Plan Review Notes
Plan Review Notes For Permit 20120145
Permit Number 20120145
Review Stop P
Sequence Number 2
Notes
Date Text
2021-02-17 12:46:422ND REVIEW FBC-2017 PLUMBING
 PERMIT- 20120145
 2/16//2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
 COMMENTS FROM THE 1ST REVIEW THAT HAVE PASSED ARE
 REMOVED. FAILED COMMENTS FROM THE 1ST REVIEW BELOW ARE
 MARKED FAILED WITH ADDITIONAL NOTES. ADDITIONAL NOTES
 HAVE BEEN ADDED TO SOME PASSED COMMENTS.
  
 1) FAILED. SHEETS LS1.1 & LS1.2: PLEASE INCLUDE THE
 REQUIRED SERVICE SINKS IN THE PLUMBING FIXTURE
 CALCULATIONS- TABLE 403.1 FBC P. THREE SERVICE SINKS
 ARE REQUIRED FOR THE FACILITY. BASED ON TABLE 403.1 AND
 THE OCCUPANT LOAD IN PERCENTAGES: BUSINESS- 2.71 +
 ASSEMBLY- .194 = 2.904. MINIMUM 3 SERVICE SINKS. PLEASE
 REVISE THE PLANS ACCORDINGLY.
  
 3) FAILED. A1.6.1 & P DRAWINGS: BASED ON THE SERVING
 KITCHEN PLAN IT APPEARS THAT A GREASE INTERCEPTOR MUST
 BE PROVIDED TO RECEIVE THE DRAINAGE FROM THE HOT FOOD
 WELL, DISHWASHER, FOOD WASTE DISPOSAL, AND ALL DIRECT
 OR INDIRECT WASTE RECEPTORS SERVING KITCHEN APPLIANCES
 AND EQUIPMENT THAT PRODUCE GREASE OR FAT-LADEN WASTE
 EFFLUENTS- SEE SECTION 1003.3.1 FBC P. CONCERNING THE
 FOOD WASTE DISPOSAL REFER TO SECTION 1003.3.2 FBC P AND
 PROVIDE A SOLIDS INTERCEPTOR TO SEPARATE THE DISCHARGE
 BEFORE CONNECTING TO THE INTERCEPTOR. BASED ON THE
 NARRATIVE RESPONSE TO COMMENTS, PLEASE PLACE A NOTE ON
 THE PLANS INDICATING NO FOOD PREPPARATION OR COOKING OF
 MEATS, FISH OR OTHER GREASE PRODUCING FOODS ALLOWED IN
 THE SERVING KITCHEN WITHOUT INSTALLATION OF A GREASE
 TRAP.
  
 4) FAILED. A1.6.1, P0.0.1, & P2.1.1: THE SERVING
 KITCHEN SHOWS AN FD UNDER THE HOT FOOD WELL AND OTHER
 FLOOR DRAINS THAT ARE NOT INCLUDED IN THE FIXTURE
 SCHEDULE. CONCERNING THE FLOOR DRAIN SERVING THE FOOD
 WELL REFER TO SECTIONS 802.1 & 802.3: OTHER THAN HUB
 DRAINS THAT RECEIVE ONLY CLEAR-WATER WASTE AND
 STANDPIPES, A REMOVABLE STRAINER OR BASKET SHALL COVER
 THE OUTLET OF WASTE RECEPTORS. THE DISHWASHER SHALL
 ALSO DISCHARGE TO THE DRAINAGE SYSTEM THROUGH AN
 INDIRECT WASTE PIPE- PLEASE SECTIONS AND 802.3.1,
 802.3.2 AND 427.1 FOR INDIRECT WASTE RECEPTOR
 COMPLIANCES. THE PLANS ALSO SHOW AN ICE MAKER AND
 BEVERAGE DISPENSERS IN THE KITCHEN WITH NO INDIRECT
 WASTE RECEPTORS BELOW THEM TO RECEIVE CONDENSATE
 DRAINAGE- SECTION 802.1 FBC P. PLEASE NOTE THAT
 CONDENSATE FROM COOLING COILS SHALL NOT DRAIN INTO THE
 CITY SANITARY SYSTEM- SECTION 90-126 WPB CODE OF
 ORDINANCES. CONCERNING THE ICE MAKER HOW IS THIS ISSUE
 BEING ADDRESSED? WILL THE UNIT PRODUCE CONDENSATE?
  
 7) A1.6.4 & A1.6.5: ACCESSIBLE SHOWER, FBC ACC. SHEET
 A1.6.5 WITH SHOWER DETAILS WAS NOT UPLOADED PROPERLY
 AND CANNOT BE VIEWED.
  
 A) PASSED. CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR
 THE SHOWER- SECTION 608.2.1
 B) FAILED. LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF
 GRAB BARS- SECTION 608.3 AND 608.3.1.
 C) FAILED. LOCATION OF CONTROL, FAUCET, AND SHOWER
 SPRAY IN THE SHOWER- SECTION 608.5.1.
 D) FAILED. SHOWER SPRAY UNIT SPECIFICATIONS PER SECTION
 608.6.
 E) PASSED. SHOWER SEAT DIMENSIONS, HEIGHT, CLEARANCES
 AND EXTENSIONS AS OUTLINED IN SECTIONS 610.3 & 610.3.2.
 9) FAILED. SINKS- P0.0.1: REFER TO SECTION 212.3 FBC
 ACC WHICH REQUIRES A MINIMUM OF 5%, BUT NO FEWER THAN
 ONE SINK OF EACH TYPE TO BE ACCESSIBLE. THIS WOULD
 INCLUDE THE L1, S1, S2, S3, S4, & S5 IN USE THROUGHOUT
 THE FACILITY. PLEASE DESIGNATE WHICH SINKS WILL BE MADE
 ACCESSIBLE BY SHOWING THE CLEAR FLOOR SPACE DIAGRAM AND
 DIMENSIONS AT EACH LOCATION ON THE ARCHITECTURAL AND
 PLUMBING DRAWINGS- SECTION 606.2. PROVIDE ELEVATION
 VIEWS FOR EACH ACCESSIBLE SINK SHOWING COMPLIANCE WITH
 SECTIONS 606.3, 306, 308, 309- HEIGHTS FROM FINISHED
 FLOORS, KNEE AND TOE CLEARANCES, REACH RANGE TO FAUCET
 CONTROLS, AND OPERABLE PARTS. THE ARCHITECTURAL FLOOR
 PLANS WERE NOT REVISED TO SHOW THE CLEAR FLOOR SPACE
 DIAGRAMS AND DIMENSIONS AND LOCATIONS OF THE ACCESSIBLE
 SINKS- LAV SINKS ARE SHOWN- SEE SHEETS A1.1.1, A1.1.2,
 & A1.1.3. SHEET A1.6.9 SHOWS A TYP. SINK AND A BASE
 CABINET W/ SINK DETAIL. PLEASE CLARIFY WHICH DETAIL
 APPLIES TO WHICH OF THE SINKS OF THE SHOWN ON THE
 PLANS. PLEASE NOTE I AM UNABLE TO VIEW REVISED SHEET
 A1.1.2 DUE TO AN ERROR IN THE UPLOADING PROCESS.
  
 12) PASSED. P0.0.2: PROVIDE A PLUMBING DEVICE SCHEDULE
 INDICATING MAKES, MODEL NUMBERS AND LISTINGS FOR WATER
 HAMMER ARRESTORS, MIXING VALVES, BACKFLOW PREVENTERS,
 AND TRAP PRIMERS- SECTIONS 604.9, 607.2.1, 608.3 AND
 1002.4.1.1 FBC P. DEFERRED SUBMITTALS REQUIRED TO BE
 ONSITE FOR INSPECTION- SEE NOTE FOR COMMENT 34.
  
 15) FAILED. P0.0.1, P2.1.1, P4.1.1: INCLUDE THE WASHING
 MACHINE IN THE FIXTURE SCHEDULE AND INDICATE THE
 MACHINE SHALL DISCHARGE THROUGH AN INTERCEPTOR THAT IS
 PROVIDED WITH A WIRE BASKET OR SIMILAR DEVICE,
 REMOVABLE FOR CLEANING, THAT PREVENTS PASSAGE INTO THE
 DRAINAGE SYSTEM OF SOLIDS 1/2 INCH OR LARGER IN SIZE,
 STRING, RAGS, BUTTONS OR OTHER MATERIALS DETRIMENTAL TO
 THE PUBLIC SEWAGE SYSTEM- SECTION 1003.6 FBC P. PROVIDE
 AN EQUIPMENT SCHEDULE ON THE PLAN AND SUBMIT
 MANUFACTURER'S SPECIFICATIONS TO VERIFY COMPLIANCE.
 PLACE A NOTE ON THE PLANS TO INDICATE FOR DOMESTIC
 PURPOSES, NOT FOR COMMERCIAL FACILITY USE.
  
 16) PASSED. P2.1.1, P4.1.1, P4.1.2: SHOW TRAP PRIMER
 CONNECTIONS FOR EMERGENCY FLOOR DRAINS- SECTION
 1004.2.1 FBC P. REVIEWER WILL PROVIDE A REDLINE NOTE ON
 APPROVED PLANS.
  
 23) FAILED. P.2.2.1, P4.1.2: SHOW THE WATER SUPPLY
 PIPING TO THE WASHING MACHINE, DISHWASHER, BEVERAGE
 DISPENSER, AND ICE MAKER- TABLE 604.5 FBC P, AND
 SECTIONS 107.2.1, 107.3.5.1.3 WPB. SHOW THE REQUIRED
 WATER HAMMER ARRESTORS AND BACKFLOW PREVENTERS-
 SECTIONS 604.9 & 608.3 FBC P. WATER SUPPLY TO THE
 WASHING MACHINE, DISHWASHER, BEVERAGE DISPENSER, AND
 ICE MAKER NOT SHOWN.
  
 24) FAILED. P.2.2.1, P.2.2.2, P2.2.3, P4.1.2: SHOW THE
 3/4 IN. FIXTURE SUPPLY PIPES TO THE WATER CLOSETS AND
 URINALS- TABLE 604.5 FBC P. THE ISOMETRIC APPEARS TO
 SHOW 1/2 IN. CW LINES TO WC AND UR IN SOME LOCATIONS.
 FOR CLARIFICATION PLEASE SHOW THE SUPPLY PIPE SIZES OR
 ADD A NOTE.
  
 26) FAILED. P2.2.1, P2.2.2, P2.2.3, P4.1.2, P5.1.1,
 P5.1.2: INDICATE HOW TEMPERED WATER WILL BE PROVIDED TO
 THE LAVATORIES- SECTION 416.5. SHOW MIXING VALVE
 LOCATIONS- SECTION 607.1.2 FBC P. MIXING VALVE
 LOCATIONS NOT SHOWN ON THE RISER. PLEASE SEE DEFINITONS
 OF TEMPERED WATER AND HOT WATER. IT APPEARS THAT
 TEMPERED WATER LINES ARE LABELED AS HW LINES. PLEASE
 CLARIFY HOW HW WILL BE SUPPLIED TO FIXTURES SUCH AS THE
 MOP SINKS AND WASHING MACHINE THAT REQUIRE HOT WATER-
 SECTION 607.1 FBC P.
  
 28) FAILED. P0.0.2, P2.2.1, P4.1.2: BASED ON THE LEGEND
 IT APPEARS THE HOT WATER SYSTEM RETURN PIPE WILL BE A
 1/2 IN. COLD WATER PIPE. IS THE PIPE SHOWN CORRECTLY? -
 SECTION 107.2.1 WPB AND SECTION C404.6.1 FBC EC.THE 1/2
 IN. RETURN LINE TO EWH-1 IS STILL SHOWN AS A CW PIPE
 BASED ON THE LEGEND SYMBOLS ON P0.0.2.
  
 33) FAILED. PLEASE NOTE SEPARATE PERMIT APPLICATIONS
 AND PLANS ARE REQUIRED FOR THE POTABLE WATER SERVICE
 BACKFLOW PREVENTER, BACKFLOW PREVENTER FOR THE CHILLER,
 GREASE INTERCEPTOR, IRRIGATION SYSTEM, FIRE LINE, FIRE
 LINE BACKFLOW PREVENTER, AND FIRE SPRINKLER SYSTEM.
 COMPLETE SETS OF PLANS AND SPECIFICATIONS ARE REQUIRED
 FOR REVIEW AND PERMIT ISSUANCE- SECTION 107.2.1 WPB.
 PROVIDE A LIST OF SEPARATE PERMITS ON THE PLANS
 INCLUDING THE RELOCATION OF BF PREVENTERS SHOWN ON C09.
 A) FAILED. BACKFLOW PREVENTERS: PLEASE NOTE THAT FL.
 LICENSED PLUMBING CONTRACTORS SHALL OBTAIN SEPARATE
 PERMITS FOR INSTALLATION OF THE BACKFLOW PREVENTERS IN
 ACCORDANCE WITH SECTION 105.1 WPB AND SEC. 90-33 WPB
 CODE OF ORDINANCES. THE DEVICES SHALL BE TESTED AND
 CERTIFIED BY THE WPB UTILITIES DEPARTMENT PRIOR TO
 FINAL INSPECTION BY THE BUILDING DEPARTMENT. PLEASE
 CONTACT THE WPB UTILITIES CENTRAL OPERATIONS DEPT.AT
 561-822-2210 FOR FURTHER INFORMATION. SEE COMMENT #33.
 B) FAILED. GREASE INTERCEPTOR: SUBMITTED PLANS SHALL
 INCLUDE GREASE WATER CALCULATIONS IN ACCORDANCE WITH
 SECTION 1003.3.4 FOR HYDROMECHANICAL INTERCEPTORS OR
 1003.3.6 FOR GRAVITY TYPE INTERCEPTORS. MANUFACTURER'S
 SPECIFICATIONS AND INSTALLATION MANUALS SHALL ALSO BE
 SUBMITTED FOR REVIEW. PROVIDE KITCHEN COOKING NOTE- SEE
 COMMENT #3.
  
 34) PASSED. REQUIRED SUBMITTALS: MANUFACTURER'S
 SPECIFICATIONS AND INSTALL MANUALS FOR THE WATER
 HEATERS, WASHING MACHINE, MIXING VALVES, RECIRCULATION
 PUMPS, SUMP PUMP, PIPE INSULATION, KITCHEN EQUIPMENT
 BACKFLOW PREVENTERS- SECTION 107.1 WPB. PLEASE ALL
 SUBMITTALS MAY BE DEFERRED IN ACCORDANCE WITH SECTION
 107.3.4.1 WPB. PROVIDE A LIST OF DEFERRED SUBMITTALS TO
 BE REVIEWED AND APPROVAL BY THE DESIGN PROFESSIONALS OF
 RECORD, AND TO BE ONSITE AT TIME OF INSPECTION.
  
 NEW COMMENTS
  
 1) SHEET A1.6.2 DETAIL 9: PLEASE CLARIFY IF AMBULATORY
 COMPARTMENTS ARE BEING INSTALLED. BASED ON SECTION
 213.3.1 FBC ACC THEY ARE NOT REQUIRED, HOWEVER IF THE
 INTENTION IS TO PROVIDE ONE, PLEASE REVIEW SECTIONS
 605.8.2, 604.8.2.1 & 604.8.2.2 FBC ACC AND CORRECT THE
 ARCHTECTURAL AND PLUMBING FLOOR PLANS. PLEASE PROVIDE
 GRAB BAR DETAILS- SECTION 604.8.2.3 FBC ACC.
  
 2) A.1.8.1: THE ROOM FINISH SCHEDULE APPEARS TO SHOW
 EPOXY PAINTED GYPSUM WALLBOARD MATERIAL AS WALL FINISH
 FOR THE EVS ROOMS WHERE MOP SINKS ARE LOCATED. PLEASE
 NOTE WALLS AND PARTITIONS WITHIN 2 FEET OF SERVICE
 SINKS, URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH,
 HARD, NONABSORBENT SURFACE, TO A HEIGHT OF NOT LESS
 THAN 4 FEET (1219 MM) ABOVE THE FLOOR, AND EXCEPT FOR
 STRUCTURAL ELEMENTS, THE MATERIALS USED IN SUCH WALLS
 SHALL BE OF A TYPE THAT IS NOT ADVERSELY AFFECTED BY
 MOISTURE- SEE SECTION 1210.2.2 FBC B.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  