Plan Review Notes
Plan Review Notes For Permit 20120513
Permit Number 20120513
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2021-02-23 14:33:07THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE ARE INDICATIONS OF WORK THAT MAY INVOLVE NEW
 FLOOR/TILE BUT NO SPECIFICATIONS SHEETS THAT INDICATE
 MEETING THE REQUIREMENTS PER NFPA FOR FALME SPREAD AND
 SMOKE GENERATION.
  
 PER NFPA 101, CH 32
  
 30.3.3.2 INTERIOR WALL AND CEILING FINISH. INTERIOR
 WALL AND
 CEILING FINISH MATERIALS COMPLYING WITH SECTION 10.2
 SHALL BE
 PERMITTED AS FOLLOWS:
 (1) EXIT ENCLOSURES ? CLASS A
 (2) LOBBIES AND CORRIDORS ? CLASS A OR CLASS B
 (3) OTHER SPACES ? CLASS A, CLASS B, OR CLASS C
  
 30.3.3.3 INTERIOR FLOOR FINISH.
 30.3.3.3.1 INTERIOR FLOOR FINISH SHALL COMPLY WITH
 SECTION 10.2.
 30.3.3.3.2 INTERIOR FLOOR FINISH IN EXIT ENCLOSURES AND
 EXIT ACCESS
 CORRIDORS AND SPACES NOT SEPARATED FROM THEM BY WALLS
 COMPLYING
 WITH 30.3.6 SHALL BE NOT LESS THAN CLASS II.
 30.3.3.3.3 INTERIOR FLOOR FINISH SHALL COMPLY WITH
 10.2.7.1 OR
 10.2.7.2, AS APPLICABLE
  
  
 10.2.1.1 CLASSIFICATION OF INTERIOR FINISH MATERIALS
 SHALL BE IN
 ACCORDANCE WITH TESTS MADE UNDER CONDITIONS SIMULATING
 ACTUAL
 INSTALLATIONS, PROVIDED THAT THE AUTHORITY HAVING
 JURISDICTION IS
 PERMITTED TO ESTABLISH THE CLASSIFICATION OF ANY
 MATERIAL FOR WHICH
 CLASSIFICATION BY A STANDARD TEST IS NOT AVAILABLE,
 UNLESS OTHERWISE
 PROVIDED IN 10.2.1.2 OR 10.2.1.4.
 10.2.1.2 THE PROVISIONS OF 10.2.1.1 SHALL NOT APPLY TO
 MATERIALS HAVING
 A TOTAL THICKNESS OF LESS THAN 1?28 IN. (0.9 MM) THAT
 ARE APPLIED DIRECTLY
 TO THE SURFACE OF WALLS AND CEILINGS WHERE BOTH OF THE
 FOLLOWING
 CONDITIONS ARE MET:
 (1) THE WALL OR CEILING SURFACE IS A NONCOMBUSTIBLE OR
 LIMITED COMBUSTIBLE
 MATERIAL.
 (2) THE MATERIALS APPLIED MEET THE REQUIREMENTS OF
 CLASS A INTERIOR
 WALL OR CEILING FINISH WHEN TESTED IN ACCORDANCE WITH
 10.2.3,
 USING FIBER CEMENT BOARD AS THE SUBSTRATE MATERIAL.
  
 10.2.7* INTERIOR FLOOR FINISH TESTING AND
 CLASSIFICATION.
 10.2.7.1* CARPET AND CARPET LIKE INTERIOR FLOOR
 FINISHES SHALL
 COMPLY WITH ASTM D 2859, STANDARD TEST METHOD FOR
 IGNITION
 CHARACTERISTICS OF FINISHED TEXTILE FLOOR COVERING
 MATERIALS.
 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH
 10.2.2.2
 ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL
 HAVE A
 MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2.
  
 PLEASE REVIEW AND PROVIDE SPEC SHEETS.
  
  
  
 2) THERE ARE INDICATIONS OF WALL & CEILING REMOVAL &
 REPLACEMENT & MOST LIKLEY PAINTING.
  
 THE FIRE SPRINKLER HEAD COVERAGE WILL REQUIRE
 MODIFICATIONS BY A FIRE SPRINKLER CONTRACTOR.
  
 ANY WORK INVOLVING FIRE SPRINKLERS/FIRE ALARM SYSTEMS
 OR EQUIPMENT SHALL BE DONE UNDER SEPARATE PERMITS AND
 SHOP DRAWINGS.
  
 FIRE SPRINKLERS AND FIRE ALARM EQUIPMENT SHALL BE
 PROTECTED FROM PAINTING OR DAMAGE.
  
 THE FIRE SPRINKLER/FIRE ALARM SYSTEMS SHALL BE
 MAINTAINED THROUGHOUT DEMO AND RECONSTRUCTION.
  
 PLEASE PROVIDE A NOTE OF ACKNOWLEDGEMENT AND ENSURE
 COMPLIANCE.
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  