Plan Review Notes
Plan Review Notes For Permit 20120003
Permit Number 20120003
Review Stop P
Sequence Number 2
Notes
Date Text
2021-03-18 11:45:3803/18/21 2ND PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. PLEASE PROVIDE A CIVIL DRAWING SHOWING THE GREASE
 INTERCEPTOR'S LOCATION AND SIZE PER THE WPB AMENDMENTS
 TO THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 2. ON THE COVER SHEET, PLEASE PROVIDE UNDER CODE DATA
 THE YEAR, PLUMBING AND ACCESSIBILITY REFERENCED USED,
 AS WELL AS THE GAS PER THE WPB AMENDMENTS TO THE FBC
 SEC. 101.4 REFERENCED CODES.
  
 3. ON P0.1 UNDER PLUMBING FIXTURES;
  
 A. NOTE THREE HAS A TABLE BUT NO YEAR REFERENCE OR CODE
 TYPE. PLEASE CORRECT PER THE WPB AMENDMENTS TO THE FBC
 SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 B. NOTE FOUR REFERS TO WALL-HUNG PLUMBING FIXTURES, AND
 CODE REFERENCE IS NOT FOUND. PLEASE CLARIFY AND OR
 CORRECT IT PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 C. NOTE FIVE HAS UNDER LAVATORIES EXPOSED PIPING, AND
 IT SHOULD BE 2017 FBC ACC SEC. 606.5; PLEASE CORRECT
 PER THE 2017 FBC ACC SEC. 606.5.
  
 4. ON SHEET P0.2;
  
 A. IN DETAIL TEN, THERE ARE TANK-LESS WATER HEATERS AND
 NO SPECIFICATIONS PROVIDED; SOME UNITS HAVE
 CONDENSATION IN THEIR SYSTEMS FOR THE WATER HEATING.
 PLEASE PROVIDE MANUFACTURER SPECIFICATIONS OR NOTE THE
 CONDENSATE TO AN APPROVED DISPOSAL PLACE PER THE 2017
 FBC M 307.2.1 CONDENSATE DISPOSAL.
  
 B. PLEASE PROVIDE DETAIL FOR THE EQUIPMENT AND FIXTURES
 UTILIZED FOR THE STORAGE, PREPARATION, AND HANDLING AND
 SHOW THE MULTIPLE-COMPARTMENT SINK THAT SHALL DISCHARGE
 INDEPENDENTLY TO A WASTE RECEPTOR PER THE 2017 PBC SEC.
 802.1.2 FLOOR DRAINS IN FOOD STORAGE AREAS.
  
 5. ON SHEET P0.3, THE SUMP PUMP SHALL DISCHARGE THROUGH
 A CONNECTION THAT SHALL BE MADE THROUGH A WYE FITTING
 INTO THE TOP OF THE DRAINAGE PIPING PER THE 2017 FBC P
 712.3.5. PUMP CONNECTION TO THE DRAINAGE SYSTEM.
  
 6. ON SHEET P0.4;
  
 A. ON THE RECIRCULATION SYSTEM WILL REQUIRE INSULATION,
 AND PLEASE PROVIDE SIZE, DETAIL, AND VERBIAGE FOR
 APPLICATION PER THE 2017 FBC EC SEC. C403.2.10.
  
 B. THE WATER CIRCULATION SYSTEM SHALL BE A DEDICATED
 RETURN PIPE, PER THE 2017 FBC EC SEC. C404.6.1
 CIRCULATION SYSTEMS.
  
 C. THE RECIRCULATION SYSTEM SHALL BE THE NEAREST SOURCE
 OF HEATED WATER, AND THE FIXTURE SUPPLY PIPE'S
 TERMINATION SHALL BE PER THE 2017 TABLE 404.5.1.
  
 D. ON THE HOSE BIBBS, THE ROOF PLAN SHOWS TWO, AND ONLY
 ONE IS SHOWN ON THE WATER RISER DIAGRAM. PLEASE CORRECT
 PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 E. ON THE ISOMETRIC, YOU SHOW DOUBLE CHECK VALVES FOR
 THE ICE MAKER AND COFFEE MAKER THAT SHALL BE EQUIPPED
 WITH AN IN-LINE VACUUM BREAKER THAT COMPLIES WITH ASSE
 1024 PER THE 2017 FBC SEC. 608.13.10, PLEASE PUT A NOTE
 ON SCHEDULE, AND IF THERE ARE BEVERAGE, THEY SHALL BE
 EQUIPPED WITH AN IN-LINE VACUUM BREAKER THAT COMPLIES
 WITH ASSE 1022 PER THE 2017 FBC SEC. 608.16.1.
  
 6. ON SHEET P1.1, THE SERVICE SINK AND MOP SINK
 SURROUNDING WALLS SHALL BE NON-ABSORBENT SURFACE, AND
 PAINT IS NOT ACCEPTABLE PER THE AHJ AND ACCORDING TO
 THE 2017 FBC BUILDING 1210.2.2 AND 2017 FBC SEC. P
 310.3. PLEASE MAKE A NOTE ON THIS SHEET.
  
 PLEASE REFER TO THE BUILDING COMMENT FOR THE FIXTURE
 WALL IN ALL RESTROOMS.
  
 7. ON SHEET A104, PLEASE GIVE DIMENSIONS FOR FIXTURE
 CLEARANCES PER FLORIDA BUILDING CODE AND FLORIDA
 ACCESSIBILITY CODE (DRINKING FOUNTAIN, TOILET, LAVS,
 AND URINAL).
  
 A. FOR THE DRINKING, PLEASE PROVIDE DRAWINGS AND
 DETAILS SHOWING: THAT SHOWS THE KNEE AND TOE
 CLEARANCES, SPOUT HEIGHTS, SPOUT LOCATIONS PER THE 2017
 FBC ACC SEC. 306, 307, & 602.2, COMPLIANCE WITH 2017
 FBC ACC SEC. 307.2 PROTRUSION LIMITS.
  
 B. ON LAVS IN THE OPEN RESTROOM FOR MEN'S AND WOMAN'S,
 PLEASE SHOW CLEAR FLOOR SPACE FOR A FORWARD APPROACH,
 AND IT SHALL COMPLY PER THE 2017 FBC ACC SEC. 602.2.
  
 C. IN THE MEN'S RESTROOM FOR THE URINAL, PLEASE SHOW
 CLEAR FLOOR SPACE FOR A FORWARD APPROACH, AND IT SHALL
 COMPLY PER THE 2017 FBC ACC SEC. 602.2.
  
 D. THE WATER CLOSETS SHOW THE FLUSH VALVE'S LOCATION ON
 THE OPPOSITE SIDE OF THE OPEN AREA. PLEASE MOVE PER THE
 2017 FBC SEC. 604.6 FLUSH CONTROLS.
  
 E. PLEASE SHOW THE URINAL HEIGHT OF 17" INCHES SHALL BE
 A MAXIMUM AND 13 1/2" INCHES PER THE 2017 FBC ACC. SEC.
 605.2
  
 F. PLEASE SHOT THE WALLS OR PARTITIONS THAT SHALL BEGIN
 AT A HEIGHT NOT GREATER THAN 12 INCHES FROM AND EXTEND
 NOT LESS THAN 60 INCHES ABOVE THE FINISHED FLOOR
 SURFACE PER THE 2017 FBC P 405.3.5.
  
 E. PLEASE SHOW THE TOILET PAPER DISPENSERS SHALL BE 7"
 INCHES MINIMUM AND 9" INCHES MAXIMUM IN FRONT OF THE
 WATER CLOSET MEASURED TO THE CENTERLINE OF DISPENSER
 PER THE 2017 FBC ACC SEC. 604.7.
  
 F. PEASE SHOWS THE HANDICAP CAP WATER CLOSET FLUSH
 CONTROL SHALL BE HAND OPERATED OR AUTOMATIC AND SHALL
 BE 36? INCHES MAXIMUM ABOVE THE FINISH FLOOR AND ON THE
 OPEN SIDE PER THE 2017 FBC ACC SEC. 604.9.5.
  
 G. PLEASE SHOW OR NOTE THAT THE DOOR HANDLE HARDWARE
 SHOULD BE NOTED ON BOTH SIDES OF THE DOOR PER THE 2017
 FBC ACC SEC. 404.2.7.
  
 H. PLEASE NOTE THAT TEMPERED WATER SHALL BE DELIVERED
 FROM LAVATORIES AND GROUP WASH FIXTURES LOCATED IN
 PUBLIC TOILET FACILITIES PROVIDED FOR CUSTOMERS,
 PATRONS, AND VISITORS. TEMPERED WATER SHALL BE
 DELIVERED THROUGH AN APPROVED WATER-TEMPERATURE
 LIMITING DEVICE THAT CONFORMS TO ASSE 1070 OR CSA
 B125.3 PER THE 2017 FBC SEC. 416.5 TEMPERED WATER FOR
 PUBLIC HAND-WASHING FACILITIES.
  
 I. PLEASE NOTE THAT ALL SEAT NEEDS TO BE OPEN FRONT,
 2017 FBC P 420.3 WATER CLOSET SEATS.
  
 K. THE MIRRORS NEED TO THE REFLECTIVE PART OF THE
 MIRROR AT 40" PER THE 2017 FBC ACC SEC. 603.3.
  
 L. ON THE ELEVATION DRAWING FOR MEN, RESTROOM THE GRAB
 BARS IN THE REAR WALL SHALL COMPLY WITH 2017 FBC SEC.
 604.5.2. PLEASE SHOW THE DIMENSIONS TO THE CENTER ON A
 HORIZONTAL VIEW.
  
 M. ON THE ELEVATION FOR THE DRAWING WOMAN'S, THE GRAB
 BARS ON THE SIDE SHALL COMPLY WITH 2017 FBC SEC.
 604.5.1. PLEASE SHOW THE DIMENSIONS TO THE CENTER ON A
 HORIZONTAL VIEW.
  
 PLEASE FEEL FREE TO CALL ME TO DISCUSS ANY COMMENTS OR
 CONCERNS ON THE ABOVE CORRECTION.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION,
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  