Plan Review Notes For Permit 20120108 |
Permit Number |
20120108 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2021-01-06 15:28:10 | CODES IN EFFECT | | CODES IN EFFECT: | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | 6TH ED, CHAPTER 1. | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | 6TH EDITION | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | 6TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | FAC = FLORIDA ADMINISTRATIVE CODE | | | | REVIEW STATUS: FAILED. | | | | 1) VAV-1, 5, 6, AND 7 SPECS (M6.1) SHOWS 5KW HEATERS AT | | 277 VOLTS. PANEL SCHEDULE H4B SPECIFIES CIRCUITS TO BE | | 20 AMPS BREAKER WITH #12 CONDUCTOR. FIXED ELECTRIC | | HEATING IS CONTINUOUS AND THE MINIMUM AMPACITY SHOULD | | BE 125% OF TOTAL LOAD. IT APPEARS THAT THE #12 WIRE | | WITH 20 AMPS BREAKER ARE UNDERSIZED. PLEASE PROVIDE | | SPECS FROM MANUFACTURER FOR OVERCURRENT PROTECTION AND | | WIRE SIZE FOR VAV UNITS AND CONFIRM WHAT THE RIGHT | | SIZES ARE. NEC 424.3, NEC 240.4 | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. | | | | SINCERELY, | | | | ENRIQUE QUINONEZ | | ELECTRICAL PLANS EXAMINER | | 561-805-6746 | | [email protected] | | |
|