2021-01-06 15:28:10CODES IN EFFECT
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 REVIEW STATUS: FAILED.
  
 1) VAV-1, 5, 6, AND 7 SPECS (M6.1) SHOWS 5KW HEATERS AT
 277 VOLTS. PANEL SCHEDULE H4B SPECIFIES CIRCUITS TO BE
 20 AMPS BREAKER WITH #12 CONDUCTOR. FIXED ELECTRIC
 HEATING IS CONTINUOUS AND THE MINIMUM AMPACITY SHOULD
 BE 125% OF TOTAL LOAD. IT APPEARS THAT THE #12 WIRE
 WITH 20 AMPS BREAKER ARE UNDERSIZED. PLEASE PROVIDE
 SPECS FROM MANUFACTURER FOR OVERCURRENT PROTECTION AND
 WIRE SIZE FOR VAV UNITS AND CONFIRM WHAT THE RIGHT
 SIZES ARE. NEC 424.3, NEC 240.4
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  