2020-12-04 15:45:25 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| |
| 1) THERE DOES NOT APPEAR TO BE A LIFE SAFETY PLAN. AS |
| THIS IS AN ASSEMBLY OCCUPANCY, A LIFE SAFETY PLAN IS |
| REQUIRED. |
| |
| PER NFPA 101, CH 12 12.4.1.4.3 LIFE SAFETY FLOOR PLANS. |
| LIFE SAFETY FLOOR PLANS OF EACH |
| LEVEL SHALL BE PROVIDED ? AS APPLICABLE ? WITH THE |
| FOLLOWING: |
| (1) OCCUPANT LOAD, EXIT LOCATION, EGRESS CAPACITY, MAIN |
| ENTRANCE/EXIT, HORIZONTAL EXITS, TRAVEL DISTANCE, AND |
| EXIT |
| DISCHARGE |
| |
| PLEASE PROVIDE DETAILS |
| |
| |
| 2) THERE IS A BASEMENT INDICATED AND AS THIS IS A NEW |
| ASSEMBLY/CHANGE OF OCCUPANCY AND THE BASEMENT HAS WALLS |
| AND STORAGE FIRE SPRINKLER PROTECTION IS REQUIRED. |
| |
| SEE FL BUILDING CODE 903.2.11.1.3 |
| |
| PLEASE REVIEW AND CORRECT OR PROVIDE APPLICABLE CODE |
| REFERNCES AND DETAILED NARRATIVE. |
| |
| |
| |
| 3) THERE IS STORAGE INDICATED IN THE BASEMENT. AS THIS |
| IS RESTURAUNT WITH POSSIBLE AEROSOL PRODUCTS, PLEASE |
| PROVIDE IN COMPLAINCE WITH THE BELOW CODE. |
| |
| PER NFPA 1 |
| |
| 61.3.4.2 FIRE PROTECTION ? BASIC REQUIREMENTS. |
| 61.3.4.2.1 STORAGE OF LEVEL 2 AND LEVEL 3 AEROSOL |
| PRODUCTS SHALL |
| NOT BE PERMITTED IN BASEMENT AREAS OF WAREHOUSES. [30B: |
| 6.4.2.1] |
| 61.3.4.2.1.1 STORAGE OF LEVEL 2 AND LEVEL 3 AEROSOL |
| PRODUCTS SHALL |
| BE PERMITTED AS PROVIDED FOR IN 6.3.3 OF NFPA 30B. |
| [30B: |
| 6.4.2.1.1] |
| |
| PLEASE PROVIDE DETAILS. |
| |
| |
| |
| 4) THE IS A STAIRWELL LEADING DOWN INTO THE BASEMENT |
| THAT MAY BE CONFUSED AS AN EXIT. |
| |
| PER NFPA 101, CH 7 MEANS OF EGRESS |
| |
| 7.10.8.3* NO EXIT. |
| 7.10.8.3.1 ANY DOOR, PASSAGE, OR STAIRWAY THAT IS |
| NEITHER AN EXIT NOR A |
| WAY OF EXIT ACCESS AND THAT IS LOCATED OR ARRANGED SO |
| THAT IT IS LIKELY TO |
| BE MISTAKEN FOR AN EXIT SHALL BE IDENTIFIED BY A SIGN |
| THAT READS AS |
| FOLLOWS: |
| NO |
| EXIT |
| |
| A.7.10.8.3 THE LIKELIHOOD OF OCCUPANTS MISTAKING |
| PASSAGEWAYS |
| OR STAIRWAYS THAT LEAD TO DEAD-END SPACES FOR EXIT |
| DOORS |
| AND BECOMING TRAPPED GOVERNS THE NEED FOR EXIT SIGNS. |
| THUS, |
| SUCH AREAS SHOULD BE MARKED WITH A SIGN THAT READS AS |
| FOLLOWS: |
| NO EXIT |
| SUPPLEMENTARY IDENTIFICATION INDICATING THE CHARACTER |
| OF |
| THE AREA, SUCH AS TO BASEMENT, STOREROOM, LINEN |
| CLOSET, OR THE LIKE, IS PERMITTED TO BE PROVIDED. |
| |
| PLEASE CORRECT AND PROVIDE FOR THE APPLICABLE SIGNANGE. |
| |
| |
| 5) THERE ARE INDICATIONS OF OUTDOOR SMOKERS. AS THIS IS |
| LOCATED CLOSE TO RESIDENTIAL HOMES PLEASE PROVIDE HOW |
| THE SMOKE FROM THESE SMOKERS WILL BE CONTROLLED. |
| |
| PLEASE PROVIDE DETAILS. |
| |
| |
| 6) SHEET A 102 - THERE IS AN INDICATION OF WALK-IN |
| COOLERS WITH NO DETAIL |
| |
| PLEASE PROVIDE SPECIFIC DETAILS OF THESE COOLERS, |
| INCLUDING EXACT CONFIGURATION, DOORS, LIGHTING, EXITS, |
| EXIT HARDWARE. |
| |
| |
| 7) SHEET E 2.1 - THERE ARE INDICATION OF AN EXT SIGNS |
| OVER DOORS 12 & 13 THAT LEAD TO THE OUTDOOR ENCLOSED |
| SMOKER AREA. |
| |
| THERE IS ONE INSWING DOOR FROM THAT AREA. THE DOES NOT |
| APPEAR TO BE ANY EXIT SIGNAGE OVER THIS DOOR AND IT |
| NEEDS TO SWING IN PATH OF EXIT TRAVEL AND BE EQUIPPED |
| WITH EXIT HARDWARE. |
| |
| ADDITIONALLY, THE EXIT PATH IS REQUIRED TO BE |
| ILLUMINATED. |
| |
| PLEASE REVIW AND CORRECT. |
| |
| |
| 8) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| ABOVE. |
| |
| |
| 9) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| RE-SUBMITTAL OF THE ABOVE. |
| |
| |
| |
| PETER LEDUC |
| FIRE MARSHAL |
| 561-804-4709 |
| [email protected] |
| |