Plan Review Notes
Plan Review Notes For Permit 20120096
Permit Number 20120096
Review Stop G
Sequence Number 2
Notes
Date Text
2021-03-15 09:08:322ND REVIEW FBC-2017 RES. FUEL GAS
 PERMIT- 20120096
 3/15/2021
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE
 1ST REVIEW LISTED BELOW HAVE NOT BEEN COMPLETELY
 ADDRESSED. NOTES IN CAP LETTERS HAVE BEEN ADDED FOR
 FURTHER CLARIFICATION. AFTER REVIEWING THE COMMENTS
 PLEASE CONTACT ME AT 561-805-6719.
  
 1) FAILED. PLEASE CLARIFY THE EXACT LOCATIONS OF THE
 NEW METER AND NEW GAS LINE. THE DRAWING APPEARS TO
 INDICATE THE METER IS FREESTANDING ON THE PROPERTY OR
 POSSIBLY INSTALLED ON A SITE WALL. THERE ARE NOTES
 INDICATING THE NEW GAS PIPING TO BE INSTALLED ON
 UNISTRUTS ALONG THE PROPERTY LINE WHICH IS ASSUMED TO
 BE ON THE BLOCK SITE WALL INSTALLED UNDER PERMIT-
 07100359. PLEASE PROVIDE A COPY OF THE SURVEY MARKED UP
 TO SHOW THE INSTALLATION LOCATIONS. PLEASE NOTE THE
 SITE WALL IS INSTALLED IN A UTILITY EASEMENT, THEREFORE
 IF THE METER AND PIPING ARE TO BE INSTALLED ON THE WALL
 AN EASEMENT CONSENT FORM SHALL BE SUBMITTED WITH THE
 SURVEY- SECTION 107.2.1 WPB. THE EASEMENT CONSENT FORM
 CAN BE FOUND ON THE CITY OF WEST PALM BEACH WEBSITE. IF
 YOU NEED ASSISTANCE WITH OBTAINING THE FORM PLEASE
 EMAIL [email protected]. THE NEW GAS PIPING IS BEING INSTALLED
 IN A FLOOD ZONE. INDICATE WHERE THE UNISTRUTS ARE
 MOUNTED- SLAB, WALL? PLEASE NOTE THAT THE PIPING SHALL
 BE INSTALLED A MINIMUM OF 3-1/2 INCHES ABOVE GROUND,
 AND SHALL BE RESISTANT TO WATER INTRUSION, CORROSION,
 AND TO HYDROSTATIC AND HYDRODYNAMIC LOADS AND STRESSES-
 SECTION 322.1.6 FBC RES.
  
 2) FAILED PROVIDE A GAS RISER DRAWING- SECTION
 107.3.5.3 WPB. THE RISER SHALL PROVIDE THE FOLLOWING
 INFORMATION: RISER IS INCOMPLETE- SEE BELOW.
  
 B) FAILED. TOTAL DEVELOPED LENGTH OF THE PIPING FROM
 THE METER TO THE MOST REMOTE GAS OUTLET- SECTION
 G2413.4.1.NOT PROVIDED.
  
 D) FAILED. BRANCH AND CUT PIPING LENGTHS- SECTION
 G2413.4.2. PLEASE INCLUDE THE PIPING RUN TO THE
 EXISTING GAS RANGE THAT IS BEING REPLACED. NOT
 PROVIDED.
  
 E) FAILED. INDIVIDUAL GAS LOADS AT OUTLETS AND TOTAL
 LOAD OF THE SYSTEM- SECTIONS G2412.3, G2412.4, &
 G2413.2 FBC RES. NOT PROVIDED.
  
 F) FAILED. LOCATIONS OF REGULATORS AND OUTLET
 PRESSURES- SECTIONS G2421.1 & G2421.2. NOT PROVIDED.
  
 3) FAILED. INDICATE A GAS-TIGHT CAP WILL BE PROVIDED
 FOR THE PIPING SUPPLYING THE FUTURE POOL HEATER-
 SECTION G2415.15 FBC RES. THE RISER DOES NOT SHOW A TEE
 TO A FUTURE POOL HEATER AND THE GAS-TIGHT CAP NOT
 PROVIDED.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  