2020-12-10 15:52:58ROOFING REVISION SECOND BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 NOTE: SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK
 SHALL COMPLY WITH THE MATERIALS AND METHODS
 REQUIREMENTS IN THE FLORIDA BUILDING CODE.
  
  
 1- PROVIDE NEW ROOFING PRODUCT APPROVAL AND CLEARLY
 MARK WHICH APPROVED ASSEMBLY IS GOING TO BE INSTALLED
 TO VERIFY COMPLIANCE WITH THE DESIGN PRESSURES. NOTE:
 IF THE SELECTED ASSEMBLY DOESN'T MEETT THE DESIGN
 PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED
 RAS 117 CALCULATIONS ARE REQUIRED. SEE LIMITATIONS ON
 PRODUCT APPROVAL.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 RESPONSE:
 NOA 20-0902.19 SUBMITTED:
 SELECTED ASSEMBLY ON PAGE 23 OF 29 HAS A MAXIMUM DESIGN
 PRESSURE OF -52.5 PSF. THESE DESIGN PRESSURES ARE NOT
 ENOUGH TO MEE THE DESIGN PRESSURES AT THE PERIMETER AND
 CORNER AREAS. SEC. R301.2.1 FBC-RESIDENTIAL. NEED TO
 PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS AS
 REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE OF NOA.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER