2020-12-17 10:49:46 | 1ST REVIEW FBC-2017 PLUMBING |
| PERMIT- 20120261 |
| 12/17/2020 |
| |
| CODES IN EFFECT: |
| FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEET P0.1: PROVIDE NOTES FOR REQUIRED SLAB XRAY |
| PROCEDURE AND REPAIR OF THE EXISTING SLAB FOR THE NEW |
| DRAIN INSTALLATION- SECTION 107.2.1 WPB. |
| |
| 2) P0.1: PROVIDE A UL TESTED AND APPROVED FIRESTOPPING |
| ASSEMBLY DETAIL FOR SEALING THE ANNULAR SPACE AROUND |
| THE NEW DRAIN PIPE PENETRATION- SECTION 713.4.1.2 FBC |
| B. |
| |
| 4) P0.1: PROVIDE A BACKFLOW PREVENTER FOR THE SUPPLY |
| LINE TO THE COFFEE MAKER- SECTION 608.3 FBC P. |
| |
| 3) FBC-17 ACCESSIBILITY: |
| |
| A) SHOW THE CLEAR FLOOR SPACE FORWARD OR PARALLEL |
| APPROACH DIAGRAM AND DIMENSION AT THE NEW SINK AND |
| COFFEE MAKER- SECTIONS 305, 306, AND 606.2. |
| |
| B) SHOW COMPLIANCE WITH SECTIONS 904.5.1 & 308 (REACH |
| RANGES) FOR THE NEW SINK AND COFFEE MAKER. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |