2020-12-19 09:41:38 | 1ST REVIEW FBC-2017 MECHANICAL |
| PERMIT-20120439 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| EDITION 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEET M2.1: PLEASE SHOW DAMPERS AT RATED WALLS |
| PENETRATED BY DUCTWORK TO CORRIDOR FROM VAV-4 AND ALSO |
| SHOW DAMPERS FOR EXISTING DUCTWORK AND TRANSFER |
| OPENINGS FOR RETURN PATH PENETRATING ALL RATED WALLS. |
| FBC M 607 |
| |
| 2) PLEASE SHOW THE CORRECT OUTDOOR AIR FOR THIS TENANT |
| SPACE. |
| |
| 5/1000 SQ. FT.- 7625/1000 = 7.625; 7.625 X 5 =38.125 X5 |
| = 190.625 + 7625 X .06 = 457.5; 38.125 + 457.50 = 496 |
| CFM OF OUTDOOR AIR. FBC M TABLE 403.3.1.1 |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| UPDATED. |
| |