Plan Review Notes For Permit 20120145 |
Permit Number |
20120145 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2021-01-07 08:52:57 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | FLORIDA BUILDING CODE 2017 6TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | NFPA 70 2014 EDITION | | | | JAKE LEAHY BN, BU, PX | | ELECTRICAL PLANS EXAMINER II | | 561-805-6713 | | [email protected] | | | | PAGE E.2.2.1 | | | | ROOMS P120, P121, P122 WILL REQUIRE GFCI PROTECTION OF | | ALL 125V 15A, AND 20A RECEPTACLE OUTLETS. | | ALL 125-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE | | RECEPTACLES INSTAL LED IN THE LOCATIONS SPECIFIED IN | | 210.8(B)(1) THROUGH (8) SHALL HAVE GROUND-FAULT CIRCUIT | | INTERRUPTER PROTECTION FOR PERSONNEL. | | | | PAGE E.2.2.2 | | | | ROOMS P108B, P108C, P127, P135, P136, P137 ARE THESE | | ROOMS TREATMENT ROOMS THAT SHOULD BE COVERED BY ARTICLE | | 517? | | 517.1 SCOPE THE PROVISIONS OF THIS ARTICLE SHALL APPLY | | TO ELECTRICAL CONSTRUCTI ON AND INSTALLATION CRITERIA | | IN HEALTH CARE FACILITIES THAT PROVIDE SERVICES TO | | HUMAN BEINGS. THE REQUIREMENTS IN PARTS II AND III NOT | | ONLY APPLY TO SINGLEFUNCTION BUILDINGS BUT ARE ALSO | | INTENDED TO BE INDIVIDUALLY APPLIED TO THEIR RESPECTIVE | | FORMS OF OCCUPANCY WITHIN A MULTIFUNCTION BUILDING | | (E.G., A DOCTOR?S EXAMINING ROOM LOCATED WITHIN A | | LIMITED CARE FACILITY WOULD BE REQUIRED TO MEET THE | | PROVISIONS OF 517.10). | | | | |
|