Plan Review Notes
Plan Review Notes For Permit 20120465
Permit Number 20120465
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2020-12-31 12:47:25THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THE PROPOSED PROJECT APPEARS TO RESTRICT THE ONLY
 EGRESS ROUTE FROM THE UNITS.
  
 PER NFPA 101, CH 4
  
 4.6.10 CONSTRUCTION, REPAIR, AND IMPROVEMENT
 OPERATIONS.
 4.6.10.1* BUILDINGS, OR PORTIONS OF BUILDINGS, SHALL BE
 PERMITTED TO
 BE OCCUPIED DURING CONSTRUCTION, REPAIR, ALTERATIONS,
 OR ADDITIONS
 ONLY WHERE REQUIRED MEANS OF EGRESS AND REQUIRED FIRE
 PROTECTION
 FEATURES ARE IN PLACE AND CONTINUOUSLY MAINTAINED FOR
 THE PORTION
 OCCUPIED OR WHERE ALTERNATIVE LIFE SAFETY MEASURES
 ACCEPTABLE TO
 THE AUTHORITY HAVING JURISDICTION ARE IN PLACE.
  
 PLEASE PROVIDE A DETAILED SCOPE OF WORK THAT INCLUDES
 HOW THE EGRESS WILL BE MAINTAINED DURING THE ENTIRE
 DEMO AND INSTALLATION PROCESS.
  
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  