Plan Review Notes
Plan Review Notes For Permit 20120445
Permit Number 20120445
Review Stop G
Sequence Number 2
Notes
Date Text
2021-02-25 07:57:432ND REVIEW FBC-2017 RES.
 PERMIT- 20120445
 2/25/2021
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE COMBUSTION AIR CALCULATION ON THE SUBMITTED
 WORKSHEET WAS NOT COMPLETED. I COMPLETED THE
 CALCULATIONS BASED ON THE DATA SHOWN ON THE SHEET AND
 THERE IS INADEQUATE COMBUSTION INDOOR COMBUSTION AIR
 FOR THE 89,000 BTU RANGE. ACCORDING TO THE WORKSHEET:
 TOTAL ROOM VOLUME- 2080 CU.FT./89 = 23.37. 23.37 IS
 LESS THAN 50. BASED ON THE WORKSHEET A TOTAL ROOM
 VOLUME OF 4450 CU.FT. IS REQUIRED. IF THERE IS
 INSUFFICIENT ROOM VOLUME THEN ADDITIONAL AIR SHALL BE
 BROUGHT IN USING ONE OF THE METHODS DESCRIBED IN
 SECTION G2407.5.3.1- G2407.8 FBC RES.
  
 2) PLEASE NOTE THAT MAKEUP AIR, NOT COMBUSTION AIR, IS
 REQUIRED FOR THE DRYER- SECTIONS G2407.1 AND G2439.1
 FBC RES. REMOVE THE DRYER FROM THE COMBUSTION AIR
 CALCULATIONS. THE DRAWING APPEARS TO SHOW THAT THE
 DRYER IS BEING INSTALLED IN A CLOSET WITH NO DOOR WHICH
 SHOULD PROVIDE ADEQUATE MAKEUP AIR. PLEASE REFER TO
 MANUFACTURER?S SPECIFICATIONS AND INSTALLATION
 INSTRUCTIONS. THE SPECS AND INSTALL MANUAL SHALL BE
 ONSITE AT TIME OF INSPECTION.
  
 3) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 CONCENTRIC VENT ASSEMBLY- SECTIONS G2427.6.1 &
 G2427.6.5 FBC RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  