2020-12-17 10:49:461ST REVIEW FBC-2017 PLUMBING
 PERMIT- 20120261
 12/17/2020
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P0.1: PROVIDE NOTES FOR REQUIRED SLAB XRAY
 PROCEDURE AND REPAIR OF THE EXISTING SLAB FOR THE NEW
 DRAIN INSTALLATION- SECTION 107.2.1 WPB.
  
 2) P0.1: PROVIDE A UL TESTED AND APPROVED FIRESTOPPING
 ASSEMBLY DETAIL FOR SEALING THE ANNULAR SPACE AROUND
 THE NEW DRAIN PIPE PENETRATION- SECTION 713.4.1.2 FBC
 B.
  
 4) P0.1: PROVIDE A BACKFLOW PREVENTER FOR THE SUPPLY
 LINE TO THE COFFEE MAKER- SECTION 608.3 FBC P.
  
 3) FBC-17 ACCESSIBILITY:
  
 A) SHOW THE CLEAR FLOOR SPACE FORWARD OR PARALLEL
 APPROACH DIAGRAM AND DIMENSION AT THE NEW SINK AND
 COFFEE MAKER- SECTIONS 305, 306, AND 606.2.
  
 B) SHOW COMPLIANCE WITH SECTIONS 904.5.1 & 308 (REACH
 RANGES) FOR THE NEW SINK AND COFFEE MAKER.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  