2021-02-12 08:49:30 | PLAN | | REVIEW COMMENTS | | | | 2ND REVIEW: FBC SIXTH EDITION (2017) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING, PREVIOUS COMMENT WAS NOT ADDRESSED. | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) THE SURVEY NOTES THAT THE EXHAUST IS 5 FEET FROM | | OPENINGS. | | THE GENERATOR EXHAUST IS REQUIRED TO BE 10 FEET FROM | | ANY OPENINGS INTO THE BUILDING. R303.5.1 INTAKE | | OPENINGS. MECHANICAL AND GRAVITY OUTDOOR AIR INTAKE | | OPENINGS SHALL BE LOCATED NOT LESS THAN 10 FEET (3048 | | MM) FROM ANY HAZARDOUS OR NOXIOUS CONTAMINANT, SUCH AS | | VENTS, CHIMNEYS, PLUMBING VENTS, STREETS, ALLEYS, | | PARKING LOTS AND LOADING DOCKS. | | | | |
|