Plan Review Notes
Plan Review Notes For Permit 20120003
Permit Number 20120003
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2020-12-04 15:45:25THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE DOES NOT APPEAR TO BE A LIFE SAFETY PLAN. AS
 THIS IS AN ASSEMBLY OCCUPANCY, A LIFE SAFETY PLAN IS
 REQUIRED.
  
 PER NFPA 101, CH 12 12.4.1.4.3 LIFE SAFETY FLOOR PLANS.
 LIFE SAFETY FLOOR PLANS OF EACH
 LEVEL SHALL BE PROVIDED ? AS APPLICABLE ? WITH THE
 FOLLOWING:
 (1) OCCUPANT LOAD, EXIT LOCATION, EGRESS CAPACITY, MAIN
 ENTRANCE/EXIT, HORIZONTAL EXITS, TRAVEL DISTANCE, AND
 EXIT
 DISCHARGE
  
 PLEASE PROVIDE DETAILS
  
  
 2) THERE IS A BASEMENT INDICATED AND AS THIS IS A NEW
 ASSEMBLY/CHANGE OF OCCUPANCY AND THE BASEMENT HAS WALLS
 AND STORAGE FIRE SPRINKLER PROTECTION IS REQUIRED.
  
 SEE FL BUILDING CODE 903.2.11.1.3
  
 PLEASE REVIEW AND CORRECT OR PROVIDE APPLICABLE CODE
 REFERNCES AND DETAILED NARRATIVE.
  
  
  
 3) THERE IS STORAGE INDICATED IN THE BASEMENT. AS THIS
 IS RESTURAUNT WITH POSSIBLE AEROSOL PRODUCTS, PLEASE
 PROVIDE IN COMPLAINCE WITH THE BELOW CODE.
  
 PER NFPA 1
  
 61.3.4.2 FIRE PROTECTION ? BASIC REQUIREMENTS.
 61.3.4.2.1 STORAGE OF LEVEL 2 AND LEVEL 3 AEROSOL
 PRODUCTS SHALL
 NOT BE PERMITTED IN BASEMENT AREAS OF WAREHOUSES. [30B:
 6.4.2.1]
 61.3.4.2.1.1 STORAGE OF LEVEL 2 AND LEVEL 3 AEROSOL
 PRODUCTS SHALL
 BE PERMITTED AS PROVIDED FOR IN 6.3.3 OF NFPA 30B.
 [30B:
 6.4.2.1.1]
  
 PLEASE PROVIDE DETAILS.
  
  
  
 4) THE IS A STAIRWELL LEADING DOWN INTO THE BASEMENT
 THAT MAY BE CONFUSED AS AN EXIT.
  
 PER NFPA 101, CH 7 MEANS OF EGRESS
  
 7.10.8.3* NO EXIT.
 7.10.8.3.1 ANY DOOR, PASSAGE, OR STAIRWAY THAT IS
 NEITHER AN EXIT NOR A
 WAY OF EXIT ACCESS AND THAT IS LOCATED OR ARRANGED SO
 THAT IT IS LIKELY TO
 BE MISTAKEN FOR AN EXIT SHALL BE IDENTIFIED BY A SIGN
 THAT READS AS
 FOLLOWS:
 NO
 EXIT
  
 A.7.10.8.3 THE LIKELIHOOD OF OCCUPANTS MISTAKING
 PASSAGEWAYS
 OR STAIRWAYS THAT LEAD TO DEAD-END SPACES FOR EXIT
 DOORS
 AND BECOMING TRAPPED GOVERNS THE NEED FOR EXIT SIGNS.
 THUS,
 SUCH AREAS SHOULD BE MARKED WITH A SIGN THAT READS AS
 FOLLOWS:
 NO EXIT
 SUPPLEMENTARY IDENTIFICATION INDICATING THE CHARACTER
 OF
 THE AREA, SUCH AS TO BASEMENT, STOREROOM, LINEN
 CLOSET, OR THE LIKE, IS PERMITTED TO BE PROVIDED.
  
 PLEASE CORRECT AND PROVIDE FOR THE APPLICABLE SIGNANGE.
  
  
 5) THERE ARE INDICATIONS OF OUTDOOR SMOKERS. AS THIS IS
 LOCATED CLOSE TO RESIDENTIAL HOMES PLEASE PROVIDE HOW
 THE SMOKE FROM THESE SMOKERS WILL BE CONTROLLED.
  
 PLEASE PROVIDE DETAILS.
  
  
 6) SHEET A 102 - THERE IS AN INDICATION OF WALK-IN
 COOLERS WITH NO DETAIL
  
 PLEASE PROVIDE SPECIFIC DETAILS OF THESE COOLERS,
 INCLUDING EXACT CONFIGURATION, DOORS, LIGHTING, EXITS,
 EXIT HARDWARE.
  
  
 7) SHEET E 2.1 - THERE ARE INDICATION OF AN EXT SIGNS
 OVER DOORS 12 & 13 THAT LEAD TO THE OUTDOOR ENCLOSED
 SMOKER AREA.
  
 THERE IS ONE INSWING DOOR FROM THAT AREA. THE DOES NOT
 APPEAR TO BE ANY EXIT SIGNAGE OVER THIS DOOR AND IT
 NEEDS TO SWING IN PATH OF EXIT TRAVEL AND BE EQUIPPED
 WITH EXIT HARDWARE.
  
 ADDITIONALLY, THE EXIT PATH IS REQUIRED TO BE
 ILLUMINATED.
  
 PLEASE REVIW AND CORRECT.
  
  
 8) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 9) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  