Plan Review Notes
Plan Review Notes For Permit 20120439
Permit Number 20120439
Review Stop B
Sequence Number 2
Notes
Date Text
2021-03-04 09:36:09INTERIOR OFFICE BUILDOUT
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) NEW DRAWING A4.21 SHOWS TOILET PAPER DISPENSER
 DISTANCE FROM TOILET INCORRECTLY - SHOULD BE 7" TO 9"
 TO THE CENTER LINE OF THE DISPENSER FBC 604.7 (DRAWING
 A0.04 NEEDS TO BE CORRECTED ALSO).
 2) NEW DRAWING A4.21 PLEASE SHOW THE REQUIRED 18" (DOOR
 MANEUVERING CLEARANCE) BESIDE THE DOOR TO ENTER THE
 ACCESSIBLE MEN'S ROOM TOILET COMPARTMENT FBC 404.2.4