2021-02-17 11:45:39PLAN
 REVIEW COMMENTS
 2ND REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) NOT RESOLVED. [ SUBMIT THE CALCULATIONS/DATA THAT
 WERE USED TO DETERMINE THE DESIGN PRESSURES. SPECIFY
 THE WALL ZONES THAT THE OPENINGS ARE LOCATED IN. THE
 ENGINEER'S LETTER REFERS TO A TRIPLE WINDOW AND NOA
 NO.20-0722.09. THE PERMIT APPLICATION ONLY INDICATES
 THAT (2) SGDS ARE BEING REPLACED. PLEASE CLARIFY.]THIS
 PROJECT IS LOCATED IN A HIGH RISE BUILDING. PLEASE
 SUBMIT DIGITALLY SIGNED AND SEALED COMPONENT & CLADDING
 PRESSURES FOR THE TWO SLIDING GLASS DOORS FROM A
 FLORIDA LICENSED ENGINEER. THE WIND SPEED IS 170 MPH
 AND THE EXPOSURE CATEGORY IS D. FBC 107.2.1.2
  
 2) NOT RESOLVED. CIRCLE OR HI-LIGHT THE ITEMS IN THE
 PRODUCT APPROVAL THAT APPLY TO THIS PROJECT, INCLUDING
 THE DESIGN PRESSURES FOR THE SPECIFIC DOORS THAT WILL
 BE INSTALLED. NOT: THE DESIGN PRESSURES FOR THE DOORS
 MUST BE GREATER THAN THE COMPONENT AND CLADDING
 PRESSURES DETERMINED BY THE ENGINEER. FBC 107.2.1
  
 3) PARTIALLY RESOLVED. [ THE WALL ZONES WERE NOT
 SPECIFIED.] SPECIFY THE HEIGHT OF THE BUILDING AND THE
 WALL ZONE THAT EACH OF THE DOORS IS LOCATED IN. FBC
 CHAPTER 16