Plan Review Notes
Plan Review Notes For Permit 20120003
Permit Number 20120003
Review Stop E
Sequence Number 1
Notes
Date Text
2020-12-09 08:19:15ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PAGE E.1.1
  
 OUTLETS ON CIRCUITS D-13, AND A-17 NEED TO BE GFCI
 PROTECTED 210.8 (B) NFPA 70
  
 PAGE E.2.1
  
 EXIT IN BACK BY OLE HICKORY NEEDS AN EXIT SIGN, NFPA
 101 7.10.1.5.2
  
 PAGE E.3.1
  
 1200 AMPERE MDP SHALL COMPLY WITH 240.87 FOR ARC FLASH
 MITIGATION.