2021-04-05 09:14:25 | 3RD REVIEW FBC-2017 RES. |
| PERMIT- 20120445 |
| 4/5/2021 |
| |
| CODES IN EFFECT: |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| EDITION 2017 |
| FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) THE PRINTED NAME AND SIGNATURE OF KIRK ANGELOCCI |
| (CFC024557) IS REQUIRED ON THE GAS RISER DRAWING AND |
| COMBUSTION AIR CALCULATIONS- SECTION 107.2.1 WPB, AND |
| FLORIDA STATUTES 471.003(2)(H) & 471.025. |
| |
| 2) 2ND REQUEST FOR A CONDENSATE DISPOSAL PLAN FOR THE |
| WATER HEATER. PLEASE REVEW THE RINNAI INSTALL, MANUAL |
| WHICH REQUIRES CONDENSATE DISPOSAL IN ACCDORDANCE WITH |
| LOCAL CODES, AND ALSO RECOMMENDS INSTALLATION OF A |
| NEUTRALIZER KIT TO PREVENT CORROSION OF THE CONDENSATE |
| DRAIN AND THE PUBLIC SEWER SYSTEM- SECTION G2404.10 FBC |
| RES. PLEASE NOTE THIS COMMENT WAS UNDER THE PLUMBING |
| REVIEW AND NOT THE GAS. I HAVE RELOCATED IT FROM THE |
| PLUMBING REVIEW- PLEASE COMPLY. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |