Plan Review Notes
Plan Review Notes For Permit 20120027
Permit Number 20120027
Review Stop G
Sequence Number 1
Notes
Date Text
2020-12-11 12:17:201ST REVIEW FBC-2017 FUEL GAS
 PERMIT- 20120027
 12/11/2020
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P-2: CORRECT THE GAS RISER TO SHOW A MINIMUM
 37 EHD PIPE FROM THE METER TO THE TEE, A MINIMUM 31 EHD
 PIPE FROM THE TEE TO THE WATER HEATER, AND A MINIMUM 23
 EHD FROM THE TEE TO THE RANGE- SEE TABLE 402.4(13) FBC
 FG (PASTED ON THE PLAN SHEET) AND SECTION G2413.4.1 FBC
 RES.
  
 2) P-2: TYPICALLY, THERE IS A SCHEDULE 40 METALLIC
 SUPPLY RISER IS AT THE METER PRIOR TO THE TRANSITION TO
 CSST (SEE YOUR METER DETAIL ON THE PLAN SHEET). PLEASE
 PROVIDE THE SIZE AND LENGTH OF THE SCHEDULE 40 RISER-
 SECTION G2413.2 FBC RES.
  
 3) SUBMIT A GAS SUB-PERMIT APPLICATION- SECTION 105.1
 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 CCOLE@WPB
  