2020-12-17 16:10:21 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| FAC = FLORIDA ADMINISTRATIVE CODE |
| |
| REVIEW STATUS: FAILED. |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW |
| . |
| 1) PLEASE INCLUDE RISER DIAGRAM SHOWING SERVICE |
| ENTRANCE CONDUCTOR SIZE AND GROUNDING DETAILS. |
| 2) PLEASE SPECIFY AIC RATING OF NEW SERVICE PANEL. |
| 3) ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT, |
| SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS INSTALLED IN |
| KITCHENS, FAMILY ROOMS, DINING ROOMS, LIVING ROOMS, |
| PARLORS, LIBRARIES, DENS, BEDROOMS, SUN-ROOMS, |
| RECREATIONS ROOMS, CLOSETS, HALLWAYS, LAUNDRY AREAS AND |
| SIMILAR ROOMS OR AREAS SHALL BE AFCI PROTECTED. PROVIDE |
| CORRECTION. NEC 210.12; FBC RE E3902.16 (A NOTE WILL |
| SUFFICE) |
| 4) PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE |
| LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF |
| THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE. |
| FBC EC R404.1 |
| 5) TAMPER-RESISTANT RECEPTACLES REQUIRED AS PER FBC RE |
| E4002.14 (A NOTE WILL SUFFICE) |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN |
| PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE |
| 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A |
| COMPLETED RESUBMITTAL FORM, VIA EMAIL TO |
| [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT |
| NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE |
| RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE: |
| |
| HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B |
| UILDING-PERMIT-FORMS |
| |