Plan Review Notes For Permit 20120459 |
Permit Number |
20120459 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2021-02-17 11:45:39 | PLAN | | REVIEW COMMENTS | | 2ND REVIEW: FBC SIXTH EDITION (2017) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) NOT RESOLVED. [ SUBMIT THE CALCULATIONS/DATA THAT | | WERE USED TO DETERMINE THE DESIGN PRESSURES. SPECIFY | | THE WALL ZONES THAT THE OPENINGS ARE LOCATED IN. THE | | ENGINEER'S LETTER REFERS TO A TRIPLE WINDOW AND NOA | | NO.20-0722.09. THE PERMIT APPLICATION ONLY INDICATES | | THAT (2) SGDS ARE BEING REPLACED. PLEASE CLARIFY.]THIS | | PROJECT IS LOCATED IN A HIGH RISE BUILDING. PLEASE | | SUBMIT DIGITALLY SIGNED AND SEALED COMPONENT & CLADDING | | PRESSURES FOR THE TWO SLIDING GLASS DOORS FROM A | | FLORIDA LICENSED ENGINEER. THE WIND SPEED IS 170 MPH | | AND THE EXPOSURE CATEGORY IS D. FBC 107.2.1.2 | | | | 2) NOT RESOLVED. CIRCLE OR HI-LIGHT THE ITEMS IN THE | | PRODUCT APPROVAL THAT APPLY TO THIS PROJECT, INCLUDING | | THE DESIGN PRESSURES FOR THE SPECIFIC DOORS THAT WILL | | BE INSTALLED. NOT: THE DESIGN PRESSURES FOR THE DOORS | | MUST BE GREATER THAN THE COMPONENT AND CLADDING | | PRESSURES DETERMINED BY THE ENGINEER. FBC 107.2.1 | | | | 3) PARTIALLY RESOLVED. [ THE WALL ZONES WERE NOT | | SPECIFIED.] SPECIFY THE HEIGHT OF THE BUILDING AND THE | | WALL ZONE THAT EACH OF THE DOORS IS LOCATED IN. FBC | | CHAPTER 16 |
|