2021-04-29 08:31:03 | FAILED |
| |
| PROVIDE WRITTEN RESPONSE TO COMMENTS. |
| |
| 1) THANK YOU FOR PROVIDING THE GRAPHIC SHOWING HOW THE |
| SIDEWALK CONNECTION TO THE PUBLIC RIGHT-OF-WAY WILL BE |
| PROVIDED TO THE THREE BUILDINGS THAT WILL REMAIN ON THE |
| SITE BOTH DURING CONSTRUCTION AND PRIOR TO THE START OF |
| CONSTRUCTION OF PHASE II. ZONING REVIEWED YOUR PROPOSED |
| PLAN WITH ROBERT BROWN, CHIEF BUILDING OFFICIAL, AND IT |
| IS NOT APPROVED AS SHOWN. YOU MUST CLEARLY SHOW HOW A |
| PEDESTRIAN, INCLUDING ONE COVERED BY THE ADA, CAN |
| SAFELY TRAVERSE FROM THE EXISTING SIDEWALK ON THE |
| MORSELIFE SIDE OF THE SITE TO THE EXISTING SIDEWALK |
| SERVING THE HOMESAFE BUILDINGS. THE ARROWS THAT ARE |
| SHOWN ON THE PLAN FORCE THE PEDESTRIAN TO SHARE DRIVE |
| LANES WITH VEHICLES, WHICH IS NOT PERMITTED. THE |
| PEDESTRIAN MUST BE ABLE TO USE A SIDEWALK OR HAVE A |
| PATH THAT IS SEPARATED FROM THE VEHICULAR TRAVEL LANES. |
| NOTE: THE MINIMUM TRAVEL LANE WIDTH IS 20 FEET FOR FIRE |
| DEPARTMENT ACCESS, SO THE PROPOSED 20 FOOT WIDE |
| CONNECTION CANNOT BE NARROWED. THE PEDESTRIAN ROUTE |
| MUST BE IN PLACE PRIOR TO THE FENCING OF THE |
| CONSTRUCTION SITE. |
| |
| 2) EVEN THOUGH A SEPARATE SITE LIGHTING PERMIT, WITH |
| PLANS, IS REQUIRED, ZONING NOTED THAT THE ELECTRICAL |
| REVIEWER HAD ADDED A PASS STAMP TO SHEET E 0-1-1 THE |
| ELECTRICAL SITE PLAN AND THUS REVIEWED THE PLAN. ZONING |
| WILL NOT APPROVE THE PROPOSED PLAN. |
| |
| A. THE UNDERGROUND DUCT BANK LINES (HIGHLIGHTED BY THE |
| GREEN BOXES ON THE ELECTRONIC VERSION OF THE PLAN) MUST |
| BE MOVED OUT OF THE LANDSCAPE AREAS AS THEY DIRECTLY |
| CONFLICT WITH APPROVED TREE LOCATIONS. THEY CAN BE RUN |
| UNDER THE PAVEMENT. |
| |
| B. THE DUCT BANKS ARE SHOWN COVERED BY COMPACTED EARTH, |
| WHICH IS NOT PERMITTED IN THE LANDSCAPE AREAS. THE TREE |
| ROOTS WILL NOT PROPERLY GROW IN COMPACTED EARTH. |
| ADDITIONALLY, THE TREES NEED A FULL THREE FEET OF COVER |
| FOR PROPER ROOT GROWTH, WHICH DOES NOT OCCUR DUE TO THE |
| INSTALLATION OF THE MYLAR WARNING TAPE AT TWO FEET IN |
| DEPTH. |
| |
| 3) SEPARATE PERMITS WITH PLANS ARE REQUIRED FOR THE |
| FOLLOWING: |
| |
| A. SITE LIGHTING |
| B. BICYCLE RACKS |
| C. HARDSCAPE |
| D. PARKING LOT STRIPING |
| E. PERIMETER WALLS AND FENCES |
| |
| CONTACT ERIC SCHNEIDER @ (561) 822-1446 |
| [email protected] |
| |