2020-12-10 17:17:07 | 1ST REVIEW FBC-2017 GAS |
| PERMIT-2012003 |
| 12/10/2020 |
| |
| CODES IN EFFECT: |
| |
| FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) A GAS SUB PERMIT IS REQUIRED BY A LICENSED |
| CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS |
| TO THE FBC SEC. 105.1. |
| 2) SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS |
| METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE |
| OUTLET IN THE BUILDING AND/OR SYSTEM PER THE 2017 FBC |
| FUEL GAS SEC. 402.4.1 |
| 3) GAS APPLIANCES SHALL BE LISTED AND LABELED. THE |
| INSTALLATION MANUALS FOR ALL GAS APPLIANCES/EQUIPMENT |
| SHALL BE ONSITE AT THE TIME OF INSPECTION 2017 FBC FUEL |
| GAS SEC. 402.2 AND 301.3 |
| 4) SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE |
| PRESSURE REGULATORS. REGULATORS INSTALLED ON THE |
| EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR |
| INSTALLATION. 2017 FBC FUEL GAS SEC.410.1 |
| 5) GAS SHUTOFF VALVES FOR EACH APPLIANCE SHALL BE |
| INDICATED ON THE GAS ISOMETRIC. WPB AMENDMENTS TO THE |
| FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| 6) 1" IS SHOWN AFTER THE REQULATOR FOR THE SMOKERS AND |
| NOT 3/4" PLEASE CLARIFY |
| 7) SUBMIT MANUFACTURES SPECIFICATIONS FOR THE SMOKERS. |
| FBC FG SEC.305.1 |
| 8) THERE IS NO PIPE SIZE INDICATED ON THE EQUALIZER |
| OVERHEAD LINE INDICATED |
| 9) ALL FLEXIBLE CONNECTORS USED TO CONNECT GAS |
| APPLIANCES SHALL BE INSTALLED PER FLEXIBLE CONNECTORS |
| MANUFACTURES INSTALLATION INSTRUCTIONS |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |