Notes |
Date |
Text |
2020-12-31 12:47:25 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | 1) THE PROPOSED PROJECT APPEARS TO RESTRICT THE ONLY | | EGRESS ROUTE FROM THE UNITS. | | | | PER NFPA 101, CH 4 | | | | 4.6.10 CONSTRUCTION, REPAIR, AND IMPROVEMENT | | OPERATIONS. | | 4.6.10.1* BUILDINGS, OR PORTIONS OF BUILDINGS, SHALL BE | | PERMITTED TO | | BE OCCUPIED DURING CONSTRUCTION, REPAIR, ALTERATIONS, | | OR ADDITIONS | | ONLY WHERE REQUIRED MEANS OF EGRESS AND REQUIRED FIRE | | PROTECTION | | FEATURES ARE IN PLACE AND CONTINUOUSLY MAINTAINED FOR | | THE PORTION | | OCCUPIED OR WHERE ALTERNATIVE LIFE SAFETY MEASURES | | ACCEPTABLE TO | | THE AUTHORITY HAVING JURISDICTION ARE IN PLACE. | | | | PLEASE PROVIDE A DETAILED SCOPE OF WORK THAT INCLUDES | | HOW THE EGRESS WILL BE MAINTAINED DURING THE ENTIRE | | DEMO AND INSTALLATION PROCESS. | | | | | | | | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | ABOVE. | | | | | | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | RE-SUBMITTAL OF THE ABOVE. | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | |
|