Permit Number |
20120440 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2021-01-07 10:53:57 | INTERIOR OFFICE BUILDOUT | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected] | | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 | | AMENDMENTS | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | 1) DRAWINGS SHOW CORRIDOR WALLS BETWEEN ELEVATOR AND | | OFFICES AS NON FIRE RATED. PLEASE SHOW HOW THE EXISTING | | ELEVATOR HOISTWAY IS PROTECTED PER FBC 3006.3 | | 2) PLEASE SHOW THE REQUIRED MANEUVERING CLEARANCE AT | | DOOR (1403) FROM INSIDE THE CONFERENCE ROOM TO COMPLY | | WITH FBC ACCESSIBILITY 404.2.4 | | 3) PLEASE SHOW THE REQUIRED FLOOR SPACE FOR ALL | | ACCESSIBLE ELEMENTS SUCH AS SINK, MICROWAVE, | | REFRIGERATOR ETC. PER FBC 305 |
|