2021-04-01 10:54:12 | PLAN |
| REVIEW COMMENTS |
| 3RD REVIEW: FBC SIXTH EDITION (2017) |
| ROBERT MCDOUGAL, CBO |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561) 805-6714 |
| [email protected] |
| |
| [ PREVIOUS COMMENTS HAVE NOT BEEN ADDRESSED ] |
| DENIED BY BUILDING |
| PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| |
| 1) NOT RESOLVED. [ SUBMIT THE CALCULATIONS/DATA THAT |
| WERE USED TO DETERMINE THE DESIGN PRESSURES. SPECIFY |
| THE WALL ZONES THAT THE OPENINGS ARE LOCATED IN. THE |
| ENGINEER'S LETTER REFERS TO A TRIPLE WINDOW AND NOA |
| NO.20-0722.09. THE PERMIT APPLICATION ONLY INDICATES |
| THAT (2) SGDS ARE BEING REPLACED. PLEASE CLARIFY.]THIS |
| PROJECT IS LOCATED IN A HIGH RISE BUILDING. PLEASE |
| SUBMIT DIGITALLY SIGNED AND SEALED COMPONENT & CLADDING |
| PRESSURES FOR THE TWO SLIDING GLASS DOORS FROM A |
| FLORIDA LICENSED ENGINEER. THE WIND SPEED IS 170 MPH |
| AND THE EXPOSURE CATEGORY IS D. FBC 107.2.1.2 |
| |
| 2) NOT RESOLVED. CIRCLE OR HI-LIGHT THE ITEMS IN THE |
| PRODUCT APPROVAL THAT APPLY TO THIS PROJECT, INCLUDING |
| THE DESIGN PRESSURES FOR THE SPECIFIC DOORS THAT WILL |
| BE INSTALLED. NOT: THE DESIGN PRESSURES FOR THE DOORS |
| MUST BE GREATER THAN THE COMPONENT AND CLADDING |
| PRESSURES DETERMINED BY THE ENGINEER. FBC 107.2.1 |
| |
| 3) PARTIALLY RESOLVED. [ THE WALL ZONES WERE NOT |
| SPECIFIED.] SPECIFY THE HEIGHT OF THE BUILDING AND THE |
| WALL ZONE THAT EACH OF THE DOORS IS LOCATED IN. FBC |
| CHAPTER 16 |
| |
| 4) NEW COMMENT. SUBMIT A RESPONSE LETTER STATING HOW |
| EACH REVIEW COMMENT HAS BEEN ADDRESSED. |