2021-02-08 08:02:04PLAN
 REVIEW COMMENTS
  
 3RD REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 THE PREVIOUS COMMENTS WERE NOT ADDRESSED. SEE BELOW.
 THE BUILDING OFFICIAL HAS MADE AN OFFICIAL DETERMINED
 THAT GENERATOR EXHAUST IS TO BE LOCATED 10 FEET FROM
 OPENINGS.
  
 1) FBC-R303.5.1 INTAKE OPENINGS.MECHANICAL AND GRAVITY
 OUTDOOR AIR INTAKE OPENINGS SHALL BE LOCATED NOT LESS
 THAN 10 FEET (3048 MM) FROM ANY HAZARDOUS OR NOXIOUS
 CONTAMINANT, SUCH AS VENTS, CHIMNEYS, PLUMBING VENTS,
 STREETS, ALLEYS, PARKING LOTS AND LOADING DOCKS.
  
 2) SEE SIGNATURE REVIEW.
  