2021-04-12 12:19:28 | 3RD REVIEW FBC-2017 PLUMBING |
| PERMIT- 20120145 |
| 4/12/2021 |
| |
| CODES IN EFFECT: |
| FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| COMMENTS FROM THE 1ST AND 2ND REVIEW LISTED BELOW HAVE |
| NOT BEEN COMPLETELY RESOLVED. NOTES HAVE BEEN ADDED FOR |
| FURTHER CLARIFICATION. |
| |
| 3) FAILED. A1.6.1 & P DRAWINGS: BASED ON THE SERVING |
| KITCHEN PLAN IT APPEARS THAT A GREASE INTERCEPTOR MUST |
| BE PROVIDED TO RECEIVE THE DRAINAGE FROM THE HOT FOOD |
| WELL, DISHWASHER, FOOD WASTE DISPOSAL, AND ALL DIRECT |
| OR INDIRECT WASTE RECEPTORS SERVING KITCHEN APPLIANCES |
| AND EQUIPMENT THAT PRODUCE GREASE OR FAT-LADEN WASTE |
| EFFLUENTS- SEE SECTION 1003.3.1 FBC P. CONCERNING THE |
| FOOD WASTE DISPOSAL REFER TO SECTION 1003.3.2 FBC P AND |
| PROVIDE A SOLIDS INTERCEPTOR TO SEPARATE THE DISCHARGE |
| BEFORE CONNECTING TO THE INTERCEPTOR. SHEETS P2.1.1 & |
| P4.1.1: THE ARCHITECT'S RESPONSE INDICATES A GREASE |
| INTERCEPTOR TO BE INSTALLED UNDER THE KITCHEN SINK |
| HOWEVER NOTE 8 ON SHEET P.2.1.1 SPECIFIES A SOLIDS |
| INTERCEPTOR EQUAL TO STRIEM MODEL #HTL-1176-1. PLEASE |
| NOTE THAT HTL-1176-1 IS A HAIR AND LINT INTERCEPTOR. |
| PLEASE PROVIDE THE CORRECT INTERCEPTOR MAKE AND MODEL |
| AND SUBMIT MANUFACTURER'S SPECIFICATIONS. SOLIDS |
| INTERECPTORS ARE REQUIRED FOR FOOD WASTE DISPOSERS |
| CONNECTING TO GREASE INTERCEPTORS- SECTION 1003.3.2. |
| |
| 7) A1.6.4 & A1.6.5: ACCESSIBLE SHOWER: |
| |
| C) FAILED. LOCATION OF CONTROL, FAUCET, AND SHOWER |
| SPRAY IN THE SHOWER- SECTION 608.5.2 FBC ACC. WHERE A |
| SEAT IS PROVIDED, THE CONTROLS, FAUCETS, AND SHOWER |
| SPRAY UNIT SHALL BE INSTALLED ON THE BACK WALL ADJACENT |
| TO THE SEAT WALL AND SHALL BE LOCATED 27 INCHES MAXIMUM |
| FROM THE SEAT WALL. DETAILS ON THE SHEETS SHOW THE |
| CONTROLS ON THE SIDE WALL. |
| |
| E) FAILED SHOWER SEAT DIMENSIONS, HEIGHT, CLEARANCES |
| AND EXTENSIONS AS OUTLINED IN SECTIONS 610.3 & 610.3.2. |
| THE 2 FT. SHOWER SEAT DIMENSION EXCEEDS THE MAX 23 |
| INCHES ALLOWED AS SHOWN IN FIGURE 610.3.2. PLEASE |
| CORRECT THE DETAIL AND PROVIDE COMPLETE DIMENSIONS. |
| |
| 33) FAILED. PLEASE NOTE SEPARATE PERMIT APPLICATIONS |
| AND PLANS ARE REQUIRED FOR THE POTABLE WATER SERVICE |
| BACKFLOW PREVENTER, BACKFLOW PREVENTER FOR THE CHILLER, |
| IRRIGATION SYSTEM, FIRE LINE, FIRE LINE BACKFLOW |
| PREVENTER, AND FIRE SPRINKLER SYSTEM. COMPLETE SETS OF |
| PLANS AND SPECIFICATIONS ARE REQUIRED FOR REVIEW AND |
| PERMIT ISSUANCE- SECTION 107.2.1 WPB. PROVIDE A LIST OF |
| SEPARATE PERMITS ON THE PLANS INCLUDING THE RELOCATION |
| OF BF PREVENTERS SHOWN ON C09. |
| |
| A) FAILED. BACKFLOW PREVENTERS: PLEASE NOTE THAT FL. |
| LICENSED PLUMBING CONTRACTORS SHALL OBTAIN SEPARATE |
| PERMITS FOR INSTALLATION OF THE BACKFLOW PREVENTERS IN |
| ACCORDANCE WITH SECTION 105.1 WPB AND SEC. 90-33 WPB |
| CODE OF ORDINANCES. THE DEVICES SHALL BE TESTED AND |
| CERTIFIED BY THE WPB UTILITIES DEPARTMENT PRIOR TO |
| FINAL INSPECTION BY THE BUILDING DEPARTMENT. PLEASE |
| CONTACT THE WPB UTILITIES CENTRAL OPERATIONS DEPT.AT |
| 561-822-2210 FOR FURTHER INFORMATION. SEE COMMENT #33. |
| |
| B) FAILED. GREASE INTERCEPTOR: SUBMITTED PLANS SHALL |
| INCLUDE GREASE WATER CALCULATIONS IN ACCORDANCE WITH |
| SECTION 1003.3.4 FOR HYDROMECHANICAL INTERCEPTORS OR |
| 1003.3.6 FOR GRAVITY TYPE INTERCEPTORS. MANUFACTURER'S |
| SPECIFICATIONS AND INSTALLATION MANUALS SHALL ALSO BE |
| SUBMITTED FOR REVIEW. SEE ADDED NOTES UNDER COMMENT #3 |
| ABOVE. |
| |
| NEW COMMENT. |
| |
| 1) SHEET A1.64: THE DOOR TO THE WOMEN'S TLT. (P131) |
| SHALL NOT SWING INTO THE CLEAR FLOOR SPACE FOR THE |
| LAVATORY- SECTION 603.2.3 FBC ACC. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |
| CHRISTOPHER L. COLE |
| MECHANICAL/PLUMBING PLANS EXAMINER |
| 401 CLEMATIS STREET |
| WEST PALM BEACH FL 33401 |
| 561-805-6719 |
| [email protected] |
| |