Date |
Text |
2020-12-09 11:24:19 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| |
| 1) SHEET LS 1.1 - THERE IS NO INDICATION OF COMPLIANCE |
| OR REVIEW WITH THE REQUIREMENTS OF THE FLORIDA FIRE |
| PREVENTION CODE. |
| |
| THE PROPOSED SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| 6TH EDITION OF FLORIDA FIRE PREVENTION CODE WHICH |
| INCLUDES THE 2015 EDITION OF NFPA 1 AND NFPA 101. |
| |
| PLEASE PROVIDE AN APPLICABLE NOTE OF ACKNOWLEDGEMENT, |
| REVIEW, AND COMPLIANCE. |
| |
| THE BELOW LIST ARE THE MOST COMMON REFERENCED CODES: |
| |
| FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS |
| OF NFPA 13, 2013 EDITION. |
| UNDERGROUND WORK SAHLL COMPLY WITH NFPA 24, 2013 |
| EDITION. |
| FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF |
| NFPA 72, 2013 EDITION. |
| CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF |
| NFPA 241, 2013 EDITION. |
| FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS |
| OF NFPA 10, 2013 EDITION. |
| ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2014 EDITION. |
| EMERGENCY AND STANDBY POWER SYSTEMS SHALL COMPLY WITH |
| NFPA 110, 2013 EDITION. |
| COMMERCIAL COOKING SHALL COMPLY WITH NFPA 96, 2014 |
| EDITION. |
| AIR CONDITION WORK SHALL COMPLY WITH NFPA 90 A & B, |
| 2015 EDITION |
| |
| |
| |
| 2) SHEET FP 1.1.1 - THERE IS UNDERGROUND FIRE LINE |
| INDICATED. |
| |
| ALL UNDERGROUND FIRE LINE WORK SHALL BE SUBMITTED UNDER |
| SEPARATE PERMIT AND SHOP DRAWINGS, INCLUDING |
| EQUIPMENT/PRODUCT SPEC SHEETS. |
| |
| PLEASE PROVIDE A NOTE OF ACKNOWLEDGEMENT. |
| |
| |
| |
| 2A) SHEET FP 1.1.1 - THE IS AN INDICATION OF A PROPOSED |
| FDC LOCATION. |
| |
| DUE TO PROPOSED FUTURE BUILDING AND THE LOCATION OF THE |
| PORTE COCHE, IT IS RECOMMENDED THAT THE FDC BE MOVED TO |
| THE SAME SIDE OF THE PORTE COCHE(SOUTH) AND FIRE |
| HYDRANT(EAST SIDE OF DRIVE PATH). |
| |
| PLEASE REVIEW AND CORRECT OR PROVIDE A COMMENT TO |
| CONTINUE TO COORDINATE WITH THE FIRE MARSHAL'S OFFICE |
| PRIOR TO UNDERGROUND PERMIT SUBMITTAL. |
| |
| |
| 3) SHEET E 2.3..1 & E 2.3.2 - THERE ARE INDICATIONS OF |
| FIRE ALARM EQUIPMENT/DEVICES. |
| |
| ALL FIRE ALARM WORK SHALL BE SUBMITTED UNDER SEPARATE |
| PERMIT AND SHOP DRAWINGS, INCLUDING EQUIPMENT/PRODUCT |
| SPEC SHEETS. |
| |
| PLEASE PROVIDE A NOTE OF ACKNOWLEDGEMENT. |
| |
| |
| 4) ELECTRICAL SHEETS - THERE ARE NO INDICATIONS OF A |
| RADIO FREQUENCY TWO- WAY EMERGENCY COMMUNICATION |
| COMPLIANCE. |
| |
| PER NFPA 1 - CH 11 BUILDING SERVICES |
| |
| 11.10* TWO-WAY RADIO COMMUNICATION ENHANCEMENT SYSTEMS. |
| 11.10.1 IN ALL NEW AND EXISTING BUILDINGS, MINIMUM |
| RADIO SIGNAL |
| STRENGTH FOR FIRE DEPARTMENT COMMUNICATIONS SHALL BE |
| MAINTAINED AT A |
| LEVEL DETERMINED BY THE AHJ. |
| 11.10.2 WHERE REQUIRED BY THE AHJ, TWO-WAY RADIO |
| COMMUNICATION |
| ENHANCEMENT SYSTEMS SHALL COMPLY WITH NFPA 72. |
| 11.10.3 WHERE A TWO-WAY RADIO COMMUNICATION ENHANCEMENT |
| SYSTEM IS |
| REQUIRED AND SUCH SYSTEM, COMPONENTS, OR EQUIPMENT HAS |
| A NEGATIVE |
| IMPACT ON THE NORMAL OPERATIONS OF THE FACILITY AT |
| WHICH IT IS INSTALLED, |
| THE AHJ SHALL HAVE THE AUTHORITY TO ACCEPT AN |
| AUTOMATICALLY ACTIVATED |
| RESPONDER SYSTEM. |
| |
| ANY ENHANCEMENT SYSTEM (BDA) SHALL BE INSTALLED UNDER |
| SEPARATE PEMRIT AND SHOP DRAWINGS. |
| |
| PLEASE REVIEW AND PROVIDE A NOTE OF ACKNOWLEDGEMENT |
| |
| |
| |
| 5) SHEET A 1.1.0 - THERE APPEARS TO BE GENERATOR WITHIN |
| THE OPEN MECHANICAL YARD. |
| |
| PLEASE REVIEW AND CONFIRM, SIZE AND TYPE. |
| |
| THE GENERATOR SHALL BE INSTALLED UNDER SEPARATE PERMIT |
| AND SHOP DRAWINGS IN COMPLIANCE WITH ALL APPLICABLE |
| CODES INCLUDING NFPA 110 AND NFPA 37. |
| |
| PLEASE REVIEW AND PROVIDE A NOTE OF ACKNOWLEDGEMENT |
| |
| |
| |
| 6) SHEETS E 2.3.1, 2.3.2 & 2.3.3 - THERE APPEARS TO BE |
| PROPOSED ACCESS CONTROL. |
| |
| ACCESS CONTROL SHALL BE INSTALLED UNDER SEPARATE PERMIT |
| AND SHOP DRAWINGS IN COMPLIANCE WITH ALL APPLICABLE |
| CODES INCLUDING NFPA 101, CH 7 MEANS OF EGRESS. |
| |
| PLEASE REVIEW AND PROVIDE A NOTE OF ACKNOWLEDGEMENT |
| |
| |
| |
| 7) SHEET A 1.2.7 - THE PORTE COCHERE INDICATES A |
| DIMENSIONAL HEIGHT OF 12.0' |
| |
| PER NFPA 1 CH 18 FIRE DEPARTMENT ACCESS AND WATER |
| SUPPLY |
| |
| 18.1 GENERAL. FIRE DEPARTMENT ACCESS AND WATER SUPPLIES |
| SHALL |
| COMPLY WITH THIS CHAPTER. |
| 18.1.1 APPLICATION. |
| 18.1.1.1 THIS CHAPTER SHALL APPLY TO PUBLIC AND |
| PRIVATELY OWNED |
| FIRE APPARATUS ACCESS ROADS. |
| 18.1.1.2 THIS CHAPTER SHALL APPLY TO PUBLIC AND |
| PRIVATELY OWNED |
| FIRE HYDRANT SYSTEMS. |
| |
| 18.2.3.4 SPECIFICATIONS. |
| 18.2.3.4.1 DIMENSIONS. |
| |
| 18.2.3.4.1.2 FIRE DEPARTMENT ACCESS ROADS SHALL HAVE AN |
| UNOBSTRUCTED |
| VERTICAL CLEARANCE OF NOT LESS THAN 13 FT 6 IN. (4.1 |
| M). |
| |
| |
| PLEASE REVIEW AND CORRECT. |
| |
| |
| |
| 8) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| ABOVE. |
| |
| |
| |
| 9) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| RE-SUBMITTAL OF THE ABOVE. |
| |
| |
| |
| |
| PETER LEDUC |
| FIRE MARSHAL |
| 561-804-4709 |
| [email protected] |
| |