Plan Review Notes
Plan Review Notes For Permit 20120394
Permit Number 20120394
Review Stop B
Sequence Number 3
Notes
Date Text
2021-02-01 13:26:05GENERATOR
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 3RD REVIEW
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) GENERATOR EXHAUST NEEDS TO BE 10' FROM OPENINGS PER
 FBC R303.5.1 INTAKE OPENINGS.
 MECHANICAL AND GRAVITY OUTDOOR AIR INTAKE OPENINGS
 SHALL BE LOCATED NOT LESS THAN 10 FEET (3048 MM) FROM
 ANY HAZARDOUS OR NOXIOUS CONTAMINANT,
  