Plan Review Notes
Plan Review Notes For Permit 20120003
Permit Number 20120003
Review Stop G
Sequence Number 1
Notes
Date Text
2020-12-10 17:17:071ST REVIEW FBC-2017 GAS
 PERMIT-2012003
 12/10/2020
  
 CODES IN EFFECT:
  
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) A GAS SUB PERMIT IS REQUIRED BY A LICENSED
 CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS
 TO THE FBC SEC. 105.1.
 2) SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS
 METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER THE 2017 FBC
 FUEL GAS SEC. 402.4.1
 3) GAS APPLIANCES SHALL BE LISTED AND LABELED. THE
 INSTALLATION MANUALS FOR ALL GAS APPLIANCES/EQUIPMENT
 SHALL BE ONSITE AT THE TIME OF INSPECTION 2017 FBC FUEL
 GAS SEC. 402.2 AND 301.3
 4) SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION. 2017 FBC FUEL GAS SEC.410.1
 5) GAS SHUTOFF VALVES FOR EACH APPLIANCE SHALL BE
 INDICATED ON THE GAS ISOMETRIC. WPB AMENDMENTS TO THE
 FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 6) 1" IS SHOWN AFTER THE REQULATOR FOR THE SMOKERS AND
 NOT 3/4" PLEASE CLARIFY
 7) SUBMIT MANUFACTURES SPECIFICATIONS FOR THE SMOKERS.
 FBC FG SEC.305.1
 8) THERE IS NO PIPE SIZE INDICATED ON THE EQUALIZER
 OVERHEAD LINE INDICATED
 9) ALL FLEXIBLE CONNECTORS USED TO CONNECT GAS
 APPLIANCES SHALL BE INSTALLED PER FLEXIBLE CONNECTORS
 MANUFACTURES INSTALLATION INSTRUCTIONS
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  