2021-01-07 08:52:57ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PAGE E.2.2.1
  
 ROOMS P120, P121, P122 WILL REQUIRE GFCI PROTECTION OF
 ALL 125V 15A, AND 20A RECEPTACLE OUTLETS.
 ALL 125-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE
 RECEPTACLES INSTAL LED IN THE LOCATIONS SPECIFIED IN
 210.8(B)(1) THROUGH (8) SHALL HAVE GROUND-FAULT CIRCUIT
 INTERRUPTER PROTECTION FOR PERSONNEL.
  
 PAGE E.2.2.2
  
 ROOMS P108B, P108C, P127, P135, P136, P137 ARE THESE
 ROOMS TREATMENT ROOMS THAT SHOULD BE COVERED BY ARTICLE
 517?
 517.1 SCOPE THE PROVISIONS OF THIS ARTICLE SHALL APPLY
 TO ELECTRICAL CONSTRUCTI ON AND INSTALLATION CRITERIA
 IN HEALTH CARE FACILITIES THAT PROVIDE SERVICES TO
 HUMAN BEINGS. THE REQUIREMENTS IN PARTS II AND III NOT
 ONLY APPLY TO SINGLEFUNCTION BUILDINGS BUT ARE ALSO
 INTENDED TO BE INDIVIDUALLY APPLIED TO THEIR RESPECTIVE
 FORMS OF OCCUPANCY WITHIN A MULTIFUNCTION BUILDING
 (E.G., A DOCTOR?S EXAMINING ROOM LOCATED WITHIN A
 LIMITED CARE FACILITY WOULD BE REQUIRED TO MEET THE
 PROVISIONS OF 517.10).
  
  