Plan Review Notes
Plan Review Notes For Permit 20120145
Permit Number 20120145
Review Stop P
Sequence Number 3
Notes
Date Text
2021-04-12 12:19:283RD REVIEW FBC-2017 PLUMBING
 PERMIT- 20120145
 4/12/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
 COMMENTS FROM THE 1ST AND 2ND REVIEW LISTED BELOW HAVE
 NOT BEEN COMPLETELY RESOLVED. NOTES HAVE BEEN ADDED FOR
 FURTHER CLARIFICATION.
  
 3) FAILED. A1.6.1 & P DRAWINGS: BASED ON THE SERVING
 KITCHEN PLAN IT APPEARS THAT A GREASE INTERCEPTOR MUST
 BE PROVIDED TO RECEIVE THE DRAINAGE FROM THE HOT FOOD
 WELL, DISHWASHER, FOOD WASTE DISPOSAL, AND ALL DIRECT
 OR INDIRECT WASTE RECEPTORS SERVING KITCHEN APPLIANCES
 AND EQUIPMENT THAT PRODUCE GREASE OR FAT-LADEN WASTE
 EFFLUENTS- SEE SECTION 1003.3.1 FBC P. CONCERNING THE
 FOOD WASTE DISPOSAL REFER TO SECTION 1003.3.2 FBC P AND
 PROVIDE A SOLIDS INTERCEPTOR TO SEPARATE THE DISCHARGE
 BEFORE CONNECTING TO THE INTERCEPTOR. SHEETS P2.1.1 &
 P4.1.1: THE ARCHITECT'S RESPONSE INDICATES A GREASE
 INTERCEPTOR TO BE INSTALLED UNDER THE KITCHEN SINK
 HOWEVER NOTE 8 ON SHEET P.2.1.1 SPECIFIES A SOLIDS
 INTERCEPTOR EQUAL TO STRIEM MODEL #HTL-1176-1. PLEASE
 NOTE THAT HTL-1176-1 IS A HAIR AND LINT INTERCEPTOR.
 PLEASE PROVIDE THE CORRECT INTERCEPTOR MAKE AND MODEL
 AND SUBMIT MANUFACTURER'S SPECIFICATIONS. SOLIDS
 INTERECPTORS ARE REQUIRED FOR FOOD WASTE DISPOSERS
 CONNECTING TO GREASE INTERCEPTORS- SECTION 1003.3.2.
  
 7) A1.6.4 & A1.6.5: ACCESSIBLE SHOWER:
  
 C) FAILED. LOCATION OF CONTROL, FAUCET, AND SHOWER
 SPRAY IN THE SHOWER- SECTION 608.5.2 FBC ACC. WHERE A
 SEAT IS PROVIDED, THE CONTROLS, FAUCETS, AND SHOWER
 SPRAY UNIT SHALL BE INSTALLED ON THE BACK WALL ADJACENT
 TO THE SEAT WALL AND SHALL BE LOCATED 27 INCHES MAXIMUM
 FROM THE SEAT WALL. DETAILS ON THE SHEETS SHOW THE
 CONTROLS ON THE SIDE WALL.
  
 E) FAILED SHOWER SEAT DIMENSIONS, HEIGHT, CLEARANCES
 AND EXTENSIONS AS OUTLINED IN SECTIONS 610.3 & 610.3.2.
 THE 2 FT. SHOWER SEAT DIMENSION EXCEEDS THE MAX 23
 INCHES ALLOWED AS SHOWN IN FIGURE 610.3.2. PLEASE
 CORRECT THE DETAIL AND PROVIDE COMPLETE DIMENSIONS.
  
 33) FAILED. PLEASE NOTE SEPARATE PERMIT APPLICATIONS
 AND PLANS ARE REQUIRED FOR THE POTABLE WATER SERVICE
 BACKFLOW PREVENTER, BACKFLOW PREVENTER FOR THE CHILLER,
 IRRIGATION SYSTEM, FIRE LINE, FIRE LINE BACKFLOW
 PREVENTER, AND FIRE SPRINKLER SYSTEM. COMPLETE SETS OF
 PLANS AND SPECIFICATIONS ARE REQUIRED FOR REVIEW AND
 PERMIT ISSUANCE- SECTION 107.2.1 WPB. PROVIDE A LIST OF
 SEPARATE PERMITS ON THE PLANS INCLUDING THE RELOCATION
 OF BF PREVENTERS SHOWN ON C09.
  
 A) FAILED. BACKFLOW PREVENTERS: PLEASE NOTE THAT FL.
 LICENSED PLUMBING CONTRACTORS SHALL OBTAIN SEPARATE
 PERMITS FOR INSTALLATION OF THE BACKFLOW PREVENTERS IN
 ACCORDANCE WITH SECTION 105.1 WPB AND SEC. 90-33 WPB
 CODE OF ORDINANCES. THE DEVICES SHALL BE TESTED AND
 CERTIFIED BY THE WPB UTILITIES DEPARTMENT PRIOR TO
 FINAL INSPECTION BY THE BUILDING DEPARTMENT. PLEASE
 CONTACT THE WPB UTILITIES CENTRAL OPERATIONS DEPT.AT
 561-822-2210 FOR FURTHER INFORMATION. SEE COMMENT #33.
  
 B) FAILED. GREASE INTERCEPTOR: SUBMITTED PLANS SHALL
 INCLUDE GREASE WATER CALCULATIONS IN ACCORDANCE WITH
 SECTION 1003.3.4 FOR HYDROMECHANICAL INTERCEPTORS OR
 1003.3.6 FOR GRAVITY TYPE INTERCEPTORS. MANUFACTURER'S
 SPECIFICATIONS AND INSTALLATION MANUALS SHALL ALSO BE
 SUBMITTED FOR REVIEW. SEE ADDED NOTES UNDER COMMENT #3
 ABOVE.
  
 NEW COMMENT.
  
 1) SHEET A1.64: THE DOOR TO THE WOMEN'S TLT. (P131)
 SHALL NOT SWING INTO THE CLEAR FLOOR SPACE FOR THE
 LAVATORY- SECTION 603.2.3 FBC ACC.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  