Plan Review Notes
Plan Review Notes For Permit 20120003
Permit Number 20120003
Review Stop B
Sequence Number 3
Notes
Date Text
2021-03-03 10:54:01WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20120003
 ADD: 2400 S DIXIE HWY.
 CONT: BUTLER CONSTRUCTION
 TEL: 561-832-9700
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: WED. MARCH 03RD/2021
 ACTION: DENIED
  
 1-2) COMPLIED.
  
 3) SHEET A101:
 3A) COMPLIED.
  
 3B) SEMI-COMPLIED. A NEW SHEET SHOWING THE BASEMENT
 STAIR, HANDRAIL AND ENCLOSURE. THE BASEMENT PORTION OF
 THE STAIRWAY IS AN OPEN STAIR, NO ENCLOSURE. EXIT
 ACCESS STAIRWAYS ARE ALLOWED IN THE 2017 FBC-B SECTION
 1019.3. THE SUBMITTED PLAN DOES NOT SHOW A GUARDRAIL,
 IT WAS ASSUMED THERE WAS A WALL AND GUARDRAILS WERE NOT
 REQUIRED. GUARDRAILS MUST SHOW COMPLIANCE WITH THE 2017
 FBC-B SECTIONS 1015.3 & 11015.4.
  
 1ST ROUND OF COMMENTS. THERE IS NO INFORMATION ON THE
 STAIRWAY AND HANDRAILS IF THEY ARE EXISTING AND THE
 RISE / RUN OF THE STAIRS NOR IF THERE IS ANY HANDRAILS.
 SEE THE 2017 FBC-EXISTING BUILDING CODE SECTION
 1012.4.2.
  
 4) SHEET A102 THE PROPOSED 1ST FLOOR PLAN:
 4A)2ND REQUEST. EGRESS DOORWAYS MUST SHOW THEY ARE
 ACCESSIBLE, THE INTERIOR AND EXTERIOR GRADE ARE IN
 COMPLIANCE WITH THE 2017 ACCESSIBILITY CODE SECTION
 303.2 VERTICAL OR 303.3 BEVELED, CHANGE IN LEVEL GRADE.
 1ST ROUND OF COMMENTS. THE PLANS DO NOT SHOW WHICH
 EGRESS DOORS ARE ACCESSIBLE EXITS. 2017
 FBC-ACCESSIBILITY CODE SECTION 207.1 MEANS OF EGRESS
 SHALL COMPLY WITH SECTION 1003.2.13 OF THE
 INTERNATIONAL BUILDING CODE (2000 EDITION AND 2001
 SUPPLEMENT) OR SECTION 1007 OF THE INTERNATIONAL
 BUILDING CODE (2003 EDITION).
  
 2003 IBC-B 1007.1 WHERE MORE THAN ONE MEANS OF EGRESS
 IS REQUIRED BY SECTIONS 1014.1 OR 1018.1 FROM ANY
 ACCESSIBLE SPACE, EACH ACCESSIBLE PORTION OF THE SPACE
 SHALL BE SERVED BY NOT LESS THAN TWO MEANS OF EGRESS.
  
 4B) SEE NOTE ABOVE 2ND REVIEW. THE PLANS DO NOT SHOW
 COMPLIANCE WITH SECTION 1007.1.1 OF THE 2017 FBC-B, TWO
 EXITS AND OR EXIT ACCESS DOORWAYS.
 WHERE 2 EXIT OR EXIT ACCESS DOORWAYS ARE REQUIRED FROM
 ANY PORTION OF THE EXIT ACCESS, THEY SHALL BE PLACED A
 DISTANCE APART EQUAL TO NOT LESS THAN ? THE OVERALL
 MAXIMUM OVERALL DIAGONAL DIMENSION OF THE BUILDING OR
 AREA TO BE SERVED MEASURED IN A STRAIGHT LINE BETWEEN
 THEM.
 EXCEPTION BUILDINGS EQUIPPED THROUGHOUT WITH AN
 AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH SECTION
 903.3.1.1 OR 903.3.1.2, THE SEPARATION DISTANCE SHALL
 NOT BE LESS THAN 1/3RD OVERALL DIAGONAL DIMENSION OF
 THE BUILDING OR AREA TO BE SERVED MEASURED IN A
 STRAIGHT LINE BETWEEN THEM.
  
 4C)2ND REVIEW. SEE COMMENT 3B.
 1ST ROUND OF COMMENTS. PLEASE REVIEW THE STAIRWAY THAT
 LEADS FORM THE BASEMENT. THE 2017 FBC-B SECTION 1019.3
 WOULD REQUIRE THE STAIRWAY TO BE ENCLOSED WITH A SHAFT
 ENCLOSURE CONSTRUCTED IN ACCORDANCE WITH 713. DOORS
 WILL NEED TO SHOW COMPLIANCE WITH 713.7 & 716 FOR FIRE
 BARRIER. DOORS SHALL BE SELF OR AUTOMATIC CLOSING BY
 SMOKE DETECTION IN ACCORDANCE WITH 716.5.9.3.
  
 4D) BUILDING PROVISO: THE PROPOSED FLOOR PLAN SHOWS A
 NEW 602 SQ. FT. WALK IN COOLER. PLEASE NOTE WALK IN
 COOLERS REQUIRE A SEPARATE PERMIT, REVIEW AND
 ASSOCIATED FEES. THEY ARE ALSO PART OF THE COMPONENTS
 AND CLADDING OF THE BUILDING AND REQUIRE PRODUCT
 APPROVALS. 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA
 DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE
 61G20-3.005, RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY
 OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE
 PRODUCT APPROVALS: (31)(G) EXTERIOR COOLER, FREEZERS.
 THE 602 SQ. FT. COOLERS WILL ALSO NEED TO SHOW
 COMPLIANCE WITH THE 2017 FBC-B SECTION 2603.4.1.2 AND
 2603.4.1.3.
  
 4E) THE PLAN INDICATES THERE IS 110 INDOOR SEATS. THE
 FLOOR PLAN DOES NOT SHOW ANY ACCESSIBLE SEATING. PLEASE
 SHOW COMPLIANCE WITH THE FOLLOWING ACCESSIBILITY
 REQUIREMENTS:
  
 4E)(1)SEMI-COMPLIED. 226.1 WHERE DINING SURFACES ARE
 PROVIDED FOR THE CONSUMPTION OF FOOD OR DRINK, AT LEAST
 5 PERCENT OF THE SEATING SPACES AND STANDING SPACES AT
 THE DINING SURFACES SHALL COMPLY WITH 902.
 110X0.05= 6 ACCESSIBLE SEATS. THE PROBLEM IS THE BAR
 AREA SEATING.
  
 4E)(2) SEMI-COMPLIED. THE PROBLEM IS THE BAR AREA
 SEATING. 226.2 DISPERSION. DINING SURFACES AND WORK
 SURFACES REQUIRED TO COMPLY WITH 902 SHALL BE DISPERSED
 THROUGHOUT THE SPACE OR FACILITY CONTAINING DINING
 SURFACES AND WORK SURFACES.
  
 4E)(3) SEMI-COMPLIED, THE PROBLEM IS THE BAR AREA
 SEATING. 206.2.5 206.2.5 RESTAURANTS AND CAFETERIAS. IN
 RESTAURANTS AND CAFETERIAS, AN ACCESSIBLE ROUTE SHALL
 BE PROVIDED TO ALL DINING AREAS, INCLUDING RAISED OR
 SUNKEN DINING AREAS, AND OUTDOOR DINING AREAS.
  
 4E)(4) SEMI-COMPLIED, THE PROBLEM IS THE BAR AREA
 SEATING. 902.1 .DINING SURFACES AND WORK SURFACES SHALL
 COMPLY WITH 902.2 AND 902.3. ADVISORY 902.1 GENERAL.
 DINING SURFACES INCLUDE, BUT ARE NOT LIMITED TO, BARS,
 TABLES, LUNCH COUNTERS, AND BOOTHS.
  
 4E)(5)(1) COMPLIED. 902.2 CLEAR FLOOR OR GROUND SPACE.
 A CLEAR FLOOR SPACE COMPLYING WITH 305 POSITIONED FOR A
 FORWARD APPROACH SHALL BE PROVIDED. KNEE AND TOE
 CLEARANCE COMPLYING WITH 306 SHALL BE PROVIDED.
  
 4E)(5)(2) SEMI-COMPLIED ,THE PROBLEM AREA IS THE BAR
 AREA SEATING. PLEASE PROVIDE A CUT SECTION THROUGH THE
 ACCESSIBLE SEATING AREA AT THE BAR TO SHOW COMPLIANCE
 WITH 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND WORK
 SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 4F) 2ND REQUEST, THE DESIGNER OF RECORD SHOW THE
 MANEUVERING CLEARANCES ON THE WRONG SIDE OF THE DOOR.
 PLEASE LOOK AT DOORS 12 & 13 MISSING MANEUVERING
 CLEARANCES AT DOORS. ACCESS. CODE 404.2.4 MANEUVERING
 CLEARANCES. DOORS.
 MINIMUM MANEUVERING CLEARANCES AT DOORS AND GATES SHALL
 COMPLY WITH 404.2.4. MANEUVERING CLEARANCES SHALL
 EXTEND THE FULL WIDTH OF THE DOORWAY AND THE REQUIRED
 LATCH SIDE FOR SIDE CLEARANCE.
  
 4G) COMPLIED.
  
 5) SHEET A104 ENLARGES RESTROOM FLOOR PLAN &
 ELEVATIONS:
 5A) 2ND REQUEST. PLEASE BE AWARE ONE NOTE WAS ADDED
 CERAMIC TILE WAINSCOT WAS ADDED FOR ALL ELEVATIONS. THE
 HEIGHT OF THE WAINSCOT IS NOT GIVEN AND IN THE FINISH
 SCHEDULE THE WALL SCHEDULE STILL STATES TO PAINT THE
 DRYWALL WALLS.
 1ST ROUND COMMENT. THERE IS NO FINISHES SHEET FOR
 FLOORS, WALLS & CEILINGS. SHEET A104 IN THE SOUTH
 ELEVATION OF THE MENS RESTROOM STATES LINE OF SMOOTH,
 HARD, NONABSORBENT SURFACES ABOVE THE FLOOR. 2017 FBC-B
 1210.2.2. WALLS & PARTITIONS. THIS COMMENT IS A RESULT
 OF THE BUILDING OFFICIAL INTERPRETATION. IN RESTROOMS
 EPOXY PAINT IS NO LONGER CONSIDERED A SMOOTH HARD,
 NON-ABSORBENT SURFACE.
  
 5A)(1) SEMI-COMPLIED. 1210.2.2 WALLS & PARTITIONS
 WITHIN 2 FEET OF SERVICE SINKS, URINALS, AND WATER
 CLOSETS SHALL HAVE A SMOOTH, HARD, NON-ABSORBENT
 SURFACE TO A HEIGHT OF NOT LESS THAN 4 FEET ABOVE THE
 FLOOR, EXCEPT FOR STRUCTURAL ELEMENTS, THE MATERIAL
 USED IN SUCH WALLS SHALL BE OF A TYPE THAT IS NOT
 ADVERSELY AFFECTED BY MOISTURE.
  
 5B) COMPLIED. LOCATION OF THE BABY CHANGING TABLE.
  
 5C) 2ND ROUND OF COMMENTS. THE PLANS SHOW THE 40 INCHES
 TO THE BOTTOM OF THE MIRROR, NOT THE REFLECTIVE
 SURFACE.
 1ST ROUND OF COMMENTS. IN BOTH THE MENS AND WOMENS
 RESTROOMS THE HEIGHT ABOVE THE FLOOR IS NOT GIVEN, SHOW
 COMPLIANCE WITH 603.3 MIRRORS. 2017 FBC-ACCESSIBILITY
 CODE. MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS
 SHALL BE INSTALLED WITH THE BOTTOM EDGE OF THE
 REFLECTING SURFACE 40 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND.
  
 5D-F) COMPLIED.
  
 5G) 2ND ROUND OF COMMENTS. ALL PARTS OF 5G. TO ANSWER
 CODE REQUIREMENTS YOU CAN NOT RECITE THE CODE. 2017
 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION 107.2.1. W.P.B.
 ADMINISTRATIVE CODE/2017 DRAWINGS & SPECIFICATIONS
 SHALL CONTAIN INFORMATION, IN THE FORM OF NOTES OR
 OTHERWISE, AS TO THE QUALITY OF MATERIALS, WHERE
 QUALITY IS ESSENTIAL TO CONFORMITY WITH THE TECHNICAL
 CODES. SUCH INFORMATION SHALL BE SPECIFIC TO THE
 TECHNICAL CODES "CODE SECTIONS SHALL NOT BE CITED AS A
 WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 1ST ROUND OF COMMENTS. WHAT DETAILS FOR ACCESSIBILITY
 WERE NOT PROVIDED AND OR EXCEPTION ARE FOR DRINKING
 FOUNTAINS.
 5G)(1) 602.2 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE
 COMPLYING WITH 305, POSITIONED FOR A FORWARD APPROACH,
 AND KNEE AND TOE CLEARANCE COMPLYING WITH 306 SHALL BE
 PROVIDED.
  
 5G)(2) SPOUT OUTLETS/ DRINKING FOUNTAINS. 2017 ACCESS.
 CODE. SPOUT OUTLETS SHALL COMPLY WITH:
 602.4 SPOUT HEIGHT. 36 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND FOR WHEELCHAIR BOUND INDIVIDUALS.
 602.7 SPOUT HEIGHT FOR THE STANDING PERSONS SHALL BE
 BETWEEN 38 TO 43 INCHES ABOVE FINISH FLOOR.
  
 5G)(3) PROTRUDING OBJECTS 307.2 PROTRUSION LIMITS
 307.2. OBJECTS WITH LEADING EDGES MORE THAN 27 INCHES
 AND NOT MORE THAN 80 INCHES ABOVE THE FLOOR SHALL NOT
 PROTRUDE MORE THAN 4 INCHES HORIZONTALLY INTO THE
 CIRCULATION PATH.
  
 6) COMPLIED.
  
 7) THE COMPONENT AND CLADDING PRESSURES FOUND ON S302
 FOR THE ROOF AND WALL ZONES ARE GIVEN IN VASD. THANK
 YOU. THE WALL PRESSURES ARE UP TO 9.0 LBS. LOW PER PSF.
 WE ARE TAKING THE PRESSURES FROM AN ENGINEERS SPREAD
 SHEET FOR WALL COMPONENTS & CLADDING AND COMPARING TO
 ASCE 7-10 FIGURE 30.5.1, AS WELL AS THE PRESSURES FOUND
 IN THE 2017 RESIDENTIAL CODE THE SIMPLIFIED TABLE
 R301.2(2).
  
 8) BUILDING PROVISO: WELDED OR BOLTED CONNECTIONS. THE
 CONTRACTOR IS REQUIRED TO PROVIDE WELD PROCEDURE
 SPECIFICATIONS & WELDER OPERATOR PERFORMANCE
 QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED
 STANDARDS AT TIME OF INSPECTION FOR FIELD WIELDING, ON
 THE JOB-SITE WIELDING. THIRD PARTY CERTIFICATION WILL
 BE REQUIRED. REPORTS SUBMITTED TO BUILDING INSPECTOR AT
 TIME OF FRAMING INSPECTION.
 2017 FBC-B 2204.1 WELDING
 1. WELD PROCEDURES SPECIFICATIONS
 2. QUALIFICATIONS OF WELDING PERSONAL
 2017 FBC-B 2204.2 BOLTING.
 IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED,
 PLEASE CONTACT THE CHIEF BUILDING INSPECTOR KEN CONRAD
 AT 561-805-6666.
  
 9) BUILDING PROVISO/ DEFERRED SUBMITTALS: 2017 FBC-B
 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1
 COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3
 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS, MULLIONS.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, WALL LOUVERS.
 (D) ROOFING PRODUCTS AND ASSEMBLIES, LIGHTWEIGHT
 CONCRETE INSULATION, ROOF TOP CURBS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 10) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE
 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING (SHOP
 DRAWING STAMP OF APPROVAL) BY THE DESIGNER OF RECORD
 PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC.
  
 11) BUILDING PROVISO/ DEFERRED SUBMITTALS: IDENTIFY
 GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE PRODUCT
 APPROVAL BEFORE SUBMITTING TO DESIGNER OF RECORD AND
 BEFORE SUBMISSION TO THE BUILDING DEPARTMENT. FOR ALL
 PRODUCTS WITH GLAZING, PLEASE IDENTIFY THE OPENING
 WIDTH & HEIGHT, TYPE OF GLAZING, MULLION SIZE, LENGTH
 IF UNREINFORCED OR REINFORCED INFORMATION IF REQUIRED,
 ATTACHMENTS AND ASSOCIATE PRESSURES FOR EACH OPENING
 SIZE. 2017 FBC-B 1405.13.1 INSTALLATION. WINDOWS AND
 DOORS SHALL BE INSTALLED IN ACCORDANCE WITH APPROVED
 MANUFACTURERS INSTRUCTIONS. FASTENER SIZE AND SPACING
 SHALL BE PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE
 CALCULATED BASED ON MAXIMUM LOADS AND SPACING USED IN
 THE TESTS.
  
 12) BUILDING PROVISO/ DEFERRED SUBMITTALS: THE ROOF TOP
 A/C STAND PRODUCT APPROVALS, TO BE REVIEWED BY THE
 DESIGNER OF RECORD. PLEASE IDENTIFY THE FOLLOWING
 REQUIREMENTS CALCULATING THE AREA (SIDE VIEW) OF THE
 ROOF TOP COMPRESSORS, CONFIGURATION ON STAND, THE MEAN
 ROOF HEIGHT OF THE STAND AND COMPRESSORS, WEIGHT,
 CIRCLED THE DESIGN PARAMETERS IN THE TABLES, ANCHORS
 AND UPLIFT VERSES MOMENT FOR THE UNIT TO THE STAND AND
 THE STAND TO THE ROOF. THE PRODUCT APPROVAL IS TO BE
 REVIEWED BY THE DESIGNER OF RECORD, APPROVED BEFORE
 SUBMISSION TO THE BUILDING DEPARTMENT.
  
 13) 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF
 THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 14) BUILDING PROVISO/ DEFERRED SUBMITTALS: ROOF TOP &
 EQUIPMENT MAINTENANCE LADDER SHOP DRAWINGS TO BE
 SUBMITTED TO DESIGNER OF RECORD FOR REVIEW AND SHOP
 DRAWING STAMP OF APPROVAL BEFORE BEING SUBMITTED TO THE
 BUILDING DEPARTMENT. 2017 FBC-M 306.5 EQUIPMENT AND
 APPLIANCES ON ROOFS.
  
 15) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/
 RETIRED.
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  