 CLASSIFICATION OF INTERIOR FINISH MATERIALS |
| SHALL BE IN |
| ACCORDANCE WITH TESTS MADE UNDER CONDITIONS SIMULATING |
| ACTUAL |
| INSTALLATIONS, PROVIDED THAT THE AUTHORITY HAVING |
| JURISDICTION IS |
| PERMITTED TO ESTABLISH THE CLASSIFICATION OF ANY |
| MATERIAL FOR WHICH |
| CLASSIFICATION BY A STANDARD TEST IS NOT AVAILABLE, |
| UNLESS OTHERWISE |
| PROVIDED IN 10.2.1.2 OR 10.2.1.4. |
| 10.2.1.2 THE PROVISIONS OF 10.2.1.1 SHALL NOT APPLY TO |
| MATERIALS HAVING |
| A TOTAL THICKNESS OF LESS THAN 1?28 IN. (0.9 MM) THAT |
| ARE APPLIED DIRECTLY |
| TO THE SURFACE OF WALLS AND CEILINGS WHERE BOTH OF THE |
| FOLLOWING |
| CONDITIONS ARE MET: |
| (1) THE WALL OR CEILING SURFACE IS A NONCOMBUSTIBLE OR |
| LIMITED COMBUSTIBLE |
| MATERIAL. |
| (2) THE MATERIALS APPLIED MEET THE REQUIREMENTS OF |
| CLASS A INTERIOR |
| WALL OR CEILING FINISH WHEN TESTED IN ACCORDANCE WITH |
| 10.2.3, |
| USING FIBER CEMENT BOARD AS THE SUBSTRATE MATERIAL. |
| |
| 10.2.7* INTERIOR FLOOR FINISH TESTING AND |
| CLASSIFICATION. |
| 10.2.7.1* CARPET AND CARPET LIKE INTERIOR FLOOR |
| FINISHES SHALL |
| COMPLY WITH ASTM D 2859, STANDARD TEST METHOD FOR |
| IGNITION |
| CHARACTERISTICS OF FINISHED TEXTILE FLOOR COVERING |
| MATERIALS. |
| 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH |
| 10.2.2.2 |
| ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL |
| HAVE A |
| MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2. |
| |
| PLEASE REVIEW AND PROVIDE SPEC SHEETS. |
| |
| |
| |
| 2) THERE ARE INDICATIONS OF WALL & CEILING REMOVAL & |
| REPLACEMENT & MOST LIKLEY PAINTING. |
| |
| THE FIRE SPRINKLER HEAD COVERAGE WILL REQUIRE |
| MODIFICATIONS BY A FIRE SPRINKLER CONTRACTOR. |
| |
| ANY WORK INVOLVING FIRE SPRINKLERS/FIRE ALARM SYSTEMS |
| OR EQUIPMENT SHALL BE DONE UNDER SEPARATE PERMITS AND |
| SHOP DRAWINGS. |
| |
| FIRE SPRINKLERS AND FIRE ALARM EQUIPMENT SHALL BE |
| PROTECTED FROM PAINTING OR DAMAGE. |
| |
| THE FIRE SPRINKLER/FIRE ALARM SYSTEMS SHALL BE |
| MAINTAINED THROUGHOUT DEMO AND RECONSTRUCTION. |
| |
| PLEASE PROVIDE A NOTE OF ACKNOWLEDGEMENT AND ENSURE |
| COMPLIANCE. |
| |
| |
| 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| ABOVE. |
| |
| |
| 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| RE-SUBMITTAL OF THE ABOVE. |
| |
| PETER LEDUC |
| FIRE MARSHAL |
| 561-804-4709 |