Plan Review Notes For Permit 20120019 |
Permit Number |
20120019 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2020-12-18 15:19:35 | THERE IS A NOTE BOX ON SHEET P 100 THAT NO PLUMBING | | CONTRACTOR OR PLUMBING WORK WILL BE DONE UNDER THIS | | PERMIT. | | | | FOR INFORMATIONAL PURPOSES THE FIRE PROVISO WAS | | PROVIDED TO THE FIRE PUMP ROOM WHEN APPLICABLE TO THE | | FOUNDATION WORK. | | | | | | FIRE PROVISO: | | | | THE FIRE PUMP ROOM IS REQUIRED TO HAVE A FLOOR DRAIN. | | | | PER NFPA 20: | | | | 4.12.7* DRAINAGE. | | 4.12.7.1 FLOORS SHALL BE PITCHED FOR ADEQUATE DRAINAGE | | OF ESCAPING | | WATER AWAY FROM CRITICAL EQUIPMENT SUCH AS THE PUMP, | | DRIVER, CONTROLLER, AND SO FORTH. | | 4.12.7.2 THE PUMP ROOM OR PUMP HOUSE SHALL BE PROVIDED | | WITH A FLOOR DRAIN THAT WILL DISCHARGE TO A FROST-FREE | | LOCATION. | | | | | | PLEAE ENSURE COMPLIANCE WHEN APPLICABLE TO THE | | FOUNDATION WORK. | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | |
|