Plan Review Notes
Plan Review Notes For Permit 20120145
Permit Number 20120145
Review Stop P
Sequence Number 1
Notes
Date Text
2021-01-06 08:00:141ST REVIEW FBC-2017 PLUMBING
 PERMIT- 20120145
 1/4/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS LS1.1 & LS1.2: PLEASE INCLUDE THE REQUIRED
 SERVICE SINKS IN THE PLUMBING FIXTURE CALCULATIONS-
 TABLE 403.1 FBC P.
  
 2) LS1.1 & LS1.2: THE ARCHITECTURAL AND PLUMBING PLANS
 ARE INDICATING A DEFICIENT NUMBER OF MALE AND FEMALE
 WATER CLOSETS- 11 FOR EACH SEX ARE REQUIRED HOWEVER THE
 PLANS ARE DESIGNATING 8 FOR EACH SEX. PLEASE NOTE THAT
 PLUMBING FIXTURES IN FAMILY OR ASSISTED USE TOILET
 ROOMS ARE PERMITTED TO BE INCLUDED IN THE NUMBER OF
 REQUIRED FIXTURES FOR EITHER THE MALE OR FEMALE
 OCCUPANTS ONLY IN ASSEMBLY AND MERCANTILE OCCUPANCIES-
 SEE SECTION 403.1.2 FBC P. THE PLANS AND FIXTURE
 CALCULATIONS SPECIFY MIXED OCCUPANCIES OF BUSINESS AND
 INSTITUTIONAL- 4.
  
 3) A1.6.1 & P DRAWINGS: BASED ON THE SERVING KITCHEN
 PLAN IT APPEARS THAT A GREASE INTERCEPTOR MUST BE
 PROVIDED TO RECEIVE THE DRAINAGE FROM THE HOT FOOD
 WELL, DISHWASHER, FOOD WASTE DISPOSAL, AND ALL DIRECT
 OR INDIRECT WASTE RECEPTORS SERVING KITCHEN APPLIANCES
 AND EQUIPMENT THAT PRODUCE GREASE OR FAT-LADEN WASTE
 EFFLUENTS- SEE SECTION 1003.3.1 FBC P. CONCERNING THE
 FOOD WASTE DISPOSAL REFER TO SECTION 1003.3.2 FBC P AND
 PROVIDE A SOLIDS INTERCEPTOR TO SEPARATE THE DISCHARGE
 BEFORE CONNECTING TO THE INTERCEPTOR.
  
 4) A1.6.1, P0.0.1, & P2.1.1: THE SERVING KITCHEN SHOWS
 AN FD UNDER THE HOT FOOD WELL AND OTHER FLOOR DRAINS
 THAT ARE NOT INCLUDED IN THE FIXTURE SCHEDULE.
 CONCERNING THE FLOOR DRAIN SERVING THE FOOD WELL REFER
 TO SECTIONS 802.1 & 802.3: OTHER THAN HUB DRAINS THAT
 RECEIVE ONLY CLEAR-WATER WASTE AND STANDPIPES, A
 REMOVABLE STRAINER OR BASKET SHALL COVER THE OUTLET OF
 WASTE RECEPTORS. THE DISHWASHER SHALL ALSO DISCHARGE TO
 THE DRAINAGE SYSTEM THROUGH AN INDIRECT WASTE PIPE-
 PLEASE SECTIONS AND 802.3.1, 802.3.2 AND 427.1 FOR
 INDIRECT WASTE RECEPTOR COMPLIANCES. THE PLANS ALSO
 SHOW AN ICE MAKER AND BEVERAGE DISPENSERS IN THE
 KITCHEN WITH NO INDIRECT WASTE RECEPTORS BELOW THEM TO
 RECEIVE CONDENSATE DRAINAGE- SECTION 802.1 FBC P.
 PLEASE NOTE THAT CONDENSATE FROM COOLING COILS SHALL
 NOT DRAIN INTO THE CITY SANITARY SYSTEM- SECTION 90-126
 WPB CODE OF ORDINANCES.
  
 5) SHEETS A1.6.2, A1.6.4, A1.6.5, & A1.6.6: ACCESSIBLE
 WC COMPARTMENT AND STANDARD WC COMPARTMENT DEPTH
 MEASUREMENTS NOT SHOWN- SECTIONS 604.8.1.1 FBC ACC, AND
 SECTION 405.3.1 FBC P.
  
 6) A1.6.2, A1.6.4, A1.6.5, & A1.6.6: THE ADA PLANS
 SUBMITTED ARE STAMPED FOR REFERENCE ONLY PLEASE PROVIDE
 THE FOLLOWING LIST OF FBC ACC COMPLIANCE DETAILS-
 A) CLEAR FLOOR SPACE DIMENSIONS FOR THE WATER CLOSETS-
 SECTION 604.3.
 B) CLEAR FLOOR SPACE DIMENSIONS FOR THE LAVATORIES-
 SECTION 606.2.
 C) CENTERLINES OF THE WATER CLOSETS FROM THE SIDE
 WALLS- SECTION 604.2.
 D) HEIGHTS OF THE WATER CLOSET SEATS FROM THE FINISHED
 FLOORS- SECTION 604.4.
 E) HEIGHTS OF THE MIRRORS FROM THE FINISHED FLOORS TO
 THE REFLECTIVE SURFACES- SECTION 603.3
 F) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS FOR THE WATER CLOSETS- SECTION 604.5 & 609.4
 G) LOCATIONS OF THE WATER CLOSET FLUSH CONTROLS -
 SECTION 604.6.
 H) CENTERLINES OF THE TOILET PAPER DISPENSER MEASURED
 FROM THE FRONTS OF THE WATER CLOSETS- SECTION 604.7.
 I) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SECTION
 606.2.
 J) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE
 ACCESSIBLE URINALS- 605.3
 H) HEIGHTS OF THE ACCESSIBLE URINAL RIMS ABOVE THE
 FINISHED FLOORS- SECTION 605.2.
  
 7) A1.6.4 & A1.6.5: ACCESSIBLE SHOWER, FBC ACC-
 A) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 SHOWER- SECTION 608.2.1
 B) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS- SECTION 608.3 AND 608.3.1
 C) LOCATION OF CONTROL, FAUCET, AND SHOWER SPRAY IN THE
 SHOWER- SECTION 608.5.1.
 D) SHOWER SPRAY UNIT SPECIFICATIONS PER SECTION 608.6.
 E) SHOWER SEAT DIMENSIONS, HEIGHT, CLEARANCES AND
 EXTENSIONS AS OUTLINED IN SECTIONS 610.3 & 610.3.2.
  
 8) DRINKING FOUNTAINS.
 A) LS1.1 & LS1.2: THE FIXTURE CALCULATIONS INDICATE 5
 DRINKING FOUNTAINS ARE REQUIRED HOWEVER THERE APPEARS
 TO BE ONLY 4 SHOWN ON THE PLANS. PLEASE REFER TO TABLE
 403.1, SECTION 410.3 FBC P, AND SECTION 211.1 FBC ACC.
 PLEASE NOTE THAT A BOTTLE FILLING STATION EWC2 DOES NOT
 MEET THE REQUIREMENT, HOWEVER CLEAR FLOOR SPACE AND
 REACH RANGES TO ACCESS THE BOTTLE FILLER ARE REQUIRED-
 PROVIDE DETAILS SHOWING COMPLIANCE-SECTION 904.5.1 FBC
 ACC.
 B) REFER TO SECTIONS 306, 307, AND 602 FBC ACC AND
 PROVIDE DRINKING FOUNTAIN INSTALLATION DETAILS AND
 ELEVATION VIEWS SHOWING KNEE AND TOE CLEARANCES, SPOUT
 HEIGHTS, AND SPOUT LOCATIONS. SHOW THE REQUIRED 30 X 48
 IN. CLEAR FLOOR SPACE FOR A FORWARD WHEELCHAIR APPROACH
 TO THE FOUNTAIN- SECTION 602.2 FBC ACC, AND SHOW HOW
 THE LOCATIONS OF THE FOUNTAINS WILL BE IN COMPLIANCE
 WITH SECTION 307.2 PROTRUSION LIMITS.
  
 9) SINKS- P0.0.1: REFER TO SECTION 212.3 FBC ACC WHICH
 REQUIRES A MINIMUM OF 5%, BUT NO FEWER THAT ONE SINK OF
 EACH TYPE TO BE ACCESSIBLE. THIS WOULD INCLUDE THE L1,
 S1, S2, S3, S4, & S5 IN USE THROUGHOUT THE FACILITY.
 PLEASE DESIGNATE WHICH SINKS WILL BE MADE ACCESSIBLE BY
 SHOWING THE CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS AT
 EACH LOCATION ON THE ARCHITECTURAL AND PLUMBING
 DRAWINGS- SECTION 606.2. PROVIDE ELEVATION VIEWS FOR
 EACH ACCESSIBLE SINK SHOWING COMPLIANCE WITH SECTIONS
 606.3, 306, 308, 309- HEIGHTS FROM FINISHED FLOORS,
 KNEE AND TOE CLEARANCES, REACH RANGE TO FAUCET
 CONTROLS, AND OPERABLE PARTS.
  
 10) P0.0.1: PROVIDE SHOWER SPRAY SPECIFICATIONS IN THE
 FIXTURE SCHEDULE- SECTION 608.3 FBC ACC AND 424.2 FBC
 P.
  
 11) P0.0.1: WATER DISTRIBUTION AND SANITARY DRAINAGE
 AND VENT PIPING SPECIFICATIONS NOT PROVIDED- SECTIONS
 605.3 605.4, 702.1 & 702.2 FBC P.
  
 12) P0.0.2: PROVIDE A PLUMBING DEVICE SCHEDULE
 INDICATING MAKES, MODEL NUMBERS AND LISTINGS FOR WATER
 HAMMER ARRESTORS, MIXING VALVES, BACKFLOW PREVENTERS,
 AND TRAP PRIMERS- SECTIONS 604.9, 607.2.1, 608.3 AND
 1002.4.1.1 FBC P.
  
 13) P0.0.2 & P2.1.1: PLEASE PROVIDE ENLARGED SP-1
 INSTALLATION AND PLUMBING PIPING DETAILS- SECTIONS
 712.2- 712.3.5 FBC P.
  
 14) P0.0.1, P2.1.1, P2.1.2, P2.1.3: INCLUDE THE FLOOR
 DRAINS (FD, FD-1, FD-3) IN THE FIXTURE SCHEDULE-
 SECTION 412.1 FBC P.
  
 15) P0.0.1, P2.1.1, P4.1.1: INCLUDE THE WASHING MACHINE
 IN THE FIXTURE SCHEDULE AND INDICATE THE MACHINE SHALL
 DISCHARGE THROUGH AN INTERCEPTOR THAT IS PROVIDED WITH
 A WIRE BASKET OR SIMILAR DEVICE, REMOVABLE FOR
 CLEANING, THAT PREVENTS PASSAGE INTO THE DRAINAGE
 SYSTEM OF SOLIDS 1/2 INCH OR LARGER IN SIZE, STRING,
 RAGS, BUTTONS OR OTHER MATERIALS DETRIMENTAL TO THE
 PUBLIC SEWAGE SYSTEM- SECTION 1003.6 FBC P.
  
 16) P2.1.1, P4.1.1, P4.1.2: SHOW TRAP PRIMER
 CONNECTIONS FOR EMERGENCY FLOOR DRAINS- SECTION
 1004.2.1 FBC P.
  
 17) P2.1.1, P4.1.1, C9: SHOW THE BUILDING
 DRAIN/SANITARY SEWER POINT OF CONNECTION JUNCTION AND
 PROVIDE A CLEANOUT AT THE JUNCTION- SECTION 708.1.3 FBC
 P.
  
 18) P2.1.1, P2.1.2, P4.1.3, C9: SHOW BUILDING STORM
 DRAIN CONNECTIONS TO MAIN STORM DRAIN PIPES ON SITE-
 SECTION 107.2.1 WPB, AND CLEANOUT LOCATIONS- SECTION
 1108.1 FBC P.
  
 19) P2.1.2 & P4.1.1: S-3 IN THE CONFERENCE ROOM IS
 MISLABELED AS S-4- SECTION 107.2.1 WPB.
  
 20) P2.1.2: INDICATE THE TERMINATION LOCATION FOR THE
 CONDENSATE PIPING SHOWN EXITING THE BUILDING BY
 CORRIDOR P102- SECTION 314.2.1 FBC P.
  
 21) P0.0.1, P2.1.2: I CANNOT LOCATE THE SS1 HOWEVER
 THERE IS AN S4 COUNTER SINK SHOWN IN THE SOILED ROOM.
 IS THIS SINK MISLABELED? REFER TO SECTIONS 422.6 &
 422.7 FBC P. AND VERIFY A CLINICAL SINK IS NOT REQUIRED
 PER ACHA OR ANOTHER AGENCY.
  
 22) P.2.2.1, P4.1.2, C9: SHOW THE LOCATIONS OF THE
 WATER METER, REQUIRED SHUTOFF VALVE ON DISCHARGE SIDE,
 AND THE MAIN WATER DISTRIBUTION SHUTOFF VALVE AT THE
 BUILDING ENTRANCE- SECTION 606.1 (1,2,3) FBC P.
  
 23) P.2.2.1, P4.1.2: SHOW THE WATER SUPPLY PIPING TO
 THE WASHING MACHINE, DISHWASHER, BEVERAGE DISPENSER,
 AND ICE MAKER- TABLE 604.5 FBC P, AND SECTIONS 107.2.1,
 107.3.5.1.3 WPB. SHOW THE REQUIRED WATER HAMMER
 ARRESTORS AND BACKFLOW PREVENTERS- SECTIONS 604.9 &
 608.3 FBC P.
  
 24) P.2.2.1, P.2.2.2, P2.2.3, P4.1.2: SHOW THE 3/4 IN.
 FIXTURE SUPPLY PIPES TO THE WATER CLOSETS AND URINALS-
 TABLE 604.5 FBC P.
  
 24) P2.2.2, P4.1.2: SHOW THE LOCATIONS OF THE WATER
 LINE FEEDS UP TO THE 2ND FLOOR AND THE REQUIRED SHUTOFF
 VALVES- SECTION 606.1(4) FBC P.
  
 25) P2.2.3, P4.1.2: SHOW THE SHUTOFF VALVE LOCATIONS
 FOR WATER DOWN-FEED PIPES- SECTION 606.(5) FBC P.
  
 26) P2.2.1, P2.2.2, P2.2.3, P4.1.2 FBC P: INDICATE HOW
 TEMPERED WATER WILL BE PROVIDED TO THE LAVATORIES-
 SECTION 416.5. SHOW MIXING VALVE LOCATIONS- SECTION
 607.1.2 FBC P.
  
 27) P4.1.2: PLEASE LABEL THE RECIRCULATION PUMPS AND
 THE WATER HEATERS- SECTIONS 607.1, 607.2.1, FBC P.
  
 28) P0.0.2, P2.2.1, P4.1.2: BASED ON THE LEGEND IT
 APPEARS THE HOT WATER SYSTEM RETURN PIPE WILL BE A 1/2
 IN. COLD WATER PIPE. IS THE PIPE SHOWN CORRECTLY? -
 SECTION 107.2.1 WPB AND SECTION C404.6.1 FBC EC.
  
 29) P2.2.1: PLEASE NOTE THE BACKFLOW PREVENTER PROVIDED
 FOR THE CHILLED WATER SUPPLY SHALL BE UNDER A SEPARATE
 PERMIT. PLEASE PROVIDE A NOTE ON THE PLAN TO CLARIFY-
 SECTION 107.2.1 WPB.
  
 30) REFER TO TABLE C403.2.10 FBC EC AND INDICATE THE
 TYPE AND THICKNESS OF THE HOT WATER PIPE INSULATION AND
 PROVIDE A PRODUCT SUBMITTAL.
  
 31) P5.1.1: PROVIDE A DRAIN PAN AND DRAIN PAN LINE FOR
 THE WATER HEATER SHOWN IN THE DETAIL- REFER TO SECTIONS
 504.7, 504.7.1 FBC P. SHOW THE TERMINATION LOCATION OF
 THE LINE- SECTION 504.7.2.
  
 32) ROOF DRAINAGE- SHEETS P2.2.4, P2.2.5, A1.30,
 A1.3.1, A1.3.2:
 A) VERIFY THE ROOF AND DRAINAGE SYSTEM HAS BEEN
 DESIGNED IN COMPLIANCE WITH SECTION 1101.7 FBC P FOR
 MAXIMUM DEPTH OF PONDING WATER AND DEFLECTED STRUCTURAL
 ELEMENTS.
 B) INDICATE THE RAINFALL RATE (INCHES PER HOUR) BASED
 ON SECTION 1106.1.
 C) PROVIDE ROOF DRAINAGE AREA CALCULATIONS INCLUDING
 FLAT ROOFS, PARAPETS, AND SLOPE ROOFS DRAINING ONTO
 FLAT ROOFS. CONVERT SQUARE FT. CALCULATIONS TO GPM AND
 PROVIDE SIZING CALCULATIONS FOR PRIMARY VERTICAL AND
 HORIZONTAL DRAINS- TABLE 1106.2, AND VERTICAL LEADERS-
 TABLE 1106.3. PLEASE INCLUDE THE SLOPES OF THE
 HORIZONTAL DRAINS BASED ON TABLE 1106.2.
 D) REFER TO SECTION 1108.3 AND PROVIDE OVERFLOW DRAIN
 CALCULATIONS BASED ON SECTION 1106.
 E) SHOW THE SIZES OF THE SLOPED ROOF HORIZONTAL GUTTERS
 AND DOWNSPOUTS AND PROVIDE SIZING CALCULATIONS FOR
 EACH- SECTION AND TABLE 1106.6
 F) PROVIDE GUTTER AND DOWNSPOUT ATTACHMENT DETAILS-
 SECTION 1101.6.
 G) SHOW HOW THE GUTTER DOWNSPOUTS WILL EITHER CONNECT
 TO THE STORM DRAIN PIPE SYSTEM OR BE DRAINED TO AN
 APPROVED PLACE OF DISPOSAL- SECTION 1101.2.
  
 33) PLEASE NOTE SEPARATE PERMIT APPLICATIONS AND PLANS
 ARE REQUIRED FOR THE POTABLE WATER SERVICE BACKFLOW
 PREVENTER, BACKFLOW PREVENTER FOR THE CHILLER, GREASE
 INTERCEPTOR, IRRIGATION SYSTEM, FIRE LINE, FIRE LINE
 BACKFLOW PREVENTER, AND FIRE SPRINKLER SYSTEM. COMPLETE
 SETS OF PLANS AND SPECIFICATIONS ARE REQUIRED FOR
 REVIEW AND PERMIT ISSUANCE- SECTION 107.2.1 WPB.
  
 A) BACKFLOW PREVENTERS: PLEASE NOTE THAT FL. LICENSED
 PLUMBING CONTRACTORS SHALL OBTAIN SEPARATE PERMITS FOR
 INSTALLATION OF THE BACKFLOW PREVENTERS IN ACCORDANCE
 WITH SECTION 105.1 WPB AND SEC. 90-33 WPB CODE OF
 ORDINANCES. THE DEVICES SHALL BE TESTED AND CERTIFIED
 BY THE WPB UTILITIES DEPARTMENT PRIOR TO FINAL
 INSPECTION BY THE BUILDING DEPARTMENT. PLEASE CONTACT
 THE WPB UTILITIES CENTRAL OPERATIONS DEPT.AT
 561-822-2210 FOR FURTHER INFORMATION.
  
 B) GREASE INTERCEPTOR: SUBMITTED PLANS SHALL INCLUDE
 GREASE WATER CALCULATIONS IN ACCORDANCE WITH SECTION
 1003.3.4 FOR HYDROMECHANICAL INTERCEPTORS OR 1003.3.6
 FOR GRAVITY TYPE INTERCEPTORS. MANUFACTURER'S
 SPECIFICATIONS AND INSTALLATION MANUALS SHALL ALSO BE
 SUBMITTED FOR REVIEW.
  
 34) REQUIRED SUBMITTALS: MANUFACTURER'S SPECIFCATIONS
 AND INSTALL MANUALS FOR THE WATER HEATERS, WASHING
 MACHINE, MIXING VALVES, RECIRCULATION PUMPS, SUMP PUMP,
 PIPE INSULATION, KITCHEN EQUIPMENT BACKFLOW PREVENTERS-
 SECTION 107.1 WPB. PLEASE ALL SUBMITTALS MAY BE
 DEFERRED IN ACCORDANCE WITH SECTION 107.3.4.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  
  
  
  