Plan Review Notes
Plan Review Notes For Permit 20120465
Permit Number 20120465
Review Stop B
Sequence Number 1
Notes
Date Text
2021-01-12 10:55:42STAIR REPLACEMENT
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE SHOW THE DESIGN DATA USED PER FBC 1603.1
 2) DRAWINGS NEED TO BE SIGNED BY THE DESIGNER.
 3) PLEASE SHOW THE SPECIFIC LOCATION FOR EACH STAIR
 REPLACEMENT ON THE SITE PLAN.
 4) PLEASE SHOW THE MEANS OF EGRESS DURING CONSTRUCTION
 FBC 3302.1 ALTERATIONS, REPAIRS AND ADDITIONS.
 REQUIRED EXITS, EXISTING STRUCTURAL ELEMENTS, FIRE
 PROTECTION DEVICES AND SANITARY SAFEGUARDS SHALL BE
 MAINTAINED AT ALL TIMES DURING ALTERATIONS, REPAIRS OR
 ADDITIONS TO ANY BUILDING OR STRUCTURE.
 EXCEPTIONS:
 1.WHERE SUCH REQUIRED ELEMENTS OR DEVICES ARE BEING
 ALTERED OR REPAIRED, ADEQUATE SUBSTITUTE PROVISIONS
 SHALL BE MADE.
 2.MAINTENANCE OF SUCH ELEMENTS AND DEVICES IS NOT
 REQUIRED WHEN THE EXISTING BUILDING IS NOT OCCUPIED.