Plan Review Notes For Permit 20120003 |
Permit Number |
20120003 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2020-12-09 08:19:15 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | FLORIDA BUILDING CODE 2017 6TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | NFPA 70 2014 EDITION | | | | JAKE LEAHY BN, BU, PX | | ELECTRICAL PLANS EXAMINER II | | 561-805-6713 | | [email protected] | | | | PAGE E.1.1 | | | | OUTLETS ON CIRCUITS D-13, AND A-17 NEED TO BE GFCI | | PROTECTED 210.8 (B) NFPA 70 | | | | PAGE E.2.1 | | | | EXIT IN BACK BY OLE HICKORY NEEDS AN EXIT SIGN, NFPA | | 101 7.10.1.5.2 | | | | PAGE E.3.1 | | | | 1200 AMPERE MDP SHALL COMPLY WITH 240.87 FOR ARC FLASH | | MITIGATION. |
|