Plan Review Notes
Plan Review Notes For Permit 20120440
Permit Number 20120440
Review Stop B
Sequence Number 1
Notes
Date Text
2021-01-07 10:53:57INTERIOR OFFICE BUILDOUT
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) DRAWINGS SHOW CORRIDOR WALLS BETWEEN ELEVATOR AND
 OFFICES AS NON FIRE RATED. PLEASE SHOW HOW THE EXISTING
 ELEVATOR HOISTWAY IS PROTECTED PER FBC 3006.3
 2) PLEASE SHOW THE REQUIRED MANEUVERING CLEARANCE AT
 DOOR (1403) FROM INSIDE THE CONFERENCE ROOM TO COMPLY
 WITH FBC ACCESSIBILITY 404.2.4
 3) PLEASE SHOW THE REQUIRED FLOOR SPACE FOR ALL
 ACCESSIBLE ELEMENTS SUCH AS SINK, MICROWAVE,
 REFRIGERATOR ETC. PER FBC 305