2020-12-19 07:40:36 | 1ST REVIEW FBC-2017 MECHANICAL |
| PERMIT-20120108 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| EDITION 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEET M0.1: THERE ARE TWO CONFERENCE ROOMS IN THIS |
| TENANT SPACE, PLEASE PROVIDE OUTDOOR AIR CALCULATIONS |
| FOR THESE TWO CONFERENCE ROOMS BASED ON TABLE |
| 403.3.1.1. FBC M TABLE 403.3.1.1 |
| |
| 2) SHEET M2.1: THE LOCKER ROOM EXHAUST DUCT IS |
| PENETRATING THE WALL SEPARATING THE MEN?S BATHROOM FROM |
| THE WAR ROOM, IT APPEARS THIS WALL SHOULD BE RATED. |
| PLEASE SHOW ITS RATING AND HOW YOU WILL PROTECT THIS |
| WALL AT THE EXHAUST DUCT PENETRATION. FBC M 607 |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| UPDATED. |
| |