2020-12-08 16:27:43 | ROOFING REVISION BUILDING REVIEW COMMENTS |
| CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| |
| NOTE: SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK |
| SHALL COMPLY WITH THE MATERIALS AND METHODS |
| REQUIREMENTS IN THE FLORIDA BUILDING CODE. |
| |
| 1- SELF-ADHERING MODIFIED BITUMEN ROOFING SYSTEM NOA |
| 18-1219.01 SUBMITTED IS FOR CEMENTITIOUS WOOD FIBER |
| DECKS. THIS TYPE OF ROOD DECKING DOESN'T SEEM TO MATCH |
| ROOF DECK OF THIS STRUCTURE. ACCORDING TO CITY RECORDS |
| THIS IS A WOOD FRAMED RESIDENTIAL STRUCTURE. TYPICALLY, |
| THIS TYPE OF FRAMED BUILDINGS DON'T HAVE CEMENTITIOUS |
| WOOD FIBER DECKS. MOST LIKELY, THERE IS A WOOD DECK IN |
| THIS STRUCTURE. REVISE ROOFING NOA OR PROVIDE PROOF |
| THAT THIS IS A CEMENTITIOUS WOOD FIBER DECK. |
| SEC. 107.2.1 CITY AMENDMENTS. |
| |
| 2- PROVIDE NEW ROOFING PRODUCT APPROVAL AND CLEARLY |
| MARK WHICH APPROVED ASSEMBLY IS GOING TO BE INSTALLED |
| TO VERIFY COMPLIANCE WITH THE DESIGN PRESSURES. NOTE: |
| IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN |
| PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED |
| RAS 117 CALCULATIONS ARE REQUIRED. SEE LIMITATIONS ON |
| PRODUCT APPROVAL. |
| SEC. 107.2.1 CITY AMENDMENTS. |
| |
| PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| QUESTIONS REGARDING THESE COMMENTS, |
| JULIO GOMEZ |