2021-02-03 06:49:23 | 2ND REVIEW FBC-2020 MECHANICAL |
| PERMIT-20120108 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2020 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2020 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2020 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2020 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2020 |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| EDITION 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2020 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) PLEASE PROVIDE CALCULATION FOR THE OUTDOOR AIR BASED |
| ON SECTION 403.3.1.1 AND TABLE 403.3.1.1. YOU MUST THE |
| TABLE AND NOT USE THE ARCHITECTURAL COUNT. SEE EXAMPLE |
| BELOW: |
| CONFERENCE ROOM: 425/1000 = .425,.425 X 50 = 21.25 X 5 |
| = 106.25; 425 X .06 = 25.5; 106.25 + 25.5 = 132 CFM. |
| REMAINING OFFICES: 5237/1000 = 5.237 X 5 = 26.185 X 5 = |
| 130.925; 5237 X .06 = 314.22; 130.925 + 314.22 = 446 |
| CFM |
| WAR ROOM: 290/1000 = .29; .29 X 50 = 14.5 X 5 = 72.5; |
| 290 X .06 = 17.4; 72.5 + 17.4 = 90 CFM. FBC M 403.3.1.1 |
| |
| 2) I DO NOT SEE A REVISED M2.1 SHEET. PLEASE MAKE SURE |
| THE REVISED DRAWING HAS BEEN SUBMITTED. FBC 107.2.1 |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| UPDATED. |
| |