Plan Review Notes
Plan Review Notes For Permit 20120145
Permit Number 20120145
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2020-12-09 11:24:19THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET LS 1.1 - THERE IS NO INDICATION OF COMPLIANCE
 OR REVIEW WITH THE REQUIREMENTS OF THE FLORIDA FIRE
 PREVENTION CODE.
  
 THE PROPOSED SHALL COMPLY WITH THE REQUIREMENTS OF THE
 6TH EDITION OF FLORIDA FIRE PREVENTION CODE WHICH
 INCLUDES THE 2015 EDITION OF NFPA 1 AND NFPA 101.
  
 PLEASE PROVIDE AN APPLICABLE NOTE OF ACKNOWLEDGEMENT,
 REVIEW, AND COMPLIANCE.
  
 THE BELOW LIST ARE THE MOST COMMON REFERENCED CODES:
  
 FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 13, 2013 EDITION.
 UNDERGROUND WORK SAHLL COMPLY WITH NFPA 24, 2013
 EDITION.
 FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 72, 2013 EDITION.
 CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 241, 2013 EDITION.
 FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 10, 2013 EDITION.
 ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2014 EDITION.
 EMERGENCY AND STANDBY POWER SYSTEMS SHALL COMPLY WITH
 NFPA 110, 2013 EDITION.
 COMMERCIAL COOKING SHALL COMPLY WITH NFPA 96, 2014
 EDITION.
 AIR CONDITION WORK SHALL COMPLY WITH NFPA 90 A & B,
 2015 EDITION
  
  
  
 2) SHEET FP 1.1.1 - THERE IS UNDERGROUND FIRE LINE
 INDICATED.
  
 ALL UNDERGROUND FIRE LINE WORK SHALL BE SUBMITTED UNDER
 SEPARATE PERMIT AND SHOP DRAWINGS, INCLUDING
 EQUIPMENT/PRODUCT SPEC SHEETS.
  
 PLEASE PROVIDE A NOTE OF ACKNOWLEDGEMENT.
  
  
  
 2A) SHEET FP 1.1.1 - THE IS AN INDICATION OF A PROPOSED
 FDC LOCATION.
  
 DUE TO PROPOSED FUTURE BUILDING AND THE LOCATION OF THE
 PORTE COCHE, IT IS RECOMMENDED THAT THE FDC BE MOVED TO
 THE SAME SIDE OF THE PORTE COCHE(SOUTH) AND FIRE
 HYDRANT(EAST SIDE OF DRIVE PATH).
  
 PLEASE REVIEW AND CORRECT OR PROVIDE A COMMENT TO
 CONTINUE TO COORDINATE WITH THE FIRE MARSHAL'S OFFICE
 PRIOR TO UNDERGROUND PERMIT SUBMITTAL.
  
  
 3) SHEET E 2.3..1 & E 2.3.2 - THERE ARE INDICATIONS OF
 FIRE ALARM EQUIPMENT/DEVICES.
  
 ALL FIRE ALARM WORK SHALL BE SUBMITTED UNDER SEPARATE
 PERMIT AND SHOP DRAWINGS, INCLUDING EQUIPMENT/PRODUCT
 SPEC SHEETS.
  
 PLEASE PROVIDE A NOTE OF ACKNOWLEDGEMENT.
  
  
 4) ELECTRICAL SHEETS - THERE ARE NO INDICATIONS OF A
 RADIO FREQUENCY TWO- WAY EMERGENCY COMMUNICATION
 COMPLIANCE.
  
 PER NFPA 1 - CH 11 BUILDING SERVICES
  
 11.10* TWO-WAY RADIO COMMUNICATION ENHANCEMENT SYSTEMS.
 11.10.1 IN ALL NEW AND EXISTING BUILDINGS, MINIMUM
 RADIO SIGNAL
 STRENGTH FOR FIRE DEPARTMENT COMMUNICATIONS SHALL BE
 MAINTAINED AT A
 LEVEL DETERMINED BY THE AHJ.
 11.10.2 WHERE REQUIRED BY THE AHJ, TWO-WAY RADIO
 COMMUNICATION
 ENHANCEMENT SYSTEMS SHALL COMPLY WITH NFPA 72.
 11.10.3 WHERE A TWO-WAY RADIO COMMUNICATION ENHANCEMENT
 SYSTEM IS
 REQUIRED AND SUCH SYSTEM, COMPONENTS, OR EQUIPMENT HAS
 A NEGATIVE
 IMPACT ON THE NORMAL OPERATIONS OF THE FACILITY AT
 WHICH IT IS INSTALLED,
 THE AHJ SHALL HAVE THE AUTHORITY TO ACCEPT AN
 AUTOMATICALLY ACTIVATED
 RESPONDER SYSTEM.
  
 ANY ENHANCEMENT SYSTEM (BDA) SHALL BE INSTALLED UNDER
 SEPARATE PEMRIT AND SHOP DRAWINGS.
  
 PLEASE REVIEW AND PROVIDE A NOTE OF ACKNOWLEDGEMENT
  
  
  
 5) SHEET A 1.1.0 - THERE APPEARS TO BE GENERATOR WITHIN
 THE OPEN MECHANICAL YARD.
  
 PLEASE REVIEW AND CONFIRM, SIZE AND TYPE.
  
 THE GENERATOR SHALL BE INSTALLED UNDER SEPARATE PERMIT
 AND SHOP DRAWINGS IN COMPLIANCE WITH ALL APPLICABLE
 CODES INCLUDING NFPA 110 AND NFPA 37.
  
 PLEASE REVIEW AND PROVIDE A NOTE OF ACKNOWLEDGEMENT
  
  
  
 6) SHEETS E 2.3.1, 2.3.2 & 2.3.3 - THERE APPEARS TO BE
 PROPOSED ACCESS CONTROL.
  
 ACCESS CONTROL SHALL BE INSTALLED UNDER SEPARATE PERMIT
 AND SHOP DRAWINGS IN COMPLIANCE WITH ALL APPLICABLE
 CODES INCLUDING NFPA 101, CH 7 MEANS OF EGRESS.
  
 PLEASE REVIEW AND PROVIDE A NOTE OF ACKNOWLEDGEMENT
  
  
  
 7) SHEET A 1.2.7 - THE PORTE COCHERE INDICATES A
 DIMENSIONAL HEIGHT OF 12.0'
  
 PER NFPA 1 CH 18 FIRE DEPARTMENT ACCESS AND WATER
 SUPPLY
  
 18.1 GENERAL. FIRE DEPARTMENT ACCESS AND WATER SUPPLIES
 SHALL
 COMPLY WITH THIS CHAPTER.
 18.1.1 APPLICATION.
 18.1.1.1 THIS CHAPTER SHALL APPLY TO PUBLIC AND
 PRIVATELY OWNED
 FIRE APPARATUS ACCESS ROADS.
 18.1.1.2 THIS CHAPTER SHALL APPLY TO PUBLIC AND
 PRIVATELY OWNED
 FIRE HYDRANT SYSTEMS.
  
 18.2.3.4 SPECIFICATIONS.
 18.2.3.4.1 DIMENSIONS.
  
 18.2.3.4.1.2 FIRE DEPARTMENT ACCESS ROADS SHALL HAVE AN
 UNOBSTRUCTED
 VERTICAL CLEARANCE OF NOT LESS THAN 13 FT 6 IN. (4.1
 M).
  
  
 PLEASE REVIEW AND CORRECT.
  
  
  
 8) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 9) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
  