2020-12-14 13:51:38 | 1) SUBMIT A COPY OF THE INSTALLATION MANUAL FOR THE | | PUMP FOR REVIEW.WPB AMEND. TO FBC SEC. 107.2.1. | | 2) SHOW THE VENT FOR THE PUMP AND THE CONNECTION POINT | | TO THE EXISTING VENT SYSTEM. THE SANITARY RISER SHOWS | | AN AIR ADMITTANCE VALVE ON THE BREAK SINK. THIS AIR | | ADMITTANCE VALVE CANNOT BE USED TO VENT THE PUMP UNIT | | PER THE MANUFACTURER'S INSTALLATION MANUAL. AN | | INDIVIDUAL VENT MUST NE INSTALLED AND CONNECTED TO A | | CODE COMPLIANT PLUMBING VENT SYSTEM PER FBC-PLUMBING | | SEC. 712.1,906.5. | | 3) THE DISCHARGE LINE FROM THE PUMP SHALL CONNECT TO | | THE SANITARY SYSTEM IN ACCORDANCE WITH FBC-PLUMBING | | SEC.712.3.5. INDICATE ON THE PLAN. | | 4) THE PLANS DO NOT BEAR AN ELECTRONIC SIGNATURE OR | | SEAL PER FL. ADMIN. CODE RULE 61G15-23.004, | | 61G15-23.005 NOR DO THEY BEAR A SEAL OR SIGNATURE PER | | FL. ADMIN. CODE RULE 61G15-23.001. | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | | | |
|