Plan Review Notes
Plan Review Notes For Permit 20120096
Permit Number 20120096
Review Stop G
Sequence Number 1
Notes
Date Text
2020-12-14 14:48:471ST REVIEW FBC-2017 RES. FUEL GAS
 PERMIT- 20120096
 12/14/2020
  
 CODES IN EFFECT:
  
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE CLARIFY THE EXACT LOCATIONS OF THE NEW METER
 AND NEW GAS LINE. THE DRAWING APPEARS TO INDICATE THE
 METER IS FREESTANDING ON THE PROPERTY OR POSSIBLY
 INSTALLED ON A SITE WALL. THERE ARE NOTES INDICATING
 THE NEW GAS PIPING TO BE INSTALLED ON UNISTRUTS ALONG
 THE PROPERTY LINE WHICH IS ASSUMED TO BE ON THE BLOCK
 SITE WALL INSTALLED UNDER PERMIT- 07100359. PLEASE
 PROVIDE A COPY OF THE SURVEY MARKED UP TO SHOW THE
 INSTALLATION LOCATIONS. PLEASE NOTE THE SITE WALL IS
 INSTALLED IN A UTILITY EASEMENT, THEREFORE IF THE METER
 AND PIPING ARE TO BE INSTALLED ON THE WALL AN EASEMENT
 CONSENT FORM SHALL BE SUBMITTED WITH THE SURVEY-
 SECTION 107.2.1 WPB. THE EASEMENT CONSENT FORM CAN BE
 FOUND ON THE CITY OF WEST PALM BEACH WEBSITE. IF YOU
 NEED ASSISTANCE WITH OBTAINING THE FORM PLEASE EMAIL
 [email protected].
  
 2) PROVIDE A GAS RISER DRAWING- SECTION 107.3.5.3 WPB.
 THE RISER SHALL PROVIDE THE FOLLOWING INFORMATION:
  
 A) DELIVERY PRESSURE AT THE METER- SECTIONS G2413.1 FBC
 RES.
  
 B) TOTAL DEVELOPED LENGTH OF THE PIPING FROM THE METER
 TO THE MOST REMOTE GAS OUTLET- SECTION G2413.4.1.
  
 D) BRANCH AND CUT PIPING LENGTHS- SECTION G2413.4.2.
 PLEASE INCLUDE THE PIPING RUN TO THE EXISTING GAS RANGE
 THAT IS BEING REPLACED.
  
 E) INDIVIDUAL GAS LOADS AT OUTLETS AND TOTAL LOAD OF
 THE SYSTEM- SECTIONS G2412.3, G2412.4, & G2413.2 FBC
 RES.
  
 F) LOCATIONS OF REGULATORS AND OUTLET PRESSURES-
 SECTIONS G2421.1 & G2421.2.
  
 G) PIPE SIZING TABLES- SECTION G2413.3.
  
 3) INDICATE A GAS-TIGHT CAP WILL BE PROVIDED FOR THE
 PIPING SUPPLYING THE FUTURE POOL HEATER- SECTION
 G2415.15 FBC RES.
  
 4) THE CONTRACTOR OR QUALIFIER WHO PREPARED THE DRAWING
 SHALL PROVIDE HIS/HER PRINTED NAME AND SIGNATURE ON IT-
 SECTION 107.2.1 WPB, AND FLORIDA STATUTES 471.003(2)(H)
 & 471.025.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  