2020-12-14 14:48:47 | 1ST REVIEW FBC-2017 RES. FUEL GAS |
| PERMIT- 20120096 |
| 12/14/2020 |
| |
| CODES IN EFFECT: |
| |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| EDITION 2017 |
| FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) PLEASE CLARIFY THE EXACT LOCATIONS OF THE NEW METER |
| AND NEW GAS LINE. THE DRAWING APPEARS TO INDICATE THE |
| METER IS FREESTANDING ON THE PROPERTY OR POSSIBLY |
| INSTALLED ON A SITE WALL. THERE ARE NOTES INDICATING |
| THE NEW GAS PIPING TO BE INSTALLED ON UNISTRUTS ALONG |
| THE PROPERTY LINE WHICH IS ASSUMED TO BE ON THE BLOCK |
| SITE WALL INSTALLED UNDER PERMIT- 07100359. PLEASE |
| PROVIDE A COPY OF THE SURVEY MARKED UP TO SHOW THE |
| INSTALLATION LOCATIONS. PLEASE NOTE THE SITE WALL IS |
| INSTALLED IN A UTILITY EASEMENT, THEREFORE IF THE METER |
| AND PIPING ARE TO BE INSTALLED ON THE WALL AN EASEMENT |
| CONSENT FORM SHALL BE SUBMITTED WITH THE SURVEY- |
| SECTION 107.2.1 WPB. THE EASEMENT CONSENT FORM CAN BE |
| FOUND ON THE CITY OF WEST PALM BEACH WEBSITE. IF YOU |
| NEED ASSISTANCE WITH OBTAINING THE FORM PLEASE EMAIL |
| [email protected]. |
| |
| 2) PROVIDE A GAS RISER DRAWING- SECTION 107.3.5.3 WPB. |
| THE RISER SHALL PROVIDE THE FOLLOWING INFORMATION: |
| |
| A) DELIVERY PRESSURE AT THE METER- SECTIONS G2413.1 FBC |
| RES. |
| |
| B) TOTAL DEVELOPED LENGTH OF THE PIPING FROM THE METER |
| TO THE MOST REMOTE GAS OUTLET- SECTION G2413.4.1. |
| |
| D) BRANCH AND CUT PIPING LENGTHS- SECTION G2413.4.2. |
| PLEASE INCLUDE THE PIPING RUN TO THE EXISTING GAS RANGE |
| THAT IS BEING REPLACED. |
| |
| E) INDIVIDUAL GAS LOADS AT OUTLETS AND TOTAL LOAD OF |
| THE SYSTEM- SECTIONS G2412.3, G2412.4, & G2413.2 FBC |
| RES. |
| |
| F) LOCATIONS OF REGULATORS AND OUTLET PRESSURES- |
| SECTIONS G2421.1 & G2421.2. |
| |
| G) PIPE SIZING TABLES- SECTION G2413.3. |
| |
| 3) INDICATE A GAS-TIGHT CAP WILL BE PROVIDED FOR THE |
| PIPING SUPPLYING THE FUTURE POOL HEATER- SECTION |
| G2415.15 FBC RES. |
| |
| 4) THE CONTRACTOR OR QUALIFIER WHO PREPARED THE DRAWING |
| SHALL PROVIDE HIS/HER PRINTED NAME AND SIGNATURE ON IT- |
| SECTION 107.2.1 WPB, AND FLORIDA STATUTES 471.003(2)(H) |
| & 471.025. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |